![background image](http://html.mh-extra.com/html/daikin/altherma-ehvz04s18cb/altherma-ehvz04s18cb_reference-manual_501265052.webp)
8 Configuration
Installer reference guide
52
ERLQ004~008CA + 08S18CB
Daikin Altherma – Low temperature split
4P401676-1 – 2015.02
Maximum running current
Disinfection
The disinfection function disinfects the domestic hot water tank by
periodically heating the domestic hot water to a specific temperature.
CAUTION
The disinfection function settings MUST be configured by
the installer according to the applicable legislation.
#
Code
Description
[A.4.4.2]
[2‑00]
Operation day:
▪ 0: Each day
▪ 1: Monday
▪ 2: Tuesday
▪ 3: Wednesday
▪ 4: Thursday
▪ 5: Friday
▪ 6: Saturday
▪ 7: Sunday
[A.4.4.1]
[2‑01]
Disinfection
▪ 0: No
▪ 1: Yes
[A.4.4.3]
[2‑02]
Start time: 00~23:00, step: 1:00.
[A.4.4.4]
[2‑03]
Temperature target: 60°C (fixed).
[A.4.4.5]
[2‑04]
Duration: 40~60 minutes, default: 40
minutes.
00.00
22.00
24.00
01.00
23.00
t
T
DHW
T
H
T
U
[2-02]
[2-03]
[2-04]
T
DHW
Domestic hot water temperature
T
U
User set point temperature
T
H
High set point temperature [2-03]
t
Time
WARNING
Be aware that the domestic hot water temperature at the
hot water tap will be equal to the value selected in field
setting [2-03] after a disinfection operation.
When the high domestic hot water temperature can be a
potential risk for human injuries, a mixing valve (field
supply) shall be installed at the hot water outlet connection
of the domestic hot water tank. This mixing valve shall
secure that the hot water temperature at the hot water tap
never rise above a set maximum value. This maximum
allowable hot water temperature shall be selected
according to the applicable legislation.
CAUTION
Be sure that the disinfection function start time [A.4.4.3]
with defined duration [A.4.4.5] is NOT interrupted by
possible domestic hot water demand.
INFORMATION
In case of error code AH and no interruption of the
disinfection function occurred due to domestic hot water
tapping, following actions are recommended:
▪ When the Domestic hot water > Type > Reheat or
Reheat + sched. is selected, it is recommended to
program the start-up of the disinfection function at least
4 hours later than the last expected large hot water
tapping. This start-up can be set by installer settings
(disinfection function).
▪ When the Domestic hot water > Type > Scheduled only
is selected, it is recommended to program a Storage
eco 3 hours before the scheduled start-up of the
disinfection function to preheat the tank.
INFORMATION
Disinfection function is restarted in case the domestic hot
water temperature drops 5°C below the disinfection target
temperature within the duration time.
INFORMATION
An AH error occurs if you do the following during
disinfection:
▪ Set the user permission level to Installer.
▪ Go to the DHW tank temperature home page (Tank).
▪ Press to interrupt the disinfection.
8.3.3
Heat source settings
Backup heater
Backup heater operation mode: defines when backup heater
operation is disabled or only allowed during domestic hot water
operation. This setting is only overruled when backup heating is
required during defrost operation or malfunctioning of the outdoor
unit (when [A.5.1.2] is enabled).
#
Code
Description
[A.5.1.1]
[4‑00]
Backup heater operation:
▪ 0: Disabled
▪ 1 (default): Enabled
N/A
[5-00]
Is backup heater operation allowed
above equilibrium temperature during
space heating operation?
▪ 1: NOT allowed (default)
▪ 0: Allowed
[A.5.1.4]
[5‑01]
Equilibrium temperature.
Outdoor temperature below which
operation of the backup heater is
allowed.
Range: –15°C~35°C (default: 0°C) (step:
1°C)
INFORMATION
If backup heater operation during space heating needs to
be limited but can be allowed for domestic hot water
operation, then put [4‑00] on 1, [5‑00] on 1, and [5‑01] on –
15°C.
Auto emergency
When the heat pump fails to operate the backup heater can serve as
an emergency heater and either automatically or non-automatically
take over the heat load. When auto emergency is set to Automatic
and a heat pump failure occurs, the backup heater will automatically
take over the heat load. When a heat pump failure occurs and auto
emergency is set to Manual the domestic hot water and space