background image

6 Charging refrigerant

Installation manual

9

6 (A)RXF7 RXF50+6
RXP50~7 (A)RXM50+6 ARXM7
RXM42R5V1B
R32 split series
3P645642-1A – 2021.03

CAUTION

▪ Use the flare nut fixed to the unit.

▪ To  prevent  gas  leakage,  apply  refrigeration  oil  only  to

the inside of the flare. Use refrigeration oil for R32.

▪ Do NOT reuse joints.

1

Connect the liquid refrigerant connection from the indoor unit to
the liquid stop valve of the outdoor unit.

a

b

c

a

Liquid stop valve

b

Gas stop valve

c

Service port

2

Connect  the  gas  refrigerant  connection  from  the  indoor  unit  to
the gas stop valve of the outdoor unit.

NOTICE

It  is  recommended  that  the  refrigerant  piping  between
indoor  and  outdoor  unit  is  installed  in  a  ducting  or  the
refrigerant piping is wrapped with finishing tape.

5.3

Checking the refrigerant piping

5.3.1

To check for leaks

NOTICE

Do NOT exceed the unit's maximum working pressure (see
"PS High" on the unit name plate).

NOTICE

ALWAYS  use  a  recommended  bubble  test  solution  from
your wholesaler.

NEVER use soap water:

▪ Soap  water  may  cause  cracking  of  components,  such

as flare nuts or stop valve caps.

▪ Soap  water  may  contain  salt,  which  absorbs  moisture

that will freeze when the piping gets cold.

▪ Soap  water  contains  ammonia  which  may  lead  to

corrosion  of  flared  joints  (between  the  brass  flare  nut
and the copper flare).

1

Charge the system with nitrogen gas up to a gauge pressure of
at  least  200  kPa  (2  bar).  It  is  recommended  to  pressurize  to
3000 kPa (30 bar) in order to detect small leaks.

2

Check  for  leaks  by  applying  the  bubble  test  solution  to  all
connections.

3

Discharge all nitrogen gas.

5.3.2

To perform vacuum drying

DANGER: RISK OF EXPLOSION

Do NOT start the unit if it is vacuumed.

1

Vacuum the system until the pressure on the manifold indicates
−0.1 MPa (−1 bar).

2

Leave as is for 4-5 minutes and check the pressure:

If the pressure…

Then…

Does not change

There is no moisture in the
system. This procedure is
finished.

If the pressure…

Then…

Increases

There is moisture in the
system. Go to the next step.

3

Vacuum the system for at least 2 hours to a manifold pressure
of −0.1 MPa (−1 bar).

4

After  turning  the  pump  OFF,  check  the  pressure  for  at  least
1 hour.

5

If  you  do  NOT  reach  the  target  vacuum  or  CANNOT  maintain
the vacuum for 1 hour, do the following:

▪ Check for leaks again.
▪ Perform vacuum drying again.

NOTICE

Make  sure  to  open  the  stop  valves  after  installing  the
refrigerant  piping  and  performing  vacuum  drying.  Running
the  system  with  the  stop  valves  closed  may  break  the
compressor.

6

Charging refrigerant

6.1

About the refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R32

Global warming potential (GWP) value: 675

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

WARNING

▪ Do NOT pierce or burn refrigerant cycle parts.

▪ Do NOT use cleaning materials or means to accelerate

the  defrosting  process  other  than  those  recommended
by the manufacturer.

▪ Be  aware  that  the  refrigerant  inside  the  system  is

odourless.

WARNING

The  refrigerant  inside  the  unit  is  mildly  flammable,  but
normally  does  NOT  leak.  If  the  refrigerant  leaks  in  the
room  and  comes  in  contact  with  fire  from  a  burner,  a
heater, or a cooker, this may result in fire, or the formation
of a harmful gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room,  and  contact  the  dealer  where  you  purchased  the
unit.

Do  NOT  use  the  unit  until  a  service  person  confirms  that
the  part  from  which  the  refrigerant  leaked  has  been
repaired.

WARNING

NEVER  directly  touch  any  accidental  leaking  refrigerant.
This could result in severe wounds caused by frostbite.

Summary of Contents for ARXF50A5V1B

Page 1: ...plit series English Installation manual R32 split series ARXF50A5V1B ARXF60A5V1B ARXF71A5V1B RXF50B5V1B RXF60B5V1B RXF71A5V1B RXP50M5V1B RXP60M5V1B RXP71M5V1B ARXM50R5V1B ARXM60R5V1B ARXM71R5V1B RXM42R5V1B RXM50R5V1B RXM60R5V1B ...

Page 2: ...dosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Директиви с техните изменения Direktyvose su papildymais Direktīvās un to papildinājumos Smernice v platnom znení Değiştirilmiş halleriyle Yönetmelikler 01 02 03 04 as set out in A and judged positively by B according to th...

Page 3: ...lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídající maximá...

Page 4: ...ised installers WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable standard INFORMATION This document only describes installation instructions specific to t...

Page 5: ...he unit if it is vacuumed Charging refrigerant see 6 Charging refrigerant 49 WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the...

Page 6: ...SK OF ELECTROCUTION Make sure that the system is earthed properly Turn off the power supply before servicing Install the switch box cover before turning on the power supply Commissioning see 9 Commissioning 412 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT only the outd...

Page 7: ...s positioned at least 100 mm above the maximum expected level of snow If necessary construct a pedestal See 4 2 Mounting the outdoor unit 47 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is NOT affected by the snow If necessary install a snow...

Page 8: ...terial with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter Øp Insulation inner diameter Øi Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 10 mm 15 9 mm 5 8 16 20 mm 13 mm Øi Øi t Øp Øp If the temperature is higher than 30 C and the humidity ...

Page 9: ... for 4 5 minutes and check the pressure If the pressure Then Does not change There is no moisture in the system This procedure is finished If the pressure Then Increases There is moisture in the system Go to the next step 3 Vacuum the system for at least 2 hours to a manifold pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the tar...

Page 10: ...licable language and stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Quantity of fluorinated greenhouse gases of the total refrigerant charge expressed as tonnes CO2 equivalent f GWP Global warming potential NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of...

Page 11: ... ARXF50 71A 20 A a ARXM50 71R RXM50 60R 16 A RXM42R 13 A Earth leakage circuit breaker MUST comply with applicable legislation a Electrical equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 7 2 To connect the electrical...

Page 12: ... specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can be disabled if nece...

Page 13: ...LED V L Pilot lamp light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live Symbol Meaning L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes thro...

Page 14: ...CuT 9 5 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT RXP50M RXF50B ARXF50A b a c d f h g j1 j3 j2 k m m m m m n o e l i i M a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic e...

Page 15: ...2 7 CuT 12 7 CuT 6 4 CuT RXP60M RXP71M RXF60B RXF71A ARXF60A ARXF71A b a c d f h g j1 j3 j2 k m m m m m n M o e l i i i a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic expansion valve HPS High pressure switch automatic res...

Page 16: ...0 CuT 4 0 CuT 6 4 CuT 6 4 CuT 6 4 CuT l m j3 M n o e m m d c b a f h g j1 i i i j2 k ARXM71R a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic expansion valve HPS High pressure switch automatic reset h Muffler with filter M ...

Page 17: ... CuT 9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 12 7 CuT 12 7 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT j3 b a c d f h g j1 i i i 4 0 CuT 4 0 CuT 4 0 CuT j2 m m m n M o e l k RXM42R a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid rec...

Page 18: ......

Page 19: ......

Page 20: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P645642 1A 2021 03 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: