9 Disposal

Operation manual

20

EBLA09~16DA + EDLA09~16DA

Daikin Altherma 3 M

4P620243-1 – 2020.06

8.6

Symptom: The system is making
gurgling noises after
commissioning

Possible cause

Corrective action

There is air in the system.

Purge air from the system.

(a)

Various malfunctions.

Check if 

 or 

 is displayed

on the home screen of the user
interface. See 

"8.1 To display the

help text in case of a
malfunction" 

[

4

 19] for more

information about the
malfunction.

(a)

We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:

WARNING

Air  purging  heat  emitters  or  collectors.

  Before  you

purge  air  from  heat  emitters  or  collectors,  check  if 

  or

 is displayed on the home screen of the user interface.

▪ If not, you can purge air immediately.

▪ If  yes,  make  sure  that  the  room  where  you  want  to

purge air is sufficiently ventilated. 

Reason:

 Refrigerant

might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.

9

Disposal

NOTICE

Do  NOT  try  to  dismantle  the  system  yourself:  dismantling
of  the  system,  treatment  of  the  refrigerant,  oil  and  other
parts  MUST  comply  with  applicable  legislation.  Units
MUST  be  treated  at  a  specialised  treatment  facility  for
reuse, recycling and recovery.

10

Glossary

DHW = Domestic hot water

Hot  water  used,  in  any  type  of  building,  for  domestic
purposes.

LWT = Leaving water temperature

Water temperature at the water outlet of the unit.

11

Installer settings: Tables to
be filled in by installer

11.1

Configuration wizard

Setting

Fill in…

System

Setting

Fill in…

Backup heater type

 [9.3.1]

Domestic hot water

 [9.2.1]

Emergency

 [9.5]

Number of zones

 [4.4]

Glycol Filled system

(overview field setting [E‑0D])

Booster heater capacity

[9.4.1] (if applicable)

Backup heater

Voltage

 [9.3.2]

Configuration

 [9.3.3]

Capacity step 1

 [9.3.4]

Additional capacity step 2

[9.3.5] (if applicable)

Main zone

Emitter type

 [2.7]

Control

 [2.9]

Setpoint mode

 [2.4]

Schedule

 [2.1]

WD curve type

 [2.E]

Additional zone

 (only if [4.4]=1, dual zone)

Emitter type

 [3.7]

Control

 (read only) [3.9]

Setpoint mode

 [3.4]

Schedule

 [3.1]

WD curve type

 [3.C] (read only)

Tank

 (if applicable)

Heat up mode

 [5.6]

Comfort setpoint

 [5.2]

Eco setpoint

 [5.3]

Reheat setpoint

 [5.4]

Setpoint mode

 [5.B]

WD curve type

 [5.E] (read only)

11.2

Settings menu

Setting

Fill in…

Main zone

Thermostat type

 [2.A]

Additional zone

 (if applicable)

Thermostat type

 [3.A]

Information

Dealer information

 [8.3]

Summary of Contents for Altherma 3 M Series

Page 1: ...Operation manual Daikin Altherma 3 M English Operation manual Daikin Altherma 3 M EBLA09 16DAV3 EBLA09 16DAW1 EBLA09 16DA3V3 EBLA09 16DA3W1 EDLA09 16DAV3 EDLA09 16DAW1 EDLA09 16DA3V3 EDLA09 16DA3W1...

Page 2: ...wizard 20 11 2 Settings menu 20 1 About this document Thank you for purchasing this product Please Read the documentation carefully before operating the user interface to ensure the best possible perf...

Page 3: ...unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are marked with the following symbol This means that electrical and electronic product...

Page 4: ...nd subsequently into the room when you purge air from the heat emitters or collectors 3 About the system Depending on the system layout the system can Heat up a space Cool down a space Produce domesti...

Page 5: ...2 2 Set operation to On or Off To change the desired room temperature During room temperature control you can use the room temperature setpoint screen to read out and adjust the desired room temperat...

Page 6: ...mation see also 5 4 Turning operation ON or OFF 411 5 6 Space heating cooling control 412 5 8 Schedule screen Example 414 5 9 Weather dependent curve 416 User reference guide 4 3 Domestic hot water To...

Page 7: ...min of non interaction with the user interface the screen darkens Pressing any button or rotating any dial awakens the display Dials and buttons You use the dials and buttons To navigate through the...

Page 8: ...4 Quiet Activation Schedule Level 1 5 Setpoint range Heating minimum Heating maximum Cooling minimum Cooling maximum 4 Space heating cooling Operation mode Operation mode schedule Room comfort setpoin...

Page 9: ...ive Powerful operation mode active c Emergency Heat pump failure and system operates in Emergency mode or heat pump is forced off d Current date and time e Smart energy e1 Smart energy is available vi...

Page 10: ...in zone Shows the applicable symbol for your main zone emitter type Set the leaving water temperature for the main zone 3 Additional zone Restriction Only displayed if there are two leaving water temp...

Page 11: ...e home screen will be greyed out Room temperature control 1 6 bar 55 21 35 45 a 1 6 bar 55 21 35 45 b a Room temperature control ON b Room temperature control OFF Space heating cooling operation 1 6 b...

Page 12: ...pace You have to tell the system which operation mode to use To tell the system which space operation to use you can You can Location Check which space operation mode is currently used Home screen Set...

Page 13: ...the DHW tank mode is reheat the risk for capacity shortage and comfort problem is significant In case of frequent reheat operation space heating cooling function is regularly interrupted 5 7 2 Schedu...

Page 14: ...This example shows how to set a room temperature schedule in heating mode for the main zone INFORMATION The procedures to program other schedules are similar To program the schedule overview Example Y...

Page 15: ...Tue Sun User defined 1 C 4 Select Paste Delete Edit Copy Paste Result Mon Sat Wed Fri Thu Tue Sun User defined 1 C 5 Repeat this action for all other weekdays Mon Sat Wed Fri Thu Tue Sun User defined...

Page 16: ...g Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 5 9 4 Using weather d...

Page 17: ...to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent T...

Page 18: ...sary Example In the morning and evening 7 Maintenance and service 7 1 Overview Maintenance and service The installer has to perform a yearly maintenance You can find the contact helpdesk number via th...

Page 19: ...consumes extra energy See 5 7 4 Using DHW powerful operation 414 If the problems recurs daily do one of the following Increase the DHW tank temperature preset value See the user reference guide Adjust...

Page 20: ...smantling of the system treatment of the refrigerant oil and other parts MUST comply with applicable legislation Units MUST be treated at a specialised treatment facility for reuse recycling and recov...

Page 21: ......

Page 22: ......

Page 23: ......

Page 24: ...4P620243 1 2020 06 Copyright 2020 Daikin 4P620243 1 0000000F Verantwortung f r Energie und Umwelt...

Reviews: