![background image](http://html.mh-extra.com/html/daikin/altherma-eblq011ca3v3/altherma-eblq011ca3v3_installation-manual_501247018.webp)
5 Configuration
Installation manual
18
EBLQ+EDLQ011~0W1
Daikin Altherma low temperature monobloc
4P537990-1 – 2018.05
#
Code
Description
[7.7.2.2]
[0-04]
[0-05]
[0-06]
[0-07]
Weather-dependent curve (cooling):
[0-04]
[0-05]
Ta
Tt
[0-07]
[0-06]
▪ T
t
: Target leaving water temperature
(additional)
▪ T
a
: Outdoor temperature
Leaving water temperature: Delta T source
#
Code
Description
[A.3.1.3.1]
[9-09]
Heating: required temperature
difference between entering and
leaving water.
In case a minimum temperature
difference is required for the good
operation of the heat emitters in heating
mode.
[A.3.1.3.2]
[9-0A]
Cooling: required temperature
difference between entering and
leaving water.
In case a minimum temperature
difference is required for the good
operation of the heat emitters in cooling
mode.
Leaving water temperature: Modulation
#
Code
Description
[A.3.1.1.5]
[8-05]
Leaving water temperature modulation:
▪ 0 (No): Disabled
▪ 1 (Yes): Enabled. The leaving water
temperature is calculated according
to the difference between desired
and actual room temperature.
This allows better matching of the
heat
pump
capacity
to
actual
required capacity and results in less
start/stop cycles of the heat pump
and more economic operation.
N/A
[8-06]
Leaving water temperature maximum
modulation:
0°C~10°C (default: 3°C)
Requires modulation to be enabled.
This is the value by which the desired
leaving water temperature is increased
or lowered.
INFORMATION
When leaving water temperature modulation is enabled,
the weather‑dependent curve needs to be set to a higher
position than [8-06] plus the minimum leaving water
temperature setpoint required to reach a stable condition
on the comfort setpoint for the room. To increase
efficiency, modulation can lower the leaving water setpoint.
By setting the weather‑dependent curve to a higher
position, it cannot drop below the minimum setpoint. Refer
to the illustration below.
a
+[8-06]
−[8-06]
b
Ta
Tt
a
Weather-dependent curve
b
Minimum leaving water temperature setpoint required to
reach a stable condition on the comfort setpoint for the
room.
Leaving water temperature: Emitter type
#
Code
Description
[A.3.1.1.7]
[9-0B]
Reaction time of the system:
▪ 0: Quick (default)
Example:
Small water volume and
fan coils.
▪ 1: Slow
Example:
Large water volume, floor
heating loops.
Depending on the system water volume
and the heat emitters type, the heat up
or cool down of a space can take
longer. This setting can compensate for
a slow or a quick heating/cooling
system by adjusting the unit capacity
during the heat up/cool down cycle.
5.2.6
Domestic hot water control
#
Code
Description
[A.4.1]
[6-0D]
Domestic hot water Type:
▪ 0 (Reheat only): Only reheat operation
is allowed.
▪ 1 ( sched.)(default): Same as
2, but between the scheduled heatup
cycles, reheat operation is allowed.
▪ 2 (Scheduled only): The domestic hot
water tank can ONLY be heated
according to a schedule.
[A.4.5]
[6-0E]
The maximum temperature that users
can select for the domestic hot water.
You can use this setting to limit the
temperature at the hot water taps.
INFORMATION
There is a risk of space heating (cooling) capacity
shortage/comfort problem (in case of frequent domestic hot
water operation, frequent and long space heating/cooling
interruption will happen) when selecting [6‑0D]=0 ([A.4.1]
Domestic hot water Type=Reheat only) in case of a
domestic hot water tank without an internal booster heater.
5.2.7
Contact/helpdesk number
#
Code
Description
[6.3.2]
N/A
Number that users can call in case of
problems.