IM 1083-3
6
www.DaikinApplied.com
Safety
Follow all safety codes. Wear safety glasses and work gloves.
Use a quenching cloth for brazing operations. Have a fire
extinguisher available. Follow all warnings and cautions in
these instructions and attached to the unit. Consult applicable
local building codes and National Electrical Codes (NEC) for
special requirements.
Recognize safety information. When you see a safety symbol
on the unit or in these instructions, be alert to the potential for
personal injury. Understand the meanings of the words
DANGER, WARNING, and CAUTION. DANGER identifies
the most serious hazards that will result in death or severe
personal injury; WARNING means the hazards can result in
death or severe personal injury; CAUTION identifies unsafe
practices that can result in personal injury or product and
property damage.
Improper installation, adjustment, service, maintenance, or use
can cause explosion, fire, electrical shock, or other conditions
which may result in personal injury or property damage. This
product must be installed only by personnel with the training,
experience, skills, and applicable licensing that makes him/her
“a qualified professional HVACR installer.”
DANGER
Disconnect all electrical power before servicing unit.
Electrical shock will cause severe injury or death.
WARNING
Hazardous Voltage!Use copper conductors only. Unit terminals
are not designed to accept other types of conductors. Failure to
do so may cause damage to the equipment.
CAUTION
Personal injury hazard. Wear protective gloves to avoid possi-
ble cuts and abrasions from exposed edges. Avoid contact with
sharp edges.
WARNING
Cleaning agents may cause serious damage to internal compo-
nents, such as aluminum coils and electronic controls, etc. Do
not operate unit ventilator while building maintenance cleaning
agents are in use.
G
eneral
D
ata
Table 1: Approximate shipping weights, physical data
024
040
048
Overall Unit Dimensions
86"w × 30"h × 16⅝"d or
(21⅞"d w/Adapter Back)
98"w × 30"h × 16⅝"d or
(21⅞"d w/Adapter Back)
110"w × 30"h × 16⅝"d or
(21⅞"d w/Adapter Back)
Fan Data
Nominal CFM (L/s)
High Speed
1000 (472)
1250 (590)
1500 (708)
Medium speed
750 (354)
1000 (472)
1150 (543)
Low Speed
650 (307)
800 (378)
950 (448)
Number of Fans
3
4
4
Size
Diameter - in (mm)
8.12 (206mm)
8.12 (206mm)
8.12 (206mm)
Width- in (mm)
8.25 (210mm)
8.25 (210mm)
8.25 (210mm)
Room Fan Motor Horsepower
1/4
1/4
1/4
Filter Data
Nominal Size
in
10 x 48½ x 1
10 x 60½ x 1
(2) 10 x 36½ x 1
(mm)
254 x 1232 x 25
254 x 1537 x 25
(2) 254 x 927 x 25
Area - Ft
2
(m
2
):
3.37 (.31)
4.2 (.39)
5.08 (.47)
Quantity
1
1
2
Shipping Weight
lb (kg)
690 (310)
720 (325)
760 (340)
Refrigerant Charge
oz
81
132
109
Summary of Contents for ARQ