6/13
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
9.1.A
[0-04]
R/W
[9-07]~[9-08]°C, step: 1°C
[2-0C]=0
18°C
[2-0C]=1
7°C
[2-0C]=2
18°C
9.1.A
[0-05]
R/W
[9-07]~[9-08]°C, step: 1°C
22°C
9.1.A
[0-06]
R/W
25~43°C, step: 1°C
35°C
9.1.A
[0-07]
R/W
10~25°C, step: 1°C
20°C
└─
Tank
9.1.B.1
[6-0D]
R/W
0: Reheat only
1: sched.
2: Scheduled only
9.1.B.2
[6-0A]
R/W
30~[6-0E]°C, step: 1°C
60°C
9.1.B.3
[6-0B]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.4
[6-0C]
R/W
30~min(50, [6-0E])°C, step: 1°C
45°C
9.1.B.5
[6-08]
R/W
2~20°C, step: 1°C
10°C
└─
Domestic hot water
9.2.1
[E-05]
[E-06]
[E-07]
R/W
No DHW (*3)
EKHW, small volume (*3)
Integrated (*4)
EKHW, big volume (*3)
EKHWP (*3)
3rd party, small coil (*3)
3rd party, big coil (*3)
9.2.2
[D-02]
R/W
0: No DHW pump
1: Instant hot water
2: Disinfection
3: Circulation
4: Circulation and disinfection
9.2.4
[D-07]
R/W
0: No
1: Yes
└─
Back up heater
9.3.1
[E-03]
R/O
3: 6V (*1)
4: 9W (*2)
9.3.2
[5-0D]
R/W (*1)
R/O (*2)
0: 230V, 1~ (*1)
1: 230V, 3~ (*1)
2: 400V, 3~ (*2)
9.3.3
[4-0A]
R/W
1: 1/1+2 (*1) (*2)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.3.4
[6-03]
R/W
0~10kW, step: 0,2kW
2kW (*1)
3kW (*2)
9.3.5
[6-04]
R/W
0~10kW, step: 0,2kW
4kW (*1)
6kW (*2)
9.3.6
[5-00]
R/W
0: No (*9)
1: Yes (*8)
9.3.7
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.3.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
└─
Booster heater
9.4.1
[6-02]
R/W
0~10kW, step: 0,2kW
3kW (*3)
0kW (*4)
9.4.3
[8-03]
R/W
20~95 min, step: 5 min
50 min
9.4.4
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
└─
Emergency
9.5.1
[4-06]
R/W
0: Manual
1: Automatic
2: Auto red SH/ DHW ON
3: Auto red SH/ DHW OFF
4: Auto normal SH/ DHW OFF
9.5.2
[7-06]
R/W
0: Disabled
1: Enabled
└─
Balancing
9.6.1
[5-02]
R/W
0: Disabled
1: Enabled
9.6.2
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.6.3
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.6.4
[8-02]
R/W
0~10 hour, step: 0,5 hour
0,5 hour [E-07]=1
3 hour [E-07]
≠
1
9.6.5
[8-00]
R/W
0~20 min, step 1 min
1 min
9.6.6
[8-01]
R/W
5~95 min, step: 5 min
30 min
9.6.7
[8-04]
R/W
0~95 min, step: 5 min
95 min
Installer settings
Leaving water value for high ambient temp. for LWT add zone cooling WD curve.
Leaving water value for low ambient temp. for LWT add zone cooling WD curve.
High ambient temp. for LWT add zone cooling WD curve.
Low ambient temp. for LWT add zone cooling WD curve.
Heat up mode
Comfort setpoint
Eco setpoint
Reheat setpoint
Reheat hysteresis
Domestic hot water
DHW pump
Solar
BUH type
Voltage
Configuration
Capacity step 1
Additional capacity step 2
Equilibrium: Deactivate backup heater (or external backup heat source in case of a
bivalent system) above the equilibrium temperature for space heating?
Equilibrium temperature
Operation
Capacity
BSH eco timer
Operation
Emergency
Compressor forced OFF
Space heating priority
Priority temperature
Offset BSH setpoint
Anti-recycle timer
Minimum running timer
Maximum running timer
Additional timer
4P644734-1A - 2022.03
(*1) *6V*_(*2) *9W*_
(*3) ETB*_(*4) ETV*_
(*5) *X*_(*6) *H*_(*7) *SU*_
(*8) E_(*9) E7