25
C08AF + EHYKOMB33AA
Daikin Altherma R Hybrid
4P471762-1B – 2020.10
Sch reheat mode
In sch reheat mode ( ), the domestic hot water control is the same as in
scheduled mode. However, when the DHW tank temperature drops below a preset
value (=reheat tank temperature – hysteresis value; example: 35°C), the DHW tank
heats up until it reaches the reheat set point (example: 45°C). This ensures that a
minimum amount of hot water is available at all times.
Example:
t
Tt
60°C
00:00
07:00
50°C
45°C
15°C
14:00
21:00
35°C
1
2
4
5
3
T
t
DHW tank temperature
t
Time
60°C
Storage comfort
50°C
Storage eco
45°C
Reheat
35°C
Reheat tank temperature – hysteresis value
In sch reheat mode, you can do the following:
You can…
Location
Do the same things as in scheduled mode.
—
Adjust the preset value
(
Reheat
).
Menu structure
See also:
▪
▪
"4.7 Preset values and schedules"
Using the DHW tank temperature home page
Typical DHW tank temperature home pages
Depending on the user profile, the user interface gives you either a basic or a
detailed home page. The examples in the illustrations below are in DHW tank mode
= Scheduled.
User profile =
Basic
User profile =
Detailed
15:20
60°C
Storage comfort
Tank
Mon
15:20
60°C
00:00
Mon
Tue
Tank
Storage comfort
To read out and adjust the desired reheat temperature (in scheduled and reheat
mode)
1
Go to [7.4.3.3]:
>
User settings
>
Preset values
>
Tank
temperature
>
Reheat
.
Result:
You can read out the desired reheat temperature.
2
Press or to adjust.