Safety Precautions

• Read these Safety Precautions carefully to ensure correct installation. 
• This manual classifies the precautions into WARNING and CAUTION.

Be sure to follow all the precautions below: they are all important for ensuring safety. 

WARNING .........Failure to follow any of WARNING is likely to result in such grave consequences as death or serious injury. 

CAUTION .........Failure to follow any of CAUTION may result in grave consequences in some cases. 

• The following safety symbols are used throughout this manual: 

• After completing installation, test the unit to check for installation errors. Give the user adequate instructions 

concerning the use and cleaning of the unit according to the Operation Manual.

• The English text is the original instruction. Other languages are translations of the original instructions. 

Be sure to observe this instruction. 

Be sure to establish an earth connection. 

Never attempt. 

WARNING

• Installation should be left to the dealer or another professional. 

Improper installation may cause water leakage, electrical shock, or fire. 

• Install the air conditioner according to the instructions given in this manual. 

Incomplete installation may cause water leakage, electrical shock, or fire.

• Be sure to use the supplied or specified installation parts. 

Use of other parts may cause the unit to come to lose, water leakage, electrical shock, or fire. 

• Install the air conditioner on a solid base that can support the weight of the unit. 

An inadequate base or incomplete installation may cause injury in the event the unit falls off the base. 

• Electrical work should be carried out in accordance with the installation manual and the national electrical wiring 

rules or code of practice. 

Insufficient capacity or incomplete electrical work may cause electrical shock or fire.

• Be sure to use a dedicated power circuit. Never use a power supply shared by another appliance. 
• For wiring, use a cable length enough to cover the entire distance with no connection.

Do not use an extension cord. Do not put other loads on the power supply, use a dedicated power circuit. 

(Failure to do so may cause abnormal heat, electric shock or fire.)

• Use the specified types of wires for electrical connections between the indoor and outdoor units. 

Firmly clamp the interconnecting wires so their terminals receive no external stresses. Incomplete connections or clamping may cause terminal 
overheating or fire. 

• After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force 

on the electrical covers or panels.

Install covers over the wires. Incomplete cover installation may cause terminal overheating, electrical shock, or fire.

• If any refrigerant has leaked out during the installation work, ventilate the room. 

(The refrigerant produces a toxic gas if exposed to flames.) 

• After all installation is complete, check to make sure that no refrigerant is leaking out.  

(The refrigerant produces a toxic gas if exposed to flames.)

• When installing or relocating the system, be sure to keep the refrigerant circuit free from substances other than the 

specified refrigerant (R410A), such as air. 

(Any presence of air or other foreign substance in the refrigerant circuit causes an abnormal pressure rise or rupture, resulting in injury.)

• During pump-down, stop the compressor before removing the refrigerant piping. 

If the compressor is still running and the stop valve is open during pump-down, air will be sucked in when the refrigerant piping is removed,
causing abnormal pressure in the freezer cycle which will lead to breakage and even injury.

• During installation, attach the refrigerant piping securely before running the compressor. 

If the compressor is not attached and the stop valve is open during pump-down, air will be sucked in when the compressor is run, causing
abnormal pressure in the freezer cycle which will lead to breakage and even injury.

• Be sure to establish an earth. Do not earth the unit to a utility pipe, arrester, or telephone earth. 

Incomplete earth may cause electrical shock, or fire. A high surge current from lightning or other sources may cause damage to the 
air conditioner. 

• Be sure to install an earth leakage breaker. 

Failure to install an earth leakage breaker may result in electric shocks, or fire. 

CAUTION

• Do not install the air conditioner in a place where there is danger of exposure to inflammable gas leakage.

If the gas leaks and builds up around the unit, it may catch fire. 

• Establish drain piping according to the instructions of this manual. 

Inadequate piping may cause flooding. 

• Tighten the flare nut according to the specified method such as with a torque wrench. 

If the flare nut is tightened too hard, the flare nut may crack after a long time and cause refrigerant leakage. 

Summary of Contents for ARXB-C

Page 1: ...INSTALLATION MANUAL R410A Split Series Models RXB20C2V1B RXB25C2V1B RXB35C2V1B ARXB25C2V1B ARXB35C2V1B ...

Page 2: ... A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i ...

Page 3: ...ting wires so their terminals receive no external stresses Incomplete connections or clamping may cause terminal overheating or fire After connecting interconnecting and supply wiring be sure to shape the cables so that they do not put undue force on the electrical covers or panels Install covers over the wires Incomplete cover installation may cause terminal overheating electrical shock or fire I...

Page 4: ...hich must be kept away from moisture NOTE Cannot be installed hanging from ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below 1 To prevent exposure to wind install the outdoor unit with its suction side facing the wall 2 Never install the outdoor unit at a site where the suction side may be exposed d...

Page 5: ...ional refrigerant required for refrigerant pipe exceeding 10m in length Be sure to add the proper amount of additional refrigerant Failure to do so may result in reduced perfomance The suggested shortest pipe length is 1 5m in order to avoid noise from the outdoor unit and vibration Mechanical noise and vibration may occur depending on how the unit is installed and the environment in which it is u...

Page 6: ...foundation surface Outdoor Unit Installation 1 Installing outdoor unit 1 When installing the outdoor unit refer to Precautions for Selecting the Location and the Outdoor Unit Installation Drawings 2 If drain work is necessary follow the procedures below 2 Drain work Heat pump models 1 Use drain plug for drainage 2 If the drain port is covered by a mounting base or floor surface place additional fo...

Page 7: ...R410A 3 Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand Then tighten them fully with the torque wrenches Cut exactly at right angles Remove burrs Set exactly at the position shown below A Flaring Die Check Flare s inner surface must be flaw free The pipe end must ...

Page 8: ...de of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Do vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s low pressure valve Lo and stop vacuum pump Kee...

Page 9: ...uid piping and to provide insulation dimensions as below 3 Use separate thermal insulation for gas and liquid refrigerant pipes Gas side Liquid side Gas pipe thermal insulation Liquid pipe thermal insulation O D 9 5mm O D 6 4mm I D 12 15mm I D 8 10mm Minimum bend radius Thickness 10mm Min 30mm or more Thickness 0 8mm C1220T O Filling a cylinder with an attached siphon Stand the cylinder upright wh...

Page 10: ...force a test run to stop press the indoor unit operation stop button Using the main unit s remote controller 1 Press the operation stop button Operation will start 2 Press the temperature button and the operation select button at the same time 3 Press the operation select button twice will be displayed and the unit will enter test run mode 4 Press the operation select button to return the operatio...

Page 11: ...so that the terminal numbers match Tighten the terminal screws securely We recommend a flathead screwdriver be used to tighten the screws The screws are packed with the terminal board Observe the notes mentioned below when wiring to the power supply terminal board Precautions to be taken for power supply wiring Use a round crimp style terminal for connection to the power supply terminal board In c...

Page 12: ...OUTDOOR Outdoor INDOOR Indoor CONDENSER Condenser DISCHARGE Discharge Strip wire end to this point Excessive strip length may cause electrical shock or leakage Good Wrong Stripping wire at terminal block C400 C405 Capacitor DB1 Diode bridge E1 E2 HL1 HN1 HR1 HR2 S Connection FU1 FU2 FU3 Fuse IPM1 Intelligent power module L Live L1 Coil L1R Reactor M1C Compressor motor M1F Fan motor MR30 MRCW MRM10...

Page 13: ...dance with the operation manual to ensure that all functions and parts such as louver movement are working properly The air conditioner requires a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consumption If the circuit breaker trips to shut off the power to the air conditioner ...

Page 14: ......

Page 15: ......

Page 16: ...3P341265 6G 2014 10 Copyright 2014 Daikin ...

Reviews: