4
www.daikincomfort.com
SS-DARUF
SS-DARUF
www.daikincomfort.com
5
Airflow Data
Model
Motor
Speed
Static Pressure (in w.c) Airflow (CFM)
0.1
0.2
0.3
0.4
0.5
0.6
0.7
ARUF25B14
Low
650
620
595
540
490
420
275
Med
885
865
825
815
750
690
560
High
1255
1225
1130
1090
965
925
800
ARUF29B14
Low
650
620
595
540
490
420
275
Med
885
865
825
815
750
690
560
High
1255
1225
1130
1090
965
925
800
ARUF31B14
Low
660
625
595
560
500
430
330
Med
930
905
865
820
765
700
590
High
1235
1185
1130
1060
990
910
825
ARUF37C14
Low
1120
1085
1040
1000
940
875
800
Med
1425
1385
1345
1285
1220
1145
1060
High
1625
1575
1520
1460
1375
1295
1200
ARUF43C14
Low
1120
1085
1040
1000
940
875
800
Med
1425
1385
1345
1285
1220
1145
1060
High
1625
1575
1520
1460
1375
1295
1200
ARUF49C14
Low
1295
1255
1225
1175
1120
1055
970
Med
1535
1485
1420
1370
1295
1215
1130
High
1755
1680
1590
1515
1425
1340
1250
ARUF37D14
Low
1155
1115
1070
1015
955
895
840
Med
1505
1470
1430
1375
1300
1210
1105
High
1785
1735
1680
1625
1555
1440
1330
ARUF43D14
Low
1410
1360
1290
1210
1120
1010
920
Med
1610
1540
1470
1390
1300
1190
1060
High
1900
1830
1740
1645
1540
1420
1280
ARUF47D14
Low
1420
1370
1310
1240
1125
1045
960
Med
1625
1585
1515
1435
1350
1235
1095
High
1930
1890
1820
1735
1635
1505
1355
ARUF49D14
Low
1410
1360
1290
1210
1120
1010
920
Med
1610
1540
1470
1390
1300
1190
1060
High
1900
1830
1740
1645
1540
1420
1280
ARUF61D14
Low
1530
1500
1460
1405
1350
1280
1155
Med
1950
1885
1830
1785
1745
1670
1595
High
2235
2170
2100
2030
1965
1915
1825
Notes
•
Airflow data indicated is at 230V without air filter in place.
•
The chart is for information only. For satisfactory operation, external static pressure must not exceed value shown on rating plate.
The shaded area indicates ranges in excess of maximum design external static pressure.
•
Use the CFM adjustment factors of 0.98 for horizontal left and 0.96 for horizontal right & downflow orientations