Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1) Remove the valve cap from liquid stop valve and gas stop valve.
2) Carry out forced cooling operation.
3) After 5 to 10 minutes, close the liquid stop valve with a hexagonal wrench.
4) After 2 to 3 minutes, close the gas stop valve and stop forced cooling operation.

Forced cooling operation

Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch.

Using the indoor unit’s remote controller

• Please read about the procedure in “Trial operation from remote controller” in 

the installation manual attached to the indoor unit. Please set the operation 
mode to “cooling”.

Using the outdoor unit forced cooling operation switch (with standby 
electricity saving function turned off)

Forced cooling operation can be performed when the outdoor unit forced cooling 
operation switch is pressed within around 3 minutes after power is supplied.
Push on  “

” (SW1) with a screwdriver.  (The operation will start.)

• Forced cooling operation will stop automatically after around 15 minutes.

To stop the operation, press the switch (SW1).

 CAUTION

• When pressing the switch, do not touch the terminal block. It has a high voltage, so doing so may cause electric shock.
• After closing the liquid stop valve, close the gas stop valve within 3 minutes, then stop the forced cooling operation.

Facility Setting (cooling at low outdoor 
temperature)

This function is designed for facilities such as equipment or computer rooms. It is never to be used in a residence or office 
where people occupy the space.

1) Cutting jumper 4 (J4) on the circuit board will expand the operation range down to –15°C. However it will stop if the outdoor 

temperature drops below –20°C and start back up once the temperature rises again.

 CAUTION

• If the outdoor unit is installed where the heat exchanger of the unit is exposed to direct wind, provide a windbreak wall.
• Intermittent noises may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings.
• Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used.

A humidifier might cause dew condensation from the indoor unit outlet vent.

• Cutting jumper 4 (J4) sets the indoor fan tap to the highest position. Notify the user about this.

Liquid 

stop valve

Gas 

stop valve

Service port

Valve cap

Close

Hexagonal 

wrench

Screwdriver

Push

Forced cooling 

operation 

switch (SW1)

The selective connector for standby electricity 

saving in use (with standby electricity saving 

function turned off)

Power supply 

terminal block

For RXS20/25/35 models

Cut J4 with nippers 

or a similar tools.

Summary of Contents for ARXS35L2V1B

Page 1: ...ion S rie split R410A Fran ais Montagehandleiding R410A Split systeem Nederlands Manual de instalaci n Serie Split R410A Espa ol Manuale d installazione Serie Multiambienti R410A Italiano R410A Manual...

Page 2: ...es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o pare...

Page 3: ...ce en A y es valorado positivamente por B de acuerdo con el Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e...

Page 4: ...rmal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper...

Page 5: ...om ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor...

Page 6: ...the stop valve cover Remove the screw on the stop valve cover Slide the lid downward to remove it How to attach the stop valve cover Insert the upper part of the stop valve cover into the outdoor uni...

Page 7: ...e foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2...

Page 8: ...rque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them full...

Page 9: ...x Choose heat insulation materials that will withstand this temperature 2 Be sure to insulate both the gas and liquid piping and to provide insulation dimensions as below 3 Use separate thermal insula...

Page 10: ...f charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve...

Page 11: ...3 Disconnect the selective connector for standby electricity saving 4 Turn on the main power supply CAUTION Before connecting or disconnecting the selective connector for standby electricity saving ma...

Page 12: ...n pressing the switch do not touch the terminal block It has a high voltage so doing so may cause electric shock After closing the liquid stop valve close the gas stop valve within 3 minutes then stop...

Page 13: ...block Observe the notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the connection wires to the terminal blo...

Page 14: ...R Outdoor CONDENSER Condenser DISCHARGE Discharge C7 C8 Capacitor DB1 DB3 Diode bridge FU1 FU2 FU3 Fuse FU4 Field fuse IPM Intelligent power module L Live L803 L804 Reactor M1C Compressor motor M1F Fa...

Page 15: ...a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit brea...

Page 16: ...3P360062 2C 2013 11 Copyright 2013 Daikin...

Reviews: