7 Installation
Installer reference guide
47
ERHQ+ERLQ011~016 + EHBH/X11+16CB
Daikin Altherma – Low temperature split
4P384974-1 – 2015.01
X1M
X2M
29
X1M
YC
Y1
Y2
Y3
Y4
A4P
X2M
a
a
Installation of EKRP1HB is required.
2
Fix the cable with cable ties to the cable tie mountings.
7.9.17
To connect the changeover to external
heat source
1
Connect the changeover to external heat source cable to the
appropriate terminals as shown in the illustration below.
X1M
X1M
X3 X4
A4P
L N
X2M
X1 X2
a
a
Installation of EKRP1HB is required.
2
Fix the cable with cable ties to the cable tie mountings.
7.9.18
To connect the power consumption digital
inputs
1
Connect the power consumption digital inputs cable to the
appropriate terminals as shown in the illustration below.
X1M
X2M
1
23
4
5
A8P
X801M
S6S
S7S
S8S
S9S
a
a
Installation of EKRP1AHTA is required.
2
Fix the cable with cable ties to the cable tie mountings.
7.10
Finishing the outdoor unit
installation
7.10.1
To finish the outdoor unit installation
1
Insulate and fix the refrigerant piping and interconnection cable
as follows:
f
b
a
e
d
c
a
Gas pipe
b
Gas pipe insulation
c
Interconnection cable
d
Liquid pipe
e
Liquid pipe insulation
f
Finishing tape
2
Install the service cover.
7.10.2
To close the outdoor unit
NOTICE
When closing the outdoor unit cover, make sure that the
tightening torque does NOT exceed 4.1 N•m.
1×
2
1
7.11
Finishing the indoor unit
installation
7.11.1
To fix the user interface cover to the
indoor unit
1
Make sure that the front panel is removed from the indoor unit.
See
"7.2.3 To open the indoor unit" on page 29
.
2
Plug the user interface cover into the hinges.
3
2