8.6
Symptom: The system is making
gurgling noises after
commissioning
Possible cause
Corrective action
There is air in the system.
Purge air from the system.
(a)
Various malfunctions.
Check if
or
is displayed
on the home screen of the user
interface. See
help text in case of a
malfunction"
19] for more
information about the
malfunction.
(a)
We recommend to purge air with the air purge function of the unit
(to be performed by the installer). If you purge air from the heat
emitters or collectors, mind the following:
WARNING
Air purging heat emitters or collectors.
Before you
purge air from heat emitters or collectors, check if
or
is displayed on the home screen of the user interface.
▪ If not, you can purge air immediately.
▪ If yes, make sure that the room where you want to
purge air is sufficiently ventilated.
Reason:
Refrigerant
might leak into the water circuit, and subsequently into
the room when you purge air from the heat emitters or
collectors.
9
Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling
of the system, treatment of the refrigerant, oil and other
parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for
reuse, recycling and recovery.
10
Glossary
DHW = Domestic hot water
Hot water used, in any type of building, for domestic
purposes.
LWT = Leaving water temperature
Water temperature at the water outlet of the unit.
11
Installer settings: Tables to
be filled in by installer
11.1
Configuration wizard
Setting
Fill in…
System
Setting
Fill in…
Backup heater type
[9.3.1]
Domestic hot water
[9.2.1]
Emergency
[9.5]
Number of zones
[4.4]
Glycol Filled system
(overview field setting [E‑0D])
Booster heater capacity
[9.4.1] (if applicable)
Backup heater
Voltage
[9.3.2]
Configuration
[9.3.3]
Capacity step 1
[9.3.4]
Additional capacity step 2
[9.3.5] (if applicable)
Main zone
Emitter type
[2.7]
Control
[2.9]
Setpoint mode
[2.4]
Schedule
[2.1]
WD curve type
[2.E]
Additional zone
(only if [4.4]=1, dual zone)
Emitter type
[3.7]
Control
(read only) [3.9]
Setpoint mode
[3.4]
Schedule
[3.1]
WD curve type
[3.C] (read only)
Tank
(if applicable)
Heat up mode
[5.6]
Comfort setpoint
[5.2]
Eco setpoint
[5.3]
Reheat setpoint
[5.4]
Setpoint mode
[5.B]
WD curve type
[5.E] (read only)
11.2
Settings menu
Setting
Fill in…
Main zone
Thermostat type
[2.A]
Additional zone
(if applicable)
Thermostat type
[3.A]
Information
Dealer information
[8.3]