Outdoor Unit Installation

5.

Purging air and checking gas leakage

• When piping work is completed, it is necessary to purge the air and check for gas leakage.

 WARNING

• Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R32, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Use a vacuum pump for R32 or R410A exclusively. Using the same vacuum pump for different refrigerants may damage the 

vacuum pump or the unit.

• Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump adapter.)
• If refrigerant gas leaks, ventilate the area immediately. Toxic gas may be produced if refrigerant gas comes into contact with fire.
• Never directly touch any accidentally leaking refrigerant. This could result in severe wounds caused by frostbite.

• If using additional refrigerant, perform air purging from the refrigerant pipes 

and indoor unit using a vacuum pump, then charge additional refrigerant.

• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified 

tightening torque.

*1. Pipe length vs. vacuum pump run time.  

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe joint may exists.  

Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3)  Do vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa (–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not swing back.)*2

5) Remove caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90 degrees counterclockwise with a hexagonal wrench to open valve. 

Close it after 5 seconds, and check for gas leakage.
Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.  
After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port caps for the liquid and gas stop valves with a torque wrench at the specified torques.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

Gauge 
manifold

Compound 
pressure gauge

Pressure metre

Low-pressure 
valve

High-pressure 
valve 

Charging 
hoses

Vacuum pump

Valve caps

Service port

Liquid 
stop 
valve

Gas 
stop 
valve

3PEN386698-2K.book  Page 7  Thursday, February 2, 2017  5:52 PM

Summary of Contents for ARXM50M2V1B

Page 1: ...INSTALLATION MANUAL R32 Split Series Models RXJ50M2V1B RXM42M2V1B RXM50M2V1B RXM60M2V1B RXP50K3V1B RXP60K3V1B ARXM50M2V1B 3PEN386698 2K book Page 1 Thursday February 2 2017 5 52 PM ...

Page 2: ...udicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold...

Page 3: ...vamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifika...

Page 4: ...ndt modul F i henhold til Certifikat G Risikoklasse H Se også næste side 11 enligt A och godkänts av B enligt Certifikatet C i enlighet med den Tekniska Konstruktionsfilen D som positivt intygats av E Fastsatt modul F vilket också framgår av Certifikat G Riskkategori H Se även nästa sida 12 som det fremkommer i A og gjennom positiv bedømmelse av B ifølge Sertifikat C som det fremkommer i den Tekni...

Page 5: ...ксимално допустима температура TS TSmin Минимална температура от страната на ниското налягане L C TSmax Температура на насищане съответстваща на максимално допустимото налягане PS M C Охладител N Настройка на предпазното устройство за налягане P bar Фабричен номер и година на производство вижте табелката на модела 22 Maksimalus leistinas slėgis PS K bar Minimali maksimali leistina temperatūra TS T...

Page 6: ...nnections or wires Improper connections or securing of wires may result in abnormal heat build up or fire When wiring the power supply and connecting the wiring between the indoor and outdoor units position the wires so that the control box lid can be securely fastened Improper positioning of the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks ...

Page 7: ...erant circuit will be high please keep the inter unit wire away from copper pipes that are not thermally insulated This appliance is intended to be used by expert or trained users in shops in light industry and on farms or for commercial and household use by lay persons Sound pressure level is less than 70 dB A Provide a logbook and machine card In accordance with the applicable legislation it may...

Page 8: ...adio sets This is to prevent interference to images and sounds Noises may be heard even if they are more than 3m away depending on radio wave conditions 8 In coastal areas or other places with salty atmosphere of sulfate gas corrosion may shorten the life of the air conditioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NO...

Page 9: ...ant Failure to do so may result in reduced performance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is used Wrap the insulation pipe with the finishing tape from bottom to top Foot bolt hole centres 330 250mm from wall Stop valve ...

Page 10: ... Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional foot bases of at least 30mm in height under t...

Page 11: ...amage to the flare nuts and gas leakage After the piping work is finished after checking for gas leaks open the stop valves or the compressor might break down Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches A A Cut exactly at right angles Remove burrs Set exactly at the position shown below Flaring Die Check Flare s ...

Page 12: ...oint may exists Check all pipe joints and retighten nuts as needed then repeat steps 2 through 4 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that t...

Page 13: ...ing the refrigerant used This product contains fluorinated greenhouse gases Do not vent gases into the atmosphere Refrigerant type GWP value factory refrigerant charge of the product see unit name plate additional refrigerant amount charged in the field total refrigerant charge greenhouse gas emissions of the total refrigerant charge expressed as tonnes CO2 equivalent outdoor unit refrigerant cyli...

Page 14: ... stop forced cooling operation Forced cooling operation Using the indoor unit ON OFF switch Press the indoor unit ON OFF switch for at least 5 seconds The operation will start Forced cooling operation will stop automatically after around 15 minutes To stop the operation press the indoor unit ON OFF switch Using the indoor unit s remote controller 1 Press MODE button and select the cooling mode 2 P...

Page 15: ...es may be produced by the indoor unit due to the outdoor fan turning on and off when using facility settings Do not place humidifiers or other items which might raise the humidity in rooms where facility settings are being used A humidifier might cause dew condensation from the indoor unit outlet vent Cutting jumper 6 J6 sets the indoor fan tap to the highest position Notify the user about this WA...

Page 16: ...notes mentioned below when wiring to the power supply terminal block Precautions to be taken for power supply wiring CAUTION When connecting the wires to the terminal block using a single core wire be sure to perform curling Problems with the work may cause heat and fires If the stranded wires must be used make sure to use the round crimp style terminal for connection to the power supply terminal ...

Page 17: ...WITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FORCHARACTERISTICS REFERTOPCBINSIDEYOURUNIT FUSE S C LIMITSWITCH FG CONNECTOR FRAMEGROUND S L FLOATSWITCH H HARNESS S NPH PRESSURESENSOR HIGH H P LED V L PILOTLAMP LIGHTEMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHTEMITTINGDIODE SERVICEMONITORGREEN S PH HPS PRESSURESWITCH HIGH HIGHVOLTAGE HIGHVOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENTEYESEN...

Page 18: ...all amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner the system will restore the original operation mode when the circuit breaker is opened again 2 Test items Test items Symptom Check Indoor and outdoor...

Page 19: ...3PEN386698 2K book Page 1 Thursday February 2 2017 5 52 PM ...

Page 20: ...3P386698 2K 2016 12 Copyright 2015 Daikin 3PEN386698 2K book Page 1 Thursday February 2 2017 5 52 PM ...

Reviews: