6 Commissioning

Installation manual

20

EBLQ+EDLQ011~0W1

Daikin Altherma low temperature monobloc

4P537990-1 – 2018.05

6

Commissioning

NOTICE

NEVER  operate  the  unit  without  thermistors  and/or
pressure  sensors/switches.  Burning  of  the  compressor
might result.

6.1

Checklist before commissioning

After the installation of the unit, first check the following items. Once
all  below  checks  are  fulfilled,  the  unit  MUST  be  closed,  ONLY  then
can the unit be powered up.

Depending  on  the  system  layout,  not  all  components  may  be
available.

You  read  the  complete  installation  instructions,  as
described in the 

installer reference guide

.

The 

outdoor unit

 is properly mounted.

The 

control box

 is properly mounted.

The 

option box

 is properly mounted.

The following 

field wiring

 has been carried out according

to  the  available  documentation  and  the  applicable
legislation:

▪ Between the local supply panel and the outdoor unit

▪ Between the outdoor unit and the control box

▪ Between the control box and the option box

▪ Between the local supply panel and the control box

▪ Between the local supply panel and the option box

▪ Between the outdoor unit and the valves

▪ Between the control box and the room thermostat

▪ Between  the  control  box  and  the  domestic  hot  water

tank

The  system  is  properly 

earthed

  and  the  earth  terminals

are tightened.

The 

fuses

  or  locally  installed  protection  devices  are

installed according to this document, and have NOT been
bypassed.

The 

power  supply  voltage

  matches  the  voltage  on  the

identification label of the unit.

There  are  NO 

loose  connections

  or  damaged  electrical

components in the switch box.

There  are  NO 

damaged  components

  or 

squeezed

pipes

 on the inside of the outdoor unit.

Backup  heater  circuit  breaker

  F1B  (field  supply)  is

turned ON.

Only for tanks with built-in booster heater:

Booster heater circuit breaker

 F2B (on the switch box of

the control box) is turned ON.

The  correct  pipe  size  is  installed  and  the 

pipes

  are

properly insulated.

There are no 

water leaks

 inside the outdoor unit.

The 

shut-off valves

 are properly installed and fully open.

The 

pressure relief valve

 purges water when opened.

The 

minimum  water  volume

  is  guaranteed  in  all

conditions.  See  "To  check  the  water  volume"  in

"3.2 Preparing water piping" on page 5

.

If 

glycol

  was  added  to  the  system,  confirm  the  correct

glycol concentration, and check if glycol setting [E‑0D]=1.

NOTICE

▪ Make  sure  glycol  setting  [E-0D]  matches  the  liquid

inside the water circuit (0=water only, 1=water+glycol).
If  the  glycol  setting  is  NOT  set  correctly,  the  liquid
inside the piping can freeze.

▪ When  glycol  is  added  to  the  system,  but  the  glycol

concentration is lower than prescribed, the liquid inside
the piping can still freeze.

INFORMATION

The  software  is  equipped  with  an  "installer-on-site"  mode
([4‑0E]),  that  disables  automatic  operation  by  the  unit.  At
first  installation,  setting  [4‑0E]  is  by  default  set  to  "1",
meaning  automatic  operation  is  disabled.  All  protective
functions  are  then  disabled.  If  the  user  interface  home
pages  are  off,  the  unit  will  NOT  operate  automatically.  To
enable  automatic  operation  and  the  protective  functions,
set [4‑0E] to "0".

36 hours after the first power-on, the unit will automatically
set  [4‑0E]  to  "0",  ending  "installer-on-site"  mode  and
enabling  the  protective  functions.  If  –  after  first
installation  –  the  installer  returns  to  the  site,  the  installer
has to set [4‑0E] to "1" manually.

6.2

Checklist during commissioning

The 

minimum  flow  rate

  is  guaranteed  in  all  conditions.

See  "To  check  the  water  volume  and  flow  rate"  in

"3.2 Preparing water piping" on page 5

.

To perform an 

air purge

.

To perform a 

test run

.

To perform an 

actuator test run

.

Underfloor screed dryout function

The  underfloor  screed  dryout  function  is  started  (if
necessary).

6.2.1

To perform an air purge

Prerequisite: 

Make  sure  that  the  leaving  water  temperature  home

page, room temperature home page, and domestic hot water home
page are turned OFF.

1

Go  to  [A.7.3]: 

  >  Installer  settings  >  Commissioning  >  Air

purge.

2

Set the type.

3

Select Start air purge and press 

.

4

Select OK and press 

.

NOTICE

The  outdoor  unit  is  equipped  with  a  manual  air  purge
valve. The air purge procedure requires manual action.

NOTICE

When  purging  air  with  the  manual  air  purge  valve  of  the
unit, collect any fluid that might leak out of the valve. If this
fluid is NOT collected, it might drip on internal components
and damage the unit.

Summary of Contents for Altherma EBLQ011CA3V3

Page 1: ...mperature monobloc English Installation manual Daikin Altherma low temperature monobloc EBLQ011CA3V3 EBLQ014CA3V3 EBLQ016CA3V3 EBLQ011CA3W1 EBLQ014CA3W1 EBLQ016CA3W1 EDLQ011CA3V3 EDLQ014CA3V3 EDLQ016CA3V3 EDLQ011CA3W1 EDLQ014CA3W1 EDLQ016CA3W1 ...

Page 2: ...A B C 500 250 100 A B C E 500 250 150 1000 500 500 D 500 500 D E 1000 500 B D 250 500 B D E 250 250 400 400 400 400 400 1000 150 150 150 150 150 150 150 1000 1000 1000 500 HD HU HD HU HB HU HD HU HB HU a b c d e eB eD A B C D E HB HU HD 1 ...

Page 3: ...n että niitä käytetään ohjeidemme mukaisesti za předpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha ...

Page 4: ...ck wizard Capacities energy metering 17 5 2 5 Space heating cooling control 17 5 2 6 Domestic hot water control 18 5 2 7 Contact helpdesk number 18 5 3 Menu structure Overview installer settings 19 6 Commissioning 20 6 1 Checklist before commissioning 20 6 2 Checklist during commissioning 20 6 2 1 To perform an air purge 20 6 2 2 To perform a test run 21 6 2 3 To perform an actuator test run 21 6 ...

Page 5: ... mm at the air inlet side If shut off valves are NOT installed on the unit provide a minimum space of 250 mm If the system contains a domestic hot water tank meet the following requirements Maximum allowable distance between outdoor unit and Distance domestic hot water tank 10 m 3 way valve 10 m The outdoor unit is designed for outdoor installation only and for ambient temperatures ranging 10 43 C...

Page 6: ... Overview of electrical connections for external and internal actuators Item Description Wires Maximum running current Outdoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Normal kWh rate power supply 2 6 3 A User interface 3 User interface 2 b Optional equipment 4 Remote outdoor sensor 2 c Field supplied components 5 Domestic hot water pump 2 c 6 Space heating cooling operation con...

Page 7: ...ovide drainage Make sure that condensate can be evacuated properly When the unit is in cooling mode condensate may also form in the hydro part When providing drainage therefore make sure to cover the entire unit NOTICE If the unit is installed in a cold climate take adequate measures so that the evacuated condensate CANNOT freeze Drain holes dimensions in mm 160 620 261 5 119 161 260 285 279 345 5...

Page 8: ...lves 2 Connect the field piping on the shut off valves 3 In case of connection with the optional domestic hot water tank see the installation manual of the domestic hot water tank NOTICE Install a manometer in the system NOTICE Install air purge valves at all local high points NOTICE In case an optional domestic hot water tank is installed A pressure relief valve field supply with an opening press...

Page 9: ...release pressure Prevent water from staying and or freezing up inside the hose WARNING Due to presence of glycol corrosion of the system is possible Uninhibited glycol will turn acidic under the influence of oxygen This process is accelerated by the presence of copper and high temperatures The acidic uninhibited glycol attacks metal surfaces and forms galvanic corrosion cells that cause severe dam...

Page 10: ...ckup heater power supply cable NOTICE The distance between the high voltage and low voltage cables should be at least 25 mm Routing Possible cables depends on the installed options a Low voltage User interface Interconnection cable to control box EKCB07CAV3 Remote outdoor sensor option b High voltage Normal kWh rate power supply Preferential kWh rate power supply Heat pump convector option Shut of...

Page 11: ...oute the wiring as follows K1M K5M X4M PE L N 1 2 3 230 V AC 3 kW L N 3 Fix the cable with cable ties to the cable tie mountings INFORMATION For more information on the backup heater types and for how to configure the backup heater refer to the Configuration chapter of the installation manual of the outdoor unit 4 4 4 To connect the user interface INFORMATION If control box EKCB07CAV3 is NOT part ...

Page 12: ... 4C From the top a b PCB b 1 4D From the top centre a PCB b b 1 a Notch this part for the wiring to pass through with nippers etc b Secure the wiring to the front part of the casing using the wiring retainer and clamp 4 4 5 To connect the shut off valve 1 Connect the valve control cable to the appropriate terminals as shown in the illustration below NOTICE Only connect NO normal open valves NO X5M...

Page 13: ...ver NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the menu structure Accessing settings via the code in the overview settings Code See also To access the installer settings on page 13 5 3 Menu structure Overview installer settings on page 19 5 1 1 ...

Page 14: ...y other settings 6 Push to confirm the modification of the parameter 7 At installer settings menu press to confirm the settings Installer settings The system will restart Confirm Adjust Cancel OK Result The system will restart 5 1 3 To copy the system settings from the first to the second user interface If a second user interface is connected the installer must first proceed below instructions for...

Page 15: ...ration select Confirm layout and press Confirm layout Please confirm the system layout The system will restart and will be ready for first startup OK Cancel Confirm Adjust 5 The user interface re initialises and you can proceed the installation by setting the other applicable settings and commissioning of the system When the installer settings are changed the system will request to confirm When co...

Page 16: ... Can the system prepare domestic hot water 0 No NOT installed 1 Yes Installed N A E 07 DHW tank type 0 EKHWS DHW tank with booster heater installed at the side of the tank Default 1 EKHWP DHW tank with booster heater installed at the top of the tank A 2 2 E 5 C 05 External room thermostat for the main zone 1 Thermo ON OFF When the used external room thermostat or heat pump convector can only send ...

Page 17: ...ster heater capacity kW A 2 3 2 6 03 Backup heater capacity step 1 kW 5 2 5 Space heating cooling control Leaving water temperature Main zone Code Description A 3 1 1 1 N A Set point mode 0 Fixed Absolute 1 Weather dep Weather dependent 2 Fixed scheduled Absolute scheduled only for leaving water temperature control 3 WD scheduled Weather dependent scheduled only for leaving water temperature contr...

Page 18: ...ndition on the comfort setpoint for the room To increase efficiency modulation can lower the leaving water setpoint By setting the weather dependent curve to a higher position it cannot drop below the minimum setpoint Refer to the illustration below a 8 06 8 06 b Ta Tt a Weather dependent curve b Minimum leaving water temperature setpoint required to reach a stable condition on the comfort setpoin...

Page 19: ...control method Number of LWT zones Pump operation mode Power saving possible User interface location Options DHW pump External sensor Control box Option box Leaving water Main Additional Delta T source Room thermostat Room temp range Room temp offset Ext room sensor offset Operation range Space heating OFF temp Space cooling On temp Disinfection Disinfection Operation day Start time Temperature ta...

Page 20: ...e pressure relief valve purges water when opened The minimum water volume is guaranteed in all conditions See To check the water volume in 3 2 Preparing water piping on page 5 If glycol was added to the system confirm the correct glycol concentration and check if glycol setting E 0D 1 NOTICE Make sure glycol setting E 0D matches the liquid inside the water circuit 0 water only 1 water glycol If th...

Page 21: ...st Backup heater test Pump test INFORMATION Make sure that all air is purged before executing the test run Also avoid disturbances in the water circuit during the test run 2 way valve test 3 way valve test Alarm output test Cooling heating signal test Quick heat up test Circulation pump test 6 2 4 To perform an underfloor heating screed dryout Prerequisite Make sure there is ONLY 1 user interface ...

Page 22: ...mplified user interface or an external room thermostat is then required You can use the following locking modes Function lock Locks a specific function to prevent people from changing its settings Button lock Locks all buttons to prevent users from changing settings To activate or deactivate a function lock 1 Press to go to the menu structure 2 Press for more than 5 seconds 3 Select a function and...

Page 23: ...7 High pressure switch 18 Compressor 19 Pressure sensor 20 Accumulator 21 Service port 5 16 flare 22 Heat exchanger 23 Fan motor propeller fan 24 Capillary tube 25 Distributor 26 Refrigerant filter 27 Solenoid valve 28 Liquid stop valve with service port 29 Suction pipe thermistor 30 Discharge pipe thermistor 31 Outdoor air temperature thermistor 32 Heat exchanger thermistor middle 33 Heat exchang...

Page 24: ...nly Fuse F 1 A 250 V F1U F2U A1P W1 only Fuse T 31 5 A 500 V F3U F6U A1P W1 only Fuse T 6 3 A 500 V F7U A2P W1 only Fuse T 5 A 250 V F8U F9U W1 only Fuse F 1 A 250 V H1P H7P A2P V3 only LED service monitor is orange H1P H7P A1P W1 only LED service monitor is orange HAP A1P V3 only LED service monitor is green HAP A1P A2P W1 only LED service monitor is green K1M K2M A2P W1 only Magnetic contactor m...

Page 25: ... backup heater thermistor R3T Refrigerant liquid side thermistor R4T Inlet water thermistor R6T External outdoor ambient sensor S1L Flow switch TR1 Power supply transformer English Translation X A X Y A1P A2P Connector X M Terminal strip Optional Field supply Outdoor backup heater power supply English Translation Only for Only for E3H Backup heater element 3 kW F1B Overcurrent fuse backup heater F...

Page 26: ...ter X A A4P Connector X M Terminal strip Optional Field supply Control box option option box English Translation Alarm output Alarm output Control box Control box Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB Electric pulse meter inputs 5 V DC pulse detection voltage supplied by PCB Ext heat source External heat source External indoor ambient sensor option External ind...

Page 27: ... X2M 1a 2 Only for heat pump convector Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 2 core 3m included signal R2T External sensor floor or ambient Only for KRTETS External indoor thermistor Electricity pulse meter input 2 Electricity pulse meter input 1 Space cooling heating On OFF output Ext heat source eg boiler Alarm Output Only for KRCS01 1 3 core communication 3 ...

Page 28: ...4P537990 1 2018 05 Copyright 2018 Daikin 4P537990 1 0000000V ...

Reviews: