5 Configuration
Installation manual
18
EABH/X16DA+9W
Daikin Altherma – Low temperature split
4P556066-1 – 2018.10
#
Code
Description
[5.2]
[6-0A]
Comfort setpoint
▪ 30°C~[6‑0E]°C
Eco setpoint
The
storage economic temperature
denotes the lower desired
tank temperature. It is the desired temperature when a storage
economic action is scheduled (preferably during day).
#
Code
Description
[5.3]
[6-0B]
Eco setpoint
▪ 30°C~min(50,[6‑0E])°C
Reheat setpoint
Desired reheat tank temperature
, used:
▪ in Schedule + reheat mode, during reheat mode: the guaranteed
minimum tank temperature is set by the Reheat setpoint minus the
reheat hysteresis. If the tank temperature drops below this value,
the tank is heated up.
▪ during storage comfort, to prioritize the domestic hot water
preparation. When the tank temperature rises above this value,
domestic hot water preparation and space heating/cooling are
executed sequentially.
#
Code
Description
[5.4]
[6-0C]
Reheat setpoint
▪ 30°C~min(50,[6‑0E])°C
5.3
Settings menu
You can set additional settings using the main menu screen and its
submenus. The most important settings are presented here.
5.3.1
Main zone
Thermostat type
Only applicable in external room thermostat control.
NOTICE
If an external room thermostat is used, the external room
thermostat will control the room frost protection. However,
the room frost protection is only possible if the leaving
water temperature control on the unit's user interface is
turned ON.
#
Code
Description
[2.A]
[C–05]
External room thermostat type for the
main zone:
▪ 1: 1 contact: The used external room
thermostat can only send a thermo
ON/OFF condition. There is no
separation between heating or cooling
demand.
▪ 2: 2 contacts: The used external room
thermostat can send a separate
heating/cooling
thermo
ON/OFF
condition.
5.3.2
Additional zone
Thermostat type
Only applicable in external room thermostat control. For more info
about the functionality, see
.
#
Code
Description
[3.A]
[C–06]
External room thermostat type for the
additional zone:
▪ 1: 1 contact
▪ 2: 2 contacts
5.3.3
Information
Dealer information
The installer can fill in his contact number here.
#
Code
Description
[8.3]
N/A
Number that users can call in case of
problems.