4 Installation
Installation manual
11
EHBH/X04+08DA
Daikin Altherma 3 R W
4P495266-1D – 2019.10
Backup
heater type
Backup
heater
capacity
Power
supply
Maximum
running
current
Z
max
*6V
2 kW
1N~ 230 V
(c)
9 A
—
4 kW
1N~ 230 V
(c)
17 A
(a)(b)
0.22 Ω
6 kW
1N~ 230 V
(c)
26 A
(a)(b)
0.22 Ω
2 kW
3~ 230 V
(d)
5 A
—
4 kW
3~ 230 V
(d)
10 A
—
6 kW
3~ 230 V
(d)
15 A
—
*9W
3 kW
3N~ 400 V
4 A
—
6 kW
3N~ 400 V
9 A
—
9 kW
3N~ 400 V
13 A
—
(a)
Equipment complying with EN/IEC 61000-3-12 (European/
International Technical Standard setting the limits for
harmonic currents produced by equipment connected to
public low-voltage systems with input current >16 A and
≤75 A per phase.).
(b)
This equipment complies with EN/IEC 61000‑3‑11
(European/International Technical Standard setting the
limits for voltage changes, voltage fluctuations and flicker in
public low-voltage supply systems for equipment with rated
current ≤75 A) provided that the system impedance Z
sys
is
less than or equal to Z
max
at the interface point between the
user's supply and the public system. It is the responsibility
of the installer or user of the equipment to ensure, by
consultation with the distribution network operator if
necessary, that the equipment is connected only to a
supply with a system impedance Z
sys
less than or equal to
Z
max
.
(c)
(6V)
(d)
(6T1)
Connect the backup heater power supply as follows:
a
b
X6M
F1B
Q1DI
a
Factory-mounted cable connected to the backup heater
contactor inside the switch box (K5M for *6V and *9W
models)
b
Field wiring (see table below)
Model (power
supply)
Connections to backup heater power
supply
*6V (6V: 1N~ 230 V)
1N~, 50 Hz
230 V AC
SWB
4
3
6
5
2
1
K5M
14
13
Q1DI
1
2
3
4
5
6
7
8
F1B
I
I
I
I
N
L
X6M
BRN
GRY
BLU1
BLU2
*6V (6T1: 3~ 230 V)
SWB
3~, 50 Hz
230 V AC
4
3
6
5
2
1
K5M
14
13
1
2
3
4
5
6
7
8
F1B
I
I
I
I
Q1DI
L1
L2
L3
X6M
BRN
GRY
BLU1
BLU2
*9W (3N~ 400 V)
3N~, 50 Hz
400 V AC
SWB
Q1DI
L1
L2
L3
N
1
2
3
4
5
6
7
8
F1B
I
I
I
I
X6M
2
1
K5M
4
3
6
5
14
13
BRN
GRY
BLK
BLU
F1B
Overcurrent fuse (field supply). Recommended fuse for *6V
and *9W models: 4‑pole; 20 A; curve 400 V; tripping class
C.
K1M
Contactor (in the switch box)
K5M
Safety contactor (in the switch box)
Q1DI
Earth leakage circuit breaker (field supply)
SWB
Switch box
X6M
Terminal (field supply)