background image

5 Maintenance and service

Operation manual

9

EBLQ+EDLQ011~W1
Daikin Altherma low temperature monobloc
4P522032-1 – 2018.01

5

Maintenance and service

5.1

Overview: Maintenance and
service

The installer has to perform a yearly maintenance. You can find the
contact/helpdesk number via the user interface.

As end user, you have to:

▪ Keep the area around the unit clean.

▪ Keep the user interface clean with a soft damp cloth. Do NOT use

any detergents.

▪ Regularly check if the water pressure is above 1 bar.

Refrigerant

This  product  contains  fluorinated  greenhouse  gases.  Do  NOT  vent
gases into the atmosphere.

Refrigerant type: R410A

Global warming potential (GWP) value: 2087.5

NOTICE

In  Europe,  the 

greenhouse  gas  emissions

  of  the  total

refrigerant charge in the system (expressed as tonnes CO

2

equivalent) is used to determine the maintenance intervals.
Follow the applicable legislation.

Formula  to  calculate  the  greenhouse  gas  emissions:

GWP value of the refrigerant × Total refrigerant charge [in
kg] / 1000

Please contact your installer for more information.

WARNING

The refrigerant in the system is safe and normally does not
leak. If the refrigerant leaks in the room, contact with a fire
of  a  burner,  a  heater  or  a  cooker  may  result  in  a  harmful
gas.

Turn  off  any  combustible  heating  devices,  ventilate  the
room and contact the dealer where you purchased the unit.

Do not use the system until a service person confirms that
the portion where the refrigerant leaks is repaired.

5.2

To find the contact/helpdesk
number

Prerequisite: 

You  switched  the  permission  level  to  Advanced  end

user.

1

Go  to  [6.3.2]: 

  >  Information  >  Error  handling  >  Contact/

helpdesk number.

6

Troubleshooting

6.1

Symptom: You are feeling too cold
(hot) in your living room

Possible cause

Corrective action

The desired room temperature is
too low (high).

Increase (decrease) the desired
room temperature.

If the problem recurs daily, do
one of the following:

▪ Increase  (decrease)  the  room

temperature preset value.

▪ Adjust  the  room  temperature

schedule.

The desired room temperature
cannot be reached.

Increase the desired leaving
water temperature in accordance
with the heat emitter type.

6.2

Symptom: The water at the tap is
too cold

Possible cause

Corrective action

You ran out of domestic hot
water because of unusual high
consumption.

If you immediately need domestic
hot water, activate the DHW tank
booster mode. However, this
consumes extra energy.

If you can wait, overrule
(increase) the active or next
scheduled desired temperature
so that more hot water will be
produced exceptionally.

If the problems recurs daily, do
one of the following:

▪ Increase 

the 

DHW 

tank

temperature preset value.

▪ Adjust 

the 

DHW 

tank

temperature 

schedule.

Example: 

Program 

to

additionally 

heat 

up 

the

DHW  tank  to  a  preset  value
(Storage  eco  =  lower  tank
temperature) during the day.

The desired DHW tank
temperature is too low.

6.3

Symptom: Heat pump failure

When the heat pump fails to operate, the backup heater and booster
heater  can  serve  as  an  emergency  heater  and  either  automatically
or non-automatically take over the heat load.

▪ When  auto  emergency  is 

activated

  and  a  heat  pump  failure

occurs:

▪ The backup heater will automatically take over the heat load.

▪ The booster heater will automatically take over the domestic hot

water production.

▪ When  auto  emergency  is 

not  activated

  and  a  heat  pump  failure

occurs, the domestic hot water and space heating operations will
stop  and  need  to  be  recovered  manually.  The  user  interface  will
then  ask  you  to  confirm  whether  the  backup  heater  or  booster
heater can take over the heat load or not.

When the heat pump fails,   will appear on the user interface.

Summary of Contents for Altherma EBLQ011CAV3

Page 1: ...ow temperature monobloc English Operation manual Daikin Altherma low temperature monobloc EBLQ011CAV3 EBLQ014CAV3 EBLQ016CAV3 EBLQ011CAW1 EBLQ014CAW1 EBLQ016CAW1 EDLQ011CAV3 EDLQ014CAV3 EDLQ016CAV3 ED...

Page 2: ...entation carefully before operating the user interface to ensure the best possible performance Request the installer to inform you about the settings that he used to configure your system Check if he...

Page 3: ...e on a home page Goes up a level when you are navigating through the menu structure Goes back 1 step example when you are programming a schedule in the menu structure e NAVIGATING CHANGING SETTINGS Na...

Page 4: ...he indoor temperature and taking monthly restrictions into account Note Automatic changeover is only possible under certain conditions To restrict automatic changeover operation mode Prerequisite You...

Page 5: ...ht because the space heating demand is lower Example t 60 C 00 00 07 00 50 C 15 C 40 C 14 00 21 00 1 2 3 4 5 Tt Tt DHW tank temperature t Time 3 4 3 Scheduled reheat mode In scheduled reheat mode the...

Page 6: ...Set schedules Room temp Set heating schedule 2 Select Empty and press 3 Program the schedule for Monday See below for more details 4 Copy from Monday to Tuesday Wednesday Thursday and Friday See below...

Page 7: ...metering Consumed elec Produced energy Error information Error history Contact helpdesk number Version User interface Indoor unit Outdoor unit User settings Display Temperature lock Set schedules Pres...

Page 8: ...tage comfort problems is significant In case of frequent domestic hot water operation frequent and long space heating cooling interruptions will happen 3 8 4 Contact helpdesk number 6 3 2 Setting Defa...

Page 9: ...your living room Possible cause Corrective action The desired room temperature is too low high Increase decrease the desired room temperature If the problem recurs daily do one of the following Incre...

Page 10: ...backup heater or booster heater takes over the heat load electricity consumption will be considerably higher 7 Disposal NOTICE Do NOT try to dismantle the system yourself dismantling of the system tre...

Page 11: ......

Page 12: ...4P522032 1 2018 01 Copyright 2018 Daikin 4P522032 1 0000000C...

Reviews: