Outdoor Unit
Si04-402A
154
Removal Procedure
5
Undo the hooks.
Pull and remove the
front panel.
The front panel has 4 hooks.
The fan motor is united with
the front panel.
3. Remove the fan motor.
The screw has reverse
winding.
1
Unscrew the washer-
fitted nut (M10) of the
propeller fan with a
spanner.
2
Remove the propeller
fan.
Align
mark of the
propeller fan with D-cut
section of the motor shaft
when reassembling.
Step
Procedure
Points