10/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.I
[5-0E]
1
9.I
[6-00]
R/W
2~40°C, step: 1°C
8°C
9.I
[6-01]
R/W
0~10°C, step: 1°C
2°C
9.I
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
9.I
[6-03]
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
9.I
[6-04]
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
9.I
[6-07]
0
9.I
[6-08]
R/W
2~20°C, step: 1°C
10°C
9.I
[6-09]
0
9.I
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.I
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.I
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.I
[6-0E]
R/W
(*3) [E-07]=0 or 7:
40~ 60°C, step: 1°C
60°C
(*3) [E-07]=3 or 5 or 8:
40~80°C, step: 1°C
80°C
(*4) : 40~65°C, step: 1°C
65°C
9.I
[7-00]
R/W
0~4°C, step: 1°C
0°C
9.I
[7-01]
R/W
2~40°C, step: 1°C
2°C
9.I
[7-02]
R/W
0: 1 LWT zone
1: 2 LWT zones
9.I
[7-03]
2.5
9.I
[7-04]
0
9.I
[7-05]
R/W
0: Very high
1: High
2: Medium
3: Low
4: Very low
9.I
[7-06]
R/W
0: Disabled
1: Enabled
9.I
[7-07]
R/W
0: Disabled
1: Enabled
9.I
[7-08]
--
0
9.I
[7-09]
20
9.I
[7-0A]
R/W
20~95%, step 5%
95%
9.I
[7-0B]
R/W
20~95%, step 5%
95%
9.I
[7-0C]
R/W
20~300 seconds, step 5 sec
125 seconds
9.I
[8-00]
R/W
0~20 min, step 1 min
1 min
9.I
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.I
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour [E-07]=1
3 hour [E-07]
≠
1
9.I
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.I
[8-04]
R/W
0~95 min, step: 5 min
95 min
9.I
[8-05]
R/W
0: No
1: Yes
9.I
[8-06]
R/W
0~10°C, step: 1°C
5°C
9.I
[8-07]
R/W
[9-03]~[9-02], step: 1°C
18°C
9.I
[8-08]
R/W
[9-03]~[9-02], step: 1°C
20°C
9.I
[8-09]
R/W
[9-01]~[9-00], step: 1°C
35°C
9.I
[8-0A]
R/W
[9-01]~[9-00], step: 1°C
33°C
9.I
[8-0B]
13
--
What is the requested limit for DI4?
The temperature difference determining the heat pump ON temperature.
The temperature difference determining the heat pump OFF temperature.
What is the capacity of the booster heater?
What is the capacity of the backup heater step 1?
What is the capacity of the backup heater step 2?
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
Backup heater voltage
Additional zone fixed pump PWM, in case a bizone kit is installed.
Main zone fixed pump PWM, in case a bizone kit is installed.
Time needed by the mixing valve to turn from one side to the other, in case a
bizone kit is installed.
--
What is the hysteresis to be used in reheat mode?
--
What is the desired comfort storage temperature?
What is the desired eco storage temperature?
What is the desired reheat temperature?
What is the desired DHW production type?
What is the desired comfort main LWT in cooling?
What is the desired eco main LWT in cooling?
What is the desired comfort main LWT in heating?
--
--
Boiler efficiency
Compressor forced OFF
BBR16 activation*
*BBR16 settings are only visible when the language of the user interface is set to
Swedish
Minimum running time for domestic hot water operation.
--
What is the maximum temperature setpoint?
Domestic hot water booster heater overshoot temperature.
Domestic hot water booster heater hysteresis.
How many leaving water temperature zones are there?
What is the desired eco main LWT in heating?
--
Maximum running time for domestic hot water operation.
Anti-recycling time.
Booster heater delay timer.
Additional running time for the maximum running time.
Allow modulation of the LWT to control the room temp?
Leaving water temperature maximum modulation.
4P644734-1A - 2022.03
(*1) *6V*_(*2) *9W*_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*_
(*8) E_(*9) E7