5 Piping installation

Installation manual

8

ETBH/9W

Daikin Altherma 3 H HT W

4P644727-1 – 2021.02

75°C 

(*)

89°C

 (*)

75°C

 (*)

M

M

EXAMPLE

(*) Maximum temperature for piping and accessories

5.1.1

To check the water volume and flow rate

Minimum water volume

Check  that  the  total  water  volume  in  the  installation  is  minimum  20
litres, the internal water volume of the outdoor unit NOT included.

NOTICE

When  circulation  in  each  space  heating/cooling  loop  is
controlled by remotely controlled valves, it is important that
the minimum water volume is guaranteed, even if all of the
valves are closed.

Minimum flow rate

Check that the minimum flow rate in the installation is guaranteed in
all  conditions.  This  minimum  flow  rate  is  required  during  defrost/
backup  heater  operation.  For  this  purpose,  use  the  overpressure
bypass valve delivered with the unit, and respect the minimum water
volume.

Minimum required flow rate

25 l/min

NOTICE

To guarantee proper operation it is recommended to have
a minimum flow of 28 l/min during DHW.

NOTICE

If  glycol  was  added  to  the  water  circuit,  and  the
temperature  of  the  water  circuit  is  low,  the  flow  rate  will
NOT  be  displayed  on  the  user  interface.  In  this  case,  the
minimum  flow  rate  can  be  checked  by  way  of  the  pump
test (check that the user interface does NOT display error
7H).

NOTICE

When circulation in each or certain space heating loops is
controlled by remotely controlled valves, it is important that
the minimum flow rate is guaranteed, even if all valves are
closed. In case the minimum flow rate cannot be reached,
a flow error 7H will be generated (no heating or operation).

See the installer reference guide for more information.

See  the  recommended  procedure  as  described  in 

"8.2  Checklist

during commissioning"

 [

4

 30].

5.1.2

Third-party tank requirements

In  case  of  a  third-party  tank,  the  tank  shall  adhere  to  the  following
requirements:

▪ The heat exchanger coil of the tank is ≥1.05 m².

▪ The  tank  thermistor  must  be  located  above  the  heat  exchanger

coil.

▪ The  booster  heater  must  be  located  above  the  heat  exchanger

coil.

NOTICE

Performance.

  Performance  data  for  third-party  tanks

CANNOT  be  provided,  and  performance  CANNOT  be
guaranteed.

NOTICE

Configuration.

 Configuration of a third-party tank depends

on the size of the heat exchanger coil of the tank. For more
information, see the installer reference guide.

5.2

Connecting water piping

5.2.1

To connect the water piping

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  field
piping  and  make  sure  the  piping  is  aligned  properly.
Deformation of the piping can cause malfunctioning of the
unit.

NOTICE

Do  NOT  use  excessive  force  when  connecting  the  piping.
Deformation of the piping can cause malfunctioning of the
unit.

1

Connect the O-rings and shut-off valves to the indoor unit water
connections.

2

Connect the outdoor unit field piping on the water IN connection
(a) of the indoor unit.

3

Connect  the  space  heating/cooling  field  piping  on  the  space
heating water OUT connection (b) of the indoor unit.

b

a

a

Water IN (screw connection, 1")

b

Space heating water OUT (screw connection, 1")

Summary of Contents for Altherma 3 H HT W ETBH16EF6V

Page 1: ...https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT W English Installation manual Daikin Altherma 3 H HT W ETBH16EF6V ETBH16EF9W ETBX16EF6V ETBX16EF9W...

Page 2: ...yny odpov daj n sleduj c m norm m nebo normativn m dokument m u skladu sa slijede im standardom ima ili drugim normativnim dokumentom ima uz uvjet da se oni koriste u skladu s na im uputama 16 17 18 1...

Page 3: ...21 7 2 4 Configuration wizard Backup heater 23 7 2 5 Configuration wizard Main zone 24 7 2 6 Configuration wizard Additional zone 25 7 2 7 Configuration wizard Tank 25 7 3 Weather dependent curve 26 7...

Page 4: ...trical device Possible consequence Electric shock or fire In case of freeze protection by glycol WARNING Ethylene glycol is toxic WARNING Due to the presence of glycol corrosion of the system is possi...

Page 5: ...heating operation 5 30 C Space cooling operation 5 35 C Domestic hot water production 5 35 C INFORMATION Cooling is only applicable in case of Reversible models Heating only models conversion kit EKHB...

Page 6: ...1 2 3 2 5 Optional Remove the user interface panel NOTICE If you remove the user interface panel also disconnect the cables from the back of the user interface panel to prevent damage 3 3 1 2 X14Y X1...

Page 7: ...the applicable legislation 1 Connect a drain tube field supply to the drain pan connector as follows a a Drain pan connector It is recommended to use a tundish to collect the water 5 Piping installat...

Page 8: ...at the minimum flow rate is guaranteed even if all valves are closed In case the minimum flow rate cannot be reached a flow error 7H will be generated no heating or operation See the installer referen...

Page 9: ...out of the freeze protection valves Freeze protection by glycol About freeze protection by glycol Adding glycol to the water lowers the freezing point of water WARNING Ethylene glycol is toxic WARNIN...

Page 10: ...ning temperature of the freeze protection valve If lower freeze protection valves can open during cooling operation For more information see the installer reference guide 5 2 4 To fill the domestic ho...

Page 11: ...1 External sensor Outdoor 9 B 2 Ext amb sensor offset 9 B 3 Averaging time Item Description Remote indoor sensor See Installation manual of the remote indoor sensor Addendum book for optional equipmen...

Page 12: ...the wired room thermostat digital or analogue to the multi zoning base unit You need to connect the multi zoning base unit to the outdoor unit For cooling heating operation you also need to implement...

Page 13: ...lation CAUTION To guarantee the unit is completely earthed always connect the backup heater power supply and the earth cable The backup heater capacity can vary depending on the indoor unit model Make...

Page 14: ...y SWB Switch box X6M Terminal field supply NOTICE Do NOT cut or remove the backup heater power supply cable 6 3 3 To connect the shut off valve INFORMATION Shut off valve usage example In case of one...

Page 15: ...llustration below B C A A 6 5 4 3 S3S S2S C B X5M 5 6 3 4 X5M 3 Fix the cable with cable ties to the cable tie mountings 6 3 5 To connect the domestic hot water pump Wires 2 GND 0 75 mm DHW pump outpu...

Page 16: ...r unit 45 1 Front panel 1 2 3 2 Switch box cover 3 Switch box 2 Connect the space cooling heating ON OFF output cable to the appropriate terminals as shown in the illustration below 7 9 YC Y2 X2M 1 2...

Page 17: ...ital inputs cable to the appropriate terminals as shown in the illustration below B C A A 1 2 4 5 S6S S7S S8S S9S 3 C B A8P X801M a 5 4 3 2 1 a Installation of EKRP1AHTA is required 3 Fix the cable wi...

Page 18: ...the Smart Grid relay kit EKRELSG The 2 incoming Smart Grid contacts can activate the following Smart Grid modes Smart Grid contact Smart Grid operation mode 1 2 0 0 Free running Smart Grid contact Sm...

Page 19: ...Smart Grid relay kit installation STEP 2 Low voltage connections STEP 3 High voltage connections 1 High voltage Smart Grid contact 1 2 High voltage Smart Grid contact 2 a b Coil sides of relays c d C...

Page 20: ...ser interface for the first time via the unit the configuration wizard starts to help you configure the system Restart the configuration wizard If the system is already configured you can restart the...

Page 21: ...g the dial 00 01 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 0 1 2 3 4 Turn the left dial to select the second part of the setting 00 01 15 02 03 04 05 06 07 08 09 0A 0B 0C 0D 0E 1 5 Turn the right dial to...

Page 22: ...05 Thermistor type 0 Automatic 1 Type 1 5 8 6 0E Maximum tank temperature 60 C 75 C Emergency When the heat pump fails to operate the backup heater and or booster heater can serve as an emergency hea...

Page 23: ...e system filled with glycol 0 No 1 Yes Booster heater capacity The capacity of the booster heater must be set for the energy metering and or power consumption control feature to work properly When mea...

Page 24: ...m 55 C Variable 2 Radiator Maximum 70 C Fixed 10 C NOTICE Average emitter temperature Leaving water temperature Delta T 2 This means that for a same leaving water temperature setpoint the average emit...

Page 25: ...ration is allowed 1 Schedule reheat The domestic hot water tank is heated according to a schedule and between the scheduled heat up cycles reheat operation is allowed 2 Schedule only The domestic hot...

Page 26: ...ing Additional zone Cooling Tank only available to installers INFORMATION To operate weather dependent correctly configure the setpoint of the main zone additional zone or tank See 7 3 4 Using weather...

Page 27: ...Go to setpoint mode Set the setpoint mode to 3 4 Additional zone Setpoint mode WD heating fixed cooling OR Weather dependent Additional zone Cooling 3 4 Additional zone Setpoint mode Weather dependent...

Page 28: ...st protection However the room frost protection is only possible if C 2 Space heating cooling On Code Description 2 A C 05 External room thermostat type for the main zone 1 1 contact The used external...

Page 29: ...temperature Offset BSH setpoint Minimum running timer Anti recycle timer Maximum running timer Additional timer 9 A Energy metering Electricity meter 2 Electricity meter 1 9 B Sensors External sensor...

Page 30: ...nted The outdoor unit is properly mounted The following field wiring has been carried out according to this document and the applicable legislation Between the local supply panel and the outdoor unit...

Page 31: ...toring its leaving water temperature heating cooling mode and tank temperature domestic hot water mode To monitor the temperatures 1 In the menu go to Sensors 2 Select the temperature information 8 2...

Page 32: ...sult in cracking of the screed NOTICE For the underfloor heating screed dryout to be able to start make sure the following settings are met 4 00 1 C 02 0 D 01 0 4 08 0 4 01 1 9 Hand over to the user O...

Page 33: ...ing diagram Indoor unit 3D120613B R2T R1T B1PW B1L A B B e e k k f i g c a b h j d h S1L i A Indoor unit B Field installed a Space heating water OUT b Water IN connection c Pump d Expansion vessel e S...

Page 34: ...ireless On OFF thermostat wireless Ext thermistor External thermistor Heat pump convector Heat pump convector Add LWT Additional leaving water temperature On OFF thermostat wired On OFF thermostat wir...

Page 35: ...ntinuous current DHW pump output Domestic hot water pump output DHW pump Domestic hot water pump Electrical meters Electrical meters For HV smartgrid For high voltage Smart Grid For LV smartgrid For l...

Page 36: ...ce Only for KRTR wireless room thermostat Only for KRTW wired room thermostat 5 core for C H operation 4 core for H only operation 3 core for C H operation 2 core for H only operation communication 2...

Page 37: ......

Page 38: ......

Page 39: ......

Page 40: ...4P644727 1 2021 02 Copyright 2021 Daikin 4P644727 1 0000000S Verantwortung f r Energie und Umwelt...

Reviews: