3 Operation

Operation manual

7

EHFZ03S18DJ3V
Daikin Altherma 3 R F
4P596819-1 – 2019.10

t

60°C

00:00

07:00

50°C

15°C

40°C

14:00

21:00

1

2

3

4

5

Tt

T

t

Domestic hot water tank temperature

t

Time

3.4.3

Sch reheat mode

In sch reheat mode (   ), the domestic hot water control is
the  same  as  in  scheduled  mode.  However,  when  the  DHW  tank
temperature drops below a preset value (=reheat tank temperature –
hysteresis  value;  example:  35°C),  the  DHW  tank  heats  up  until  it
reaches  the  reheat  set  point  (example:  45°C).  This  ensures  that  a
minimum amount of hot water is available at all times.

Example: 

t

Tt

60°C

00:00

07:00

50°C
45°C

15°C

14:00

21:00

35°C

1

2

4

5

3

T

t

Domestic hot water tank temperature

t

Time

3.4.4

Using the DHW tank temperature home
page

Typical DHW tank temperature home pages

Depending on the user profile, the user interface gives you either a
basic  or  a  detailed  home  page.  The  examples  in  the  illustrations
below are in DHW tank mode = Scheduled.

User profile = 

Basic

User profile = 

Detailed

15:20

60°C

Storage comfort

Tank

Mon

15:20

60°C

00:00

Mon

Tue

Tank

Storage comfort

To read out and adjust the desired reheat temperature (in
scheduled and reheat mode)

1

Go to [7.4.3.3]: 

 > 

User settings

 > 

Preset values

 > 

Tank

temperature

 > 

Reheat

.

Result: 

You can read out the desired reheat temperature.

2

Press 

 or 

 to adjust.

To read out and overrule the active or next scheduled desired
temperature (in scheduled mode or sch reheat mode)

1

Go to the DHW tank temperature home page (

Tank

).

Result: 

60°C

 is displayed.

2

Press 

 or 

 to overrule.

Note: 

If  the  desired  temperature  is  weather  dependent,  you  cannot

change it on the home page.

3.4.5

Using the DHW tank booster mode

To activate the DHW tank booster mode (user profile = Basic)

1

Go to the DHW tank temperature home page (

Tank

).

2

Press 

 for more than 5 seconds.

To activate the DHW tank booster mode (user profile = Detailed)

1

Go to the DHW tank temperature home page (

Tank

).

2

Press 

 to select  .

3.5

Schedules: Example

INFORMATION

The procedures to program other schedules are similar.

In this example:

▪ Monday = Tuesday = Wednesday = Thursday = Friday

▪ Saturday = Sunday

To program the schedule

1

Select 

Empty

 and press 

.

2

Program the schedule for Monday. See below for more details.

3

Copy  from  Monday  to  Tuesday,  Wednesday,  Thursday  and
Friday. See below for more details.

4

Program the schedule for Saturday.

5

Copy from Saturday to Sunday.

6

Save  the  schedule  and  give  it  a  name.  See  below  for  more
details.

To program the schedule for Monday

1

Use 

 and 

 to select Monday.

2

Press 

 to enter the schedule for Monday.

3

Program the schedule for Monday:

▪ Use 

 and 

 to select an entry.

▪ Use 

 and 

 to change the value of an entry.

To copy from one day to another

1

Select  the  day  from  which  you  want  to  copy  and  press 

.

Example: 

Monday.

2

Select 

Copy day

 and press 

.

3

Set the days you want to copy to 

Yes

 and press 

Example:

Tuesday = 

Yes

, Wednesday = 

Yes

, Thursday = 

Yes

 and Friday

Yes

.

To save the schedule

1

Press 

, select 

Save schedule

 and press 

.

2

Change  the  name  and  press 

.  (Only  applicable  for  room

temperature schedules). 

Example: 

MyWeekSchedule

To select which schedule you currently want to use

1

Go to [5]: 

 > 

Select schedules

.

2

Select for which control you want to use a schedule. 

Example:

[5.1] 

Room temperature

.

3

Select  for  which  operation  mode  you  want  to  use  a  schedule.

Example: 

[5.1.1] 

Heating

 .

4

Select a predefined or user‑defined schedule and press 

.

Summary of Contents for Altherma 3 R F

Page 1: ...Operation manual Daikin Altherma 3 R F English Operation manual Daikin Altherma 3 R F EHFZ03S18DJ3V...

Page 2: ...4 Symptom Heat pump failure 9 6 5 Symptom The system is making gurgling noises after commissioning 9 7 Disposal 9 8 Glossary 10 1 Installer settings Tables to be filled in by installer 1 1 Quick wizar...

Page 3: ...n of the installation good practices reference data Format Digital files on http www daikineurope com support and manuals product information Addendum book for optional equipment Additional info about...

Page 4: ...rature home page Desired room temperature according to the selected schedule On the DHW tank temperature home page DHW tank mode Scheduled mode DHW tank mode Reheat mode DHW tank mode Scheduled reheat...

Page 5: ...unning hours Version Energy metering Consumed elec Produced energy Error information Error history Contact helpdesk number Version User interface Indoor unit Outdoor unit User settings Display Tempera...

Page 6: ...lue but will return to the scheduled value at the next scheduled action To change the mode from scheduled to preset value Prerequisite User profile Detailed 1 Go to the room temperature home page Room...

Page 7: ...ther dependent you cannot change it on the home page 3 4 5 Using the DHW tank booster mode To activate the DHW tank booster mode user profile Basic 1 Go to the DHW tank temperature home page Tank 2 Pr...

Page 8: ...water pump only during periods of the day when instant hot water is necessary Example In the morning and evening 5 Maintenance and service 5 1 Overview Maintenance and service The installer has to per...

Page 9: ...eater can serve as an emergency heater and either automatically or non automatically take over the heat load When auto emergency is activated and a heat pump failure occurs the backup heater will auto...

Page 10: ...FZ03S18DJ3V Daikin Altherma 3 R F 4P596819 1 2019 10 8 Glossary DHW Domestic hot water Hot water used in any type of building for domestic purposes LWT Leaving water temperature Water temperature at t...

Page 11: ......

Page 12: ...4P596819 1 2019 10 Copyright 2019 Daikin 4P383117 1 D 0000000 4P596819 1 0000000 Verantwortung f r Energie und Umwelt...

Reviews: