Accessories

Accessories supplied with the outdoor unit:

Precautions for Selecting the Location

1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise will not cause a nuisance to the neighbors of 

the user.

3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place.
7) Install units, power cords and inter-unit cables at least 3 meter away from television and radio sets. This is to prevent interference 

to images and sounds. (Noises may be heard even if they are more than 3 meter away depending on radio wave conditions.)

8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air conditioner.
9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.

NOTE

Cannot be installed hanging from ceiling or stacked.

 CAUTION

When operating the air conditioner in a low outdoor ambient 
temperature, be sure to follow the instructions described below.
1) To prevent exposure to wind, install the outdoor unit with its suction 

side facing the wall.

2) Never install the outdoor unit at a site where the suction side may 

be exposed directly to wind.

3) To prevent exposure to wind, it is recommended to install a baffle 

plate on the air discharge side of the outdoor unit.

4) In heavy snowfall areas, select an installation site where the snow will not affect the unit.

• Make sure to provide for adequate measures in order to prevent that the outdoor unit be used as a shelter by small animals. 

Small animals making contact with electrical parts can cause malfunctions, smoke or fire. Please instruct the customer to keep the area around the unit clean.

• This appliance is intended to be used by expert or trained users in shops, in light industry and on farms, or for 

commercial and household use by lay persons.

• Sound pressure level is less than 70 dB(A).

(A) Installation Manual

1

(B) Drain plug (Heat pump-Models)

It is on the bottom of the packing case.

1

(C) Refrigerant charge label

1

(D) Multilingual fluorinated greenhouse gases label 

1

Construct a large canopy.
Construct a pedestal.

Install the unit high enough off the 
ground to prevent burying in snow.

Summary of Contents for ARXB-C

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXB20C2V1B RXB25C2V1B RXB35C2V1B ARXB25C2V1B ARXB35C2V1B ...

Page 2: ... A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i ...

Page 3: ...ting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire I...

Page 4: ...hich must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below 1 To prevent exposure to wind install the outdoor unit with its suction side facing the wall 2 Never install the outdoor unit at a site where the suction side may be exposed d...

Page 5: ...ional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is u...

Page 6: ...foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work Heat pump models 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional fo...

Page 7: ...R410A 3 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly at right angles Remove burrs Set exactly at the position shown below A Flaring Die Check Flare s inner surface must be flaw free The pipe end must ...

Page 8: ...de of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Kee...

Page 9: ...uid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Thickness 10mm Min 30mm or more Thickness 0 8mm C1220T O Filling a cylinder with an attached siphon Stand the cylinder upright wh...

Page 10: ...force a test run to stop press the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and the operation select button at the same time 3 Press the operation select button twice will be displayed and the unit will enter test run mode 4 Press the operation select button to return the operatio...

Page 11: ...so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes mentioned below when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In c...

Page 12: ...OUTDOOR Outdoor INDOOR Indoor CONDENSER Condenser DISCHARGE Discharge Strip wire end to this point Excessive strip length may cause electrical shock or leakage Good Wrong Stripping wire at terminal block C400 C405 Capacitor DB1 Diode bridge E1 E2 HL1 HN1 HR1 HR2 S Connection FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MR30 MRCW MRM10...

Page 13: ...dance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner ...

Page 14: ......

Page 15: ......

Page 16: ...3P341265 6G 2014 10 Copyright 2014 Daikin ...

Reviews: