5 Electrical installation

Installation manual

10

EPRA14~W1

Daikin Altherma 3 H HT

4P586100-1B – 2019.09

NOTICE

When freeze protection valves are installed, do NOT select
a  minimum  cooling  setpoint  lower  than  7°C  (7°C=default).
If  lower,  freeze  protection  valves  can  open  during  cooling
operation.

For more information, see the installer reference guide.

4.1.4

To insulate the water piping

The  piping  in  the  complete  water  circuit  MUST  be  insulated  to
prevent  condensation  during  cooling  operation  and  reduction  of  the
heating and cooling capacity.

Outdoor water piping insulation

NOTICE

Outside piping.

 Make sure the outside piping is insulated

as instructed to protect against hazards.

For  piping  in  free  air,  it  is  recommended  to  use  the  insulation
thickness  as  shown  in  below  table  as  a  minimum  (with  λ=0.039  W/
mK).

Piping length (m)

Minimum insulation thickness
(mm)

<20

19

20~30

32

30~40

40

40~50

50

For other cases the minimum insulation thickness can be determined
using the Hydronic Piping Calculation tool.

The  Hydronic  Piping  Calculation  tool  also  calculates  the  maximum
hydronic piping length from the indoor unit to the outdoor unit based
on the emitter pressure drop or the other way around.

The Hydronic Piping Calculation tool is part of the Heating Solutions
Navigator 

which 

can 

be 

reached 

via 

https://

professional.standbyme.daikin.eu

.

Please  contact  your  dealer  if  you  have  no  access  to  Heating
Solutions Navigator.

This  recommendation  ensures  good  operation  of  the  unit,  however,
local regulations may differ and shall be followed.

5

Electrical installation

DANGER: RISK OF ELECTROCUTION

WARNING

Rotating fan.

 Before powering ON or servicing the outdoor

unit, make sure that the discharge grille covers the fan as
protection against a rotating fan. See:

"6.2 To install the discharge grille" 

[

4

 14]

"6.3 To remove the discharge grille, and put the grille in
safety position" 

[

4

 15]

WARNING

ALWAYS use multicore cable for power supply cables.

CAUTION

Do NOT push or place redundant cable length in the unit.

NOTICE

The  distance  between  the  high  voltage  and  low  voltage
cables should be at least 50 mm.

5.1

About electrical compliance

Only for EPRA14~18DAV3

Equipment  complying  with  EN/IEC  61000‑3‑12  (European/
International  Technical  Standard  setting  the  limits  for  harmonic
currents  produced  by  equipment  connected  to  public  low-voltage
systems with input current >16 A and ≤75 A per phase.).

5.2

Guidelines when connecting the
electrical wiring

Tightening torques

Item

Tightening torque (N•m)

M4 (X1M, X2M)

1.2~1.5

M4 (earth)

5.3

To connect the electrical wiring on
the outdoor unit

1

Open  the  switch  box  cover.  See 

"3.3  To  open  the  outdoor

unit" 

[

4

 8].

2

Insert the cables at the back of the unit, and route them through
the  factory-mounted  cable  sleeves  into  the  switch  box.  For  the
power supply, use the factory-mounted cable.

d

c2

b2

c1

b1

a1

a2

a1+a2

Power supply cable (factory-mounted cable)

b1+b2

Interconnection cable (field supply)

c1+c2

(optional) Drain tube heater cable (field supply)

d

Cable sleeves (factory-mounted)

3

Inside  the  switch  box,  connect  the  wires  to  the  appropriate
terminals, and fix the cables with cable ties. See:

"5.3.1 In case of V3 models" 

[

4

 10]

"5.3.2 In case of W1 models" 

[

4

 12]

5.3.1

In case of V3 models

1

Power supply cable

:

▪ Use  the  factory-mounted  cable,  which  is  already  routed

through the frame.

▪ Connect the wires to the terminal block.
▪ Fix the cable with a cable tie.

Summary of Contents for Altherma 3 H HT Series

Page 1: ...Installation manual Daikin Altherma 3 H HT English https daikintechnicaldatahub eu Installation manual Daikin Altherma 3 H HT EPRA14DAV3 EPRA16DAV3 EPRA18DAV3 EPRA14DAW1 EPRA16DAW1 EPRA18DAW1...

Page 2: ...ll height unrestricted 1000 X X H 150 H 500 500 300 500 500 300 300 1000 500 1000 500 500 1000 500 1000 500 1000 300 X X H X X H General mm 3D124412 300 150 100 Top side obstacle No top side obstacle...

Page 3: ...r de acordo com o previsto em 10 11 12 13 14 15 16 17 18 under iagttagelse af bestemmelserne i enligt villkoren i gitt i henhold til bestemmelsene i noudattaen m r yksi za dodr en ustanoven p edpisu p...

Page 4: ...vastaava kyll stysl mp tila M C Kylm aine N Varmuuspainelaitteen asetus P bar Valmistusnumero ja valmistusvuosi katso mallin nimikilpi Maxim ln p pustn tlak PS K bar Minim ln maxim ln p pustn teplota...

Page 5: ...l Quick guide for basic usage Format Paper in the box of the indoor unit User reference guide Detailed step by step instructions and background information for basic and advanced usage Format Digital...

Page 6: ...lish Translation General General No top side obstacle No top side obstacle Top side obstacle Top side obstacle Wall height unrestricted Wall height unrestricted The outdoor unit is designed for outdoo...

Page 7: ...2 To install the outdoor unit 1 Carry the unit by its slings and put it onto the installation structure 150 kg 4 2 Fix the unit to the installation structure 4 M12 3 Remove the slings and screws and d...

Page 8: ...on stays 2 and dispose of them 4 Piping installation 4 1 Connecting water piping 4 1 1 To connect the water piping NOTICE Do NOT use excessive force when connecting the field piping and make sure the...

Page 9: ...to air Types of glycol The types of glycol that can be used depend on whether the system contains a domestic hot water tank If Then The system contains a domestic hot water tank Only use propylene gly...

Page 10: ...ECTROCUTION WARNING Rotating fan Before powering ON or servicing the outdoor unit make sure that the discharge grille covers the fan as protection against a rotating fan See 6 2 To install the dischar...

Page 11: ...aker 30 mA field supply 2 Interconnection cable indoor outdoor Route the cable through the frame Connect the wires to the terminal block make sure the numbers match with the numbers on the indoor unit...

Page 12: ...ich is already routed through the frame Connect the wires to the terminal block Fix the cable with a cable tie Use the factory mounted cable Wires 3N GND Maximum running current Refer to name plate on...

Page 13: ...Route the cable through the frame Connect the wires to the terminal block and the earth screw Fix the cable with cable ties Wires 2 GND 0 75 mm Wiring must be double insulated Maximum power allowed fo...

Page 14: ...6 2 To install the discharge grille Install the lower part of the discharge grille 1 Insert the hooks 2 Insert the ball studs 1 2 3 Fix the 2 lower screws 3 2 Install the upper part of the discharge g...

Page 15: ...move the upper part of the discharge grille 4 2 Remove the lower part of the discharge grille 4 3 Rotate the lower part of the discharge grille 4 Align the ball stud and hook on the grille with their...

Page 16: ...illary tube j Distributor k Air heat exchanger l PCB cooling m Accumulator n Muffler E1HHEX Plate heat exchanger heater M1C Compressor M1F Fan motor S1PH High pressure switch 5 6 MPa S2PH High pressur...

Page 17: ...ircuit board ACS A5P Printed circuit board flash BS1 BS4 A1P Push button switch C1 C4 A1P A2P Capacitor DS1 A1P DIP switch E1H Drain tube heater field supply E1HHEX E3HHEX Plate heat exchanger heaters...

Page 18: ...S K2R A4P Magnetic relay E1H K3R A1P Magnetic relay Y3S K4R A1P Magnetic relay E1HC K2M K11M A2P Magnetic contactor L1R L4R Reactor M1C Compressor motor M1F Fan motor PS A2P Switching power supply Q1D...

Page 19: ......

Page 20: ...4P586100 1B 2019 09 Copyright 2019 Daikin 4P586100 1 B 0000000Y...

Reviews: