11
English
Wiring
WARNING
• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical
shock, or fire.
• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the
terminal block.) Doing so may cause electric shock or fire.
• Be sure to install an earth leak detector. (One that can handle higher harmonics.)
(This unit uses an inverter, which means that it must be used an earth leak detector capable handling harmonics in order to
prevent malfunctioning of the earth leak detector itself.)
• Use an all-pole disconnection type breaker with at least 3mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.
• Do not turn ON the safety breaker until all work is
completed.
1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wire between the indoor
and outdoor units
so that the terminal
numbers match
. Tighten the terminal screws
securely. We recommend a flathead
screwdriver be used to tighten the screws.
Observe the notes mentioned below when wiring to the power supply terminal block.
Precautions to be taken for power supply wiring.
CAUTION
• When connecting the wires to the terminal block using a single core
wire, be sure to perform curling.
Problems with the work may cause heat and fires.
• If the stranded wires must be used, make sure to use the round
crimp-style terminal for connection to the power supply terminal
block. Place the round crimp-style terminals on the wires up to the
covered part and secure in place.
3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.
RXM-42
10A
15A
15A
15A
15A
ARXM-50
RXM-50
RXM-60
RXJ-50
Safety
breaker
Earth leakage
circuit breaker
Earth
Inter-unit wire
4-core 1.5mm² or more
H05RN
Firmly fix the wires with
the terminal screws.
Outdoor unit
Indoor
unit
Power
supply
50Hz 220-240V
Firmly fix the wires with
the terminal screws.
Power supply wire
3-core 2.5mm² or more
H05RN
Power supply
terminal block
Shape wires so
that the service lid
and stop valve
cover fit securely.
Service lid
Screw
Good
Stripping wire at terminal block
Stranded wire
Round crimp-style
terminal
Wrong
Good
Strip wire end
to this point.
Excessive strip length
may cause electrical
shock or leakage.
Wrong