5 Piping installation

Installation manual

8

6 (A)RXF7 RXF50+6

RXP50~7 (A)RXM50+6 ARXM7

RXM42R5V1B

R32 split series

3P645642-1A – 2021.03

c

Drain plug

d

Hose (field supply)

To close the drain holes and attach the drain
socket

NOTICE

In cold areas, do NOT use a drain socket, hose and caps
(1,  2)  with  the  outdoor  unit.  Take  adequate  measures  so
that the evacuated condensate CANNOT freeze.

1

Install drain caps 1 and 2 (accessory). Make sure the edges of
the drain caps close off the holes completely.

a

b

a

Bottom frame

b

Drain cap

2

Install the drain socket.

a

c

b

b

b

a

a

a

Drain hole. Install a drain cap (2).

b

Drain hole. Install a drain cap (1).

c

Drain hole for drain socket

5

Piping installation

5.1

Preparing refrigerant piping

5.1.1

Refrigerant piping requirements

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping diameter:

Models

Liquid piping

Gas piping

ARXM71R

Ø9.5 mm (3/8")

Ø15.9 mm (5/8")

RXM42R

Ø6.4 mm (1/4")

Ø9.5 mm (3/8")

Other

Ø6.4 mm (1/4")

Ø12.7 mm (1/2")

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

9.5 mm (3/8")

12.7 mm (1/2")

Annealed (O)

≥0.8 mm

t

Ø

15.9 mm (5/8")

≥1 mm

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

5.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Pipe outer diameter

p

)

Insulation inner

diameter (Ø

i

)

Insulation thickness

(t)

6.4 mm (1/4")

8~10 mm

≥10 mm

9.5 mm (3/8")

10~14 mm

≥13 mm

12.7 mm (1/2")

14~16 mm

≥10 mm

15.9 mm (5/8")

16~20 mm

≥13 mm

Ø

i

Ø

i

t

Ø

p

Ø

p

If  the  temperature  is  higher  than  30°C  and  the  humidity  is  higher
than RH 80%, the thickness of the insulation materials should be at
least  20  mm  to  prevent  condensation  on  the  surface  of  the
insulation.

5.1.3

Refrigerant piping length and height
difference

What?

Distance

Maximum allowable pipe length

30 m

Minimum allowable pipe length

3 m

Maximum allowable height distance

20 m

5.2

Connecting the refrigerant piping

DANGER: RISK OF BURNING/SCALDING

CAUTION

▪ No  brazing  or  welding  on  site  for  units  with  R32

refrigerant charge during shipment.

▪ During installation of the refrigeration system, joining of

parts with at least one part charged shall be performed
taking  into  account  the  following  requirements:  inside
occupied spaces non permanent joints are not allowed
for  R32  refrigerant  except  for  site  made  joints  directly
connecting  the  indoor  unit  to  piping.  Site  made  joints
directly connecting piping to indoor units shall be of non
permanent type.

5.2.1

To connect the refrigerant piping to the
outdoor unit

Piping length.

 Keep field piping as short as possible.

Piping  protection.

  Protect  the  field  piping  against  physical

damage.

WARNING

Connect the refrigerant piping securely before running the
compressor. If the refrigerant piping is NOT connected and
the stop valve is open when the compressor is run, air will
be  sucked  in.  This  will  cause  abnormal  pressure  in  the
refrigeration cycle, which may result in equipment damage
and even injury.

Summary of Contents for ARXF50A5V1B

Page 1: ...plit series English Installation manual R32 split series ARXF50A5V1B ARXF60A5V1B ARXF71A5V1B RXF50B5V1B RXF60B5V1B RXF71A5V1B RXP50M5V1B RXP60M5V1B RXP71M5V1B ARXM50R5V1B ARXM60R5V1B ARXM71R5V1B RXM42R5V1B RXM50R5V1B RXM60R5V1B ...

Page 2: ...dosításaik rendelkezéseit z późniejszymi poprawkami 18 19 20 21 22 23 24 25 Directivelor cu amendamentele respective Direktive z vsemi spremembami Direktiivid koos muudatustega Директиви с техните изменения Direktyvose su papildymais Direktīvās un to papildinājumos Smernice v platnom znení Değiştirilmiş halleriyle Yönetmelikler 01 02 03 04 as set out in A and judged positively by B according to th...

Page 3: ...lämpötila TS TSmin Alhaisin matalapainepuolen lämpötila L C TSmax Suurinta sallittua painetta PS vastaava kyllästyslämpötila M C Kylmäaine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maximální přípustný tlak PS K bar Minimální maximální přípustná teplota TS TSmin Minimální teplota na nízkotlaké straně L C TSmax Saturovaná teplota odpovídající maximá...

Page 4: ...ised installers WARNING Make sure installation servicing maintenance repair and applied materials follow the instructions from Daikin and in addition comply with applicable legislation and are performed by qualified persons only In Europe and areas where IEC standards apply EN IEC 60335 2 40 is the applicable standard INFORMATION This document only describes installation instructions specific to t...

Page 5: ...he unit if it is vacuumed Charging refrigerant see 6 Charging refrigerant 49 WARNING The refrigerant inside the unit is mildly flammable but normally does NOT leak If the refrigerant leaks in the room and comes in contact with fire from a burner a heater or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the...

Page 6: ...SK OF ELECTROCUTION Make sure that the system is earthed properly Turn off the power supply before servicing Install the switch box cover before turning on the power supply Commissioning see 9 Commissioning 412 DANGER RISK OF ELECTROCUTION DANGER RISK OF BURNING SCALDING CAUTION Do NOT perform the test operation while working on the indoor units When performing the test operation NOT only the outd...

Page 7: ...s positioned at least 100 mm above the maximum expected level of snow If necessary construct a pedestal See 4 2 Mounting the outdoor unit 47 for more details In heavy snowfall areas it is very important to select an installation site where the snow will NOT affect the unit If lateral snowfall is possible make sure that the heat exchanger coil is NOT affected by the snow If necessary install a snow...

Page 8: ...terial with a heat transfer rate between 0 041 and 0 052 W mK 0 035 and 0 045 kcal mh C with a heat resistance of at least 120 C Insulation thickness Pipe outer diameter Øp Insulation inner diameter Øi Insulation thickness t 6 4 mm 1 4 8 10 mm 10 mm 9 5 mm 3 8 10 14 mm 13 mm 12 7 mm 1 2 14 16 mm 10 mm 15 9 mm 5 8 16 20 mm 13 mm Øi Øi t Øp Øp If the temperature is higher than 30 C and the humidity ...

Page 9: ... for 4 5 minutes and check the pressure If the pressure Then Does not change There is no moisture in the system This procedure is finished If the pressure Then Increases There is moisture in the system Go to the next step 3 Vacuum the system for at least 2 hours to a manifold pressure of 0 1 MPa 1 bar 4 After turning the pump OFF check the pressure for at least 1 hour 5 If you do NOT reach the tar...

Page 10: ...licable language and stick it on top of a b Factory refrigerant charge see unit name plate c Additional refrigerant amount charged d Total refrigerant charge e Quantity of fluorinated greenhouse gases of the total refrigerant charge expressed as tonnes CO2 equivalent f GWP Global warming potential NOTICE Applicable legislation on fluorinated greenhouse gases requires that the refrigerant charge of...

Page 11: ... ARXF50 71A 20 A a ARXM50 71R RXM50 60R 16 A RXM42R 13 A Earth leakage circuit breaker MUST comply with applicable legislation a Electrical equipment complying with EN IEC 61000 3 12 European International Technical Standard setting the limits for harmonic currents produced by equipment connected to public low voltage systems with input current 16 A and 75 A per phase 7 2 To connect the electrical...

Page 12: ... specified range Prerequisite Test run may be performed in cooling or heating mode Prerequisite Test run should be performed in accordance with the operation manual of the indoor unit to make sure that all functions and parts are working properly 1 In cooling mode select the lowest programmable temperature In heating mode select the highest programmable temperature Test run can be disabled if nece...

Page 13: ...LED V L Pilot lamp light emitting diode HAP Light emitting diode service monitor green HIGH VOLTAGE High voltage IES Intelligent eye sensor IPM Intelligent power module K R KCR KFR KHuR K M Magnetic relay L Live Symbol Meaning L Coil L R Reactor M Stepper motor M C Compressor motor M F Fan motor M P Drain pump motor M S Swing motor MR MRCW MRM MRN Magnetic relay N Neutral n N Number of passes thro...

Page 14: ...CuT 9 5 CuT 6 4 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 4 0 CuT 4 0 CuT 9 5 CuT 12 7 CuT 12 7 CuT RXP50M RXF50B ARXF50A b a c d f h g j1 j3 j2 k m m m m m n o e l i i M a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic e...

Page 15: ...2 7 CuT 12 7 CuT 6 4 CuT RXP60M RXP71M RXF60B RXF71A ARXF60A ARXF71A b a c d f h g j1 j3 j2 k m m m m m n M o e l i i i a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic expansion valve HPS High pressure switch automatic res...

Page 16: ...0 CuT 4 0 CuT 6 4 CuT 6 4 CuT 6 4 CuT l m j3 M n o e m m d c b a f h g j1 i i i j2 k ARXM71R a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid receiver n Compressor f Filter o Accumulator g Electronic expansion valve HPS High pressure switch automatic reset h Muffler with filter M ...

Page 17: ... CuT 9 5 CuT 9 5 CuT 9 5 CuT 9 5 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 6 4 CuT 12 7 CuT 12 7 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT 7 0 CuT j3 b a c d f h g j1 i i i 4 0 CuT 4 0 CuT 4 0 CuT j2 m m m n M o e l k RXM42R a Liquid field piping j3 Discharge pipe thermistor b Gas field piping k Heat exchanger c Liquid stop valve l 4 way valve ON heating d Gas stop valve m Muffler e Liquid rec...

Page 18: ......

Page 19: ......

Page 20: ...STANBUL TÜRKİYE Tel 0216 453 27 00 Faks 0216 671 06 00 Çağrı Merkezi 444 999 0 Web www daikin com tr Gülsuyu Mahallesi Fevzi Çakmak Caddesi Burçak Sokak No 20 34848 Maltepe 3P645642 1A 2021 03 Copyright 2020 Daikin Verantwortung für Energie und Umwelt ...

Reviews: