Installation manual

R32 Split series

English

Installation manual

R32 Split series

ARXD25A5V1B
ARXD35A5V1B

Summary of Contents for ARXD25A5V1B

Page 1: ...Installation manual R32 Split series English Installation manual R32 Split series ARXD25A5V1B ARXD35A5V1B...

Page 2: ...s instrukcij atbilst d m direkt v m vai regul m ja vien ie izstr d jumi tiek lietoti saska ar m su instrukcij m s v zhode s nasleduj cou imi smernicou ami alebo predpisom mi za predpokladu e sa v rob...

Page 3: ...N standby electricity saving function 12 10 Commissioning 13 10 1 Checklist before commissioning 13 10 2 Checklist during commissioning 13 10 3 To perform a test run 13 11 Troubleshooting 13 11 1 Faul...

Page 4: ...use refrigerant gas leakage DANGER RISK OF EXPLOSION Do NOT open the stop valves before the vacuum drying is finished Charging refrigerant see 6 Charging refrigerant 49 WARNING The refrigerant inside...

Page 5: ...efore you can touch electrical components For the location of the terminals see the wiring diagram Finishing indoor unit installation see 8 Finishing the outdoor unit installation 412 DANGER RISK OF E...

Page 6: ...tlet b Air inlet NOTICE The height of the wall on the outlet side of the outdoor unit MUST be 1200 mm It is recommended to install a baffle plate when the air outlet is exposed to wind It is recommend...

Page 7: ...shers field supply 20 mm 311 5 7 4 2 1 1 mm 2 1 1 a a 100 mm above expected level of snow 4 2 2 To install the outdoor unit 4 M8 M10 4 2 3 To provide drainage NOTICE If the unit is installed in a cold...

Page 8: ...ing installation of the refrigeration system joining of parts with at least one part charged shall be performed taking into account the following requirements inside occupied spaces non permanent join...

Page 9: ...ssure Then Does not change There is no moisture in the system This procedure is finished Increases There is moisture in the system Go to the next step 3 Vacuum the system for at least 2 hours to a man...

Page 10: ...tal length m of liquid piping 10 m 0 020 R Additional charge kg rounded in units of 0 01 kg INFORMATION Piping length is the one way length of liquid piping 6 4 To determine the complete recharge amou...

Page 11: ...measure the voltage at the terminals of main circuit capacitors or electrical components before servicing The voltage MUST be less than 50 V DC before you can touch electrical components For the loca...

Page 12: ...ume when the temperature rises again To cut jumper J6 1 Remove the top plate of the outdoor unit 2 Remove the front plate 3 Remove the drip proof cover 4 Cut jumper J6 on the outdoor unit PCB J6 J4 J9...

Page 13: ...consequence Condensate water might drip The indoor unit receives the signals of the user interface The specified wires are used for the interconnection cable The fuses circuit breakers or locally inst...

Page 14: ...n the unit Part numbering is by Arabic numbers in ascending order for each part and is represented in the overview below by in the part code Symbol Meaning Symbol Meaning Circuit breaker Protective ea...

Page 15: ...erminal strip block Y E Electronic expansion valve coil Y R Y S Reversing solenoid valve coil Z C Ferrite core ZF Z F Noise filter 14 Piping diagram 14 1 Piping diagram Outdoor unit M 7 0 CuT 7 0 CuT...

Page 16: ...ANBUL T RK YE Tel 0216 453 27 00 Faks 0216 671 06 00 a r Merkezi 444 999 0 Web www daikin com tr G lsuyu Mahallesi Fevzi akmak Caddesi Bur ak Sokak No 20 34848 Maltepe 3P650253 15Q 2022 12 Copyright 2...