2
www.daikincomfort.com
SS-DARUF
SS-DARUF
www.daikincomfort.com
3
ARUF
25B14*
ARUF
29B14*
ARUF
31B14*
ARUF
37C14*
ARUF
43C14*
ARUF
49C14*
ARUF
37D14*
ARUF
43D14*
ARUF
47D14*
ARUF
49D14*
ARUF
61D14*
Nominal Ratings
Cooling (Btu/h)
24,000
25,000
30,000
36,000
42,000
48,000
36,000
42,000
43,000
48,000
60,000
Piston Size (in.)
0.051
0.057
0.065
0.072
0.076
0.080
0.072
0.076
0.076
0.080
0.080
Blower
Diameter
9½"
9½"
9½"
10⅝"
10⅝"
10⅝"
10⅝"
10⅝"
10⅝"
10⅝"
11
15
/16
"
Width
6"
6"
6"
8"
8"
10⅝"
10⅝"
10⅝"
10⅝"
10⅝"
10⅝"
Coil Connections
Liquid
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
⅜"
Suction
¾"
¾"
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
⅞"
Coil Drain Connect (FPT)
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
¾"
Electrical Data
Voltage
208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230 208/230
Min Circuit Ampacity
2.4/2.4
2.4/2.4
2.4/2.4
4/4
4/4
4/4
4/4
4/4
4/4
4/4
6/6
Max. Overcurrent Device (Amps)
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
15/15
Minimum VAC
197
197
197
197
197
197
197
197
197
197
197
Maximum VAC
253
253
253
253
253
253
253
253
253
253
253
Blower Motor
Full Load Amps (FLA)
1.9
1.9
1.9
3.0
3.0
3.1
3.0
3.5
3.5
3.5
4.6
Horsepower (HP)
⅓
⅓
⅓
⅓
⅓
½
⅓
½
½
½
¾
Ship Weight (Lbs.)
100
100
110
130
130
135
140
145
150
145
155
Note:
For a properly matched system and piston sizing information, refer to Amana piston kit chart of the corresponding Amana® outdoor unit.
Minimum Circuit Ampacity (MCA) and Maximum Overcurrent Protection (MOP) for blower without supplemental heat installed.
Refer to unit nameplate and/or Heat Kit Data for specification with approved accessory heaters installed.
Product Specifications