5 Configuration

Installation manual

18

EHBH/X04+08DA

Daikin Altherma 3 R W

4P495266-1D – 2019.10

Control

The  control  type  is  displayed  here,  but  cannot  be  adjusted.  It  is
determined by the control type of the main zone. For more info about
the functionality, see 

"5.2.5 Configuration wizard: Main zone" 

[

4

 17].

#

Code

Description

[3.9]

N/A

▪ 0: 

Leaving  water

  if  the  control  type

of the main zone is 

Leaving water

.

▪ 1: 

External  room  thermostat

 if the

control  type  of  the  main  zone  is

External  room  thermostat

 or 

Room

thermostat

.

Setpoint mode

For  more  info  about  this  functionality,  see 

"5.2.5  Configuration

wizard: Main zone" 

[

4

 17].

#

Code

Description

[3.4]

N/A

▪ 0: 

Fixed

▪ 1: 

WD heating, fixed cooling

▪ 2: 

Weather dependent

If  you  choose 

WD  heating,  fixed  cooling

  or 

Weather

dependent

, the next screen will be the detailed screen with weather-

dependent  curves.  Also  see 

"5.2.7  Detailed  screen  with  weather-

dependent curve" 

[

4

 18].

Schedule

Indicates  if  the  desired  leaving  water  temperature  is  according  to  a
schedule. Also see 

"5.2.5 Configuration wizard: Main zone" 

[

4

 17].

#

Code

Description

[3.1]

N/A

▪ 0: 

No

▪ 1: 

Yes

5.2.7

Detailed screen with weather-dependent
curve

When  weather-dependent  (WD)  operation  is  active  the  desired
leaving  water  or  tank  temperature  is  determined  automatically
depending on the averaged outdoor temperature. When the outdoor
temperature is lower the leaving water or tank temperature will need
to be higher as the water pipes will be colder and vice versa.

2-points WD curve

The weather-dependent curve is defined by two setpoints:

▪ Setpoint (X1, Y2)

▪ Setpoint (X2, Y1)

Weather-dependent curve:

Y1

Y2

X1

X2

a

Possible actions on this screen

Go through the temperatures.

Change the temperature.

Go to the next temperature.

Confirm changes and proceed.

Item

Description

a

Selected weather dependent zone:

: Main zone or additional zone heating

: Main zone or additional zone cooling

: Domestic hot water

X1, X2

Examples of outdoor ambient temperature

Y1, Y2

Examples of desired tank temperature or leaving water
temperature. The icon corresponds to the heat emitter
for that zone:

: Underfloor heating

: Fan coil unit

: Radiator

: Domestic hot water tank

5.2.8

Configuration wizard: Tank

This part only applies to systems with an optional domestic hot water
tank installed.

Heat up mode

The  domestic  hot  water  can  be  prepared  in  3  different  ways.  They
differ from each other by the way the desired tank temperature is set
and how the unit acts upon it.

#

Code

Description

[5.6]

[6-0D]

Heat up mode

▪ 0: 

Reheat 

only

:  Only  reheat

operation is allowed.

▪ 1: 

Sc reheat

: The domestic

hot water tank is heated according to a
schedule  and  between  the  scheduled
heat  up  cycles,  reheat  operation  is
allowed.

▪ 2: 

Schedule  only

:  The  domestic  hot

water  tank  can  ONLY  be  heated
according to a schedule.

See the operation manual for more details.

INFORMATION

Risk  of  space  heating  capacity  shortage  for  domestic  hot
water  tank  without  internal  booster  heater:  In  case  of
frequent  domestic  hot  water  operation,  frequent  and  long
space  heating/cooling  interruption  will  happen  when
selecting the following:

Tank

 > 

Heat up mode

 > 

Reheat only

.

Comfort setpoint

Only  applicable  when  domestic  hot  water  preparation  is 

Schedule

only

 or 

Sc reheat

. When programming the schedule, you

can make use of the comfort setpoint as a preset value. When you
later  want  to  change  the  storage  setpoint,  you  only  have  to  do  it  in
one place.

The  tank  will  heat  up  until  the 

storage  comfort  temperature

  has

been  reached.  It  is  the  higher  desired  temperature  when  a  storage
comfort action is scheduled.

Additionally, a storage stop can be programmed. This feature puts a
stop  to  tank  heating  even  if  the  setpoint  has  NOT  been  reached.
Only  program  a  storage  stop  when  tank  heating  is  absolutely
undesirable.

Summary of Contents for Altherma 3 R W EHB Series

Page 1: ...Installation manual Daikin Altherma 3 R W English Installation manual Daikin Altherma 3 R W EHBH04DA6V EHBH08DA6V EHBH08DA9W EHBX04DA6V EHBX08DA6V EHBX08DA9W ...

Page 2: ...dpokladu že jsou využívány v souladu s našimi pokyny odpovídají následujícím normám nebo normativním dokumentům u skladu sa slijedećim standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s našim uputama 16 17 18 19 20 21 22 23 24 25 megfelelnek az alábbi szabvány ok nak vagy egyéb irányadó dokumentum ok nak ha azokat előírás szerint használják spełniają wymogi ...

Page 3: ...izard Main zone 17 5 2 6 Configuration wizard Additional zone 17 5 2 7 Detailed screen with weather dependent curve 18 5 2 8 Configuration wizard Tank 18 5 3 Settings menu 19 5 3 1 Main zone 19 5 3 2 Additional zone 19 5 3 3 Information 19 5 4 Menu structure Overview installer settings 20 6 Commissioning 21 6 1 Checklist before commissioning 21 6 2 Checklist during commissioning 21 6 2 1 To check ...

Page 4: ...es Space heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C Mind the following spacing installation guidelines H 1150 200 200 500 mm 450 H Height measured from the bottom of the casing to the floor Special requirements for R32 WARNING Do NOT pierce or burn Do NOT use means to accelerate the defrosting process or to clean the equipment other than those reco...

Page 5: ...ate the minimum opening area for natural ventilation between room A and room B VAmin cm2 Unit can be installed at room A if 2 ventilation openings permanently open are provided between room A and B 1 at the top and 1 at the bottom Bottom opening The bottom opening must meet the minimum area requirements VAmin It must be as close as possible to the floor and lower than H If the ventilation opening ...

Page 6: ...ernal actuators Item Description Wires Maximum running current Outdoor unit and indoor unit power supply 1 Power supply for outdoor unit 2 GND a 2 Power supply and interconnection cable to indoor unit 3 g 3 Power supply for backup heater See table below 4 Preferential kWh rate power supply voltage free contact 2 e 5 Normal kWh rate power supply 2 6 3 A Optional equipment 6 3 way valve 3 100 mA b I...

Page 7: ...itch box cover 4 3 If you have to do work behind the switch box open the switch box 2 1 2 4 If you have to do work behind the user interface panel or upload new software into the user interface open the user interface panel 1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent...

Page 8: ... 2 2 To connect the drain hose to the drain Water coming from the pressure relief valve is collected in the drain pan You must connect the drain pan to an appropriate drain according to the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain pan connector It is recommended to use a tundish to collect the water 4 3 Connecting refrigerant piping...

Page 9: ...ing pressure of maximum 10 bar 1 MPa must be installed on the domestic cold water inlet connection in accordance with the applicable legislation 4 4 2 To fill the water circuit To fill the water circuit use a field supply filling kit Make sure you comply with the applicable legislation INFORMATION Make sure both air purge valves one on the magnetic filter and one on the backup heater are open 4 4 ...

Page 10: ...3 6 a Interconnection cable main power supply b Normal kWh rate power supply c Preferential power supply contact 2 Fix the cables with cable ties to the cable tie mountings INFORMATION In case of preferential kWh rate power supply connect X11Y to X11YB The necessity of separate normal kWh rate power supply to indoor unit b X2M 5 6 depends on the type of preferential kWh rate power supply Separate ...

Page 11: ...e public system It is the responsibility of the installer or user of the equipment to ensure by consultation with the distribution network operator if necessary that the equipment is connected only to a supply with a system impedance Zsys less than or equal to Zmax c 6V d 6T1 Connect the backup heater power supply as follows a b X6M F1B Q1DI a Factory mounted cable connected to the backup heater c...

Page 12: ... case of an electricity meter with transistor output check the polarity The positive polarity MUST be connected to X5M 6 and X5M 4 the negative polarity to X5M 5 and X5M 3 1 Connect the electricity meters cable to the appropriate terminals as shown in the illustration below X5M S2S S3S 3 4 56 2 Fix the cable with cable ties to the cable tie mountings 4 5 7 To connect the domestic hot water pump 1 ...

Page 13: ... normally closed cable to the appropriate terminals as shown in the illustration below X5M 9 10 2 Fix the cable with cable ties to the cable tie mountings NOTICE Make sure to select and install the safety thermostat according to the applicable legislation In any case to prevent unnecessary tripping of the safety thermostat we recommend the following The safety thermostat is automatically resettabl...

Page 14: ... Legend for tables You can access the installer settings using two different methods However NOT all settings are accessible via both methods If so the corresponding table columns in this chapter are set to N A not applicable Method Column in tables Accessing settings via the breadcrumb in the home menu screen or the menu structure To enable breadcrumbs press the button in the home screen For exam...

Page 15: ...t in backup heater the type of heater can be viewed but not changed Code Description 9 3 1 E 03 2 3V 3 6V 4 9W Domestic hot water The following setting determines if the system can prepare domestic hot water or not and which tank is used Set this setting according to the actual installation Code Description 9 2 1 E 05 a E 06 a E 07 a No DHW No tank installed EKHWS E Tank with booster heater instal...

Page 16: ... thermostatic valve to avoid too high temperatures towards a low temperature emitter Make sure you set the emitter types for the main zone 2 7 and for the additional zone 3 7 correctly in accordance with the connected emitter NOTICE An overpressure bypass valve can be integrated in the system Keep in mind that this valve might not be shown on the illustrations 5 2 4 Configuration wizard Backup hea...

Page 17: ...Enable leaving water temperature modulation and increase the maximum modulation 2 C Control Define how the operation of the unit is controlled Control In this control Leaving water Unit operation is decided based on the leaving water temperature regardless the actual room temperature and or heating or cooling demand of the room External room thermostat Unit operation is decided by the external the...

Page 18: ...her dependent zone Main zone or additional zone heating Main zone or additional zone cooling Domestic hot water X1 X2 Examples of outdoor ambient temperature Y1 Y2 Examples of desired tank temperature or leaving water temperature The icon corresponds to the heat emitter for that zone Underfloor heating Fan coil unit Radiator Domestic hot water tank 5 2 8 Configuration wizard Tank This part only ap...

Page 19: ...ou can set additional settings using the main menu screen and its submenus The most important settings are presented here 5 3 1 Main zone Thermostat type Only applicable in external room thermostat control NOTICE If an external room thermostat is used the external room thermostat will control the room frost protection However the room frost protection is only possible if C 2 Space heating cooling ...

Page 20: ...ilibrium temperature Operation 9 4 Booster heater Capacity BSH allowance schedule BSH eco timer Operation 9 6 Balancing Space heating priority Priority temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 8 Benefit kWh power supply Benefit kWh power supply Allow heater Allow pump 9 9 Power consumption control Power consumption control Ty...

Page 21: ...he voltage on the identification label of the unit There are NO loose connections or damaged electrical components in the switch box There are NO damaged components or squeezed pipes on the inside of the indoor and outdoor units Backup heater circuit breaker F1B field supply is turned ON Only for tanks with built in booster heater Booster heater circuit breaker F2B field supply is turned ON There ...

Page 22: ...test run the correct operation of the unit can be checked by monitoring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 6 2 4 To perform an actuator test run Conditions Make sure all operation is disabled Go to C Operation and turn off Room Space heating cool...

Page 23: ...ult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 7 Hand over to the user Once the test run is finished and the unit operates properly please make sure the following is clear for the user Fill in the installer setting table in the operation manual with the actual settings Mak...

Page 24: ...ing water IN a2 Space heating water OUT b1 Gas refrigerant IN heating mode condenser b2 Liquid refrigerant OUT heating mode condenser c1 Liquid refrigerant IN cooling mode evaporator c2 Gas refrigerant OUT cooling mode evaporator d Plate heat exchanger e Shut off valve for service f Magnetic filter dirt separator g Safety valve h Air purge i Drain valve j Flow sensor k Expansion vessel l Backup he...

Page 25: ... wired On OFF thermostat wired On OFF thermostat wireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Position in switch box English Translation Position in switch box Position in switch box Legend A1P Main PCB A2P On OFF thermostat PC power circuit A3P Heat pump convector A4P Digital I O PCB A8P Demand PCB A9P Status indicator A10P MMI use...

Page 26: ...witch box 5 Ext thermistor 5 External thermistor SWB Switch box English Translation 6 Field supplied options 6 Field supplied options 12 V DC pulse detection voltage supplied by PCB 12 V DC pulse detection voltage supplied by PCB 230 V AC supplied by PCB 230 V AC supplied by PCB Continuous Continuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical...

Page 27: ... interface Optional parts Optional parts External room thermostat Heat pump convector main and or additional zone 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation 2 core 2 core communication 2x0 75 2 core 2 core signal 2 core signal 2 core 2 core communication 2x0 75 2 core 2 core 2 core signal 2 core 2 core Only for KRP1HB Changeover to ext...

Page 28: ...H 1150 200 200 500 mm 450 8 4 Table 2 Minimum floor area indoor unit mc kg Minimum floor area m H 1150 mm H 1200 mm H 1300 mm H 1400 mm H 1500 mm H 1600 mm H 1700 mm H 1800 mm 1 84 8 57 7 84 6 64 5 92 5 51 5 16 4 84 4 57 1 86 8 76 8 02 6 78 5 98 5 57 5 21 4 90 4 62 1 88 8 95 8 19 6 93 6 05 5 63 5 27 4 95 4 67 1 90 9 14 8 36 7 08 6 11 5 69 5 32 5 00 4 72 INFORMATION H Height measured from the botto...

Page 29: ...when H is between two H values from the table consider the value that corresponds to the lower H value from the table If H 1450 mm consider the floor area that corresponds to H 1400 mm For intermediate dm values i e when dm is between two dm values from the table consider the value that corresponds to the higher dm value from the table If dm 1 55 kg consider the value that corresponds to dm 1 6 kg...

Page 30: ......

Page 31: ......

Page 32: ...4P495266 1D 2019 10 Copyright 2017 Daikin 4P495266 1 D 00000005 ...

Reviews: