13/19
Breadcrumb
Setting name
Range, step
Default value
Field settings table
9.I
[3-0D]
R/W
0: Disabled (*10)
1: Enabled
9.I
[4-00]
R/W
0: Restricted
1: Allowed
2: Only DHW
9.I
[4-01]
R/W
0: None
1: Booster Heater
2: Backup Heater
9.I
[4-02]
R/W
14~35°C, step: 1°C
35°C
9.I
[4-03]
R/W
0: Restricted
1: Allowed
2: Overlap
3: Compressor off
4: Legionella only
9.I
[4-04]
R/W
0: Continuous pump operation
1: Non continuous pump operation
2: OFF
9.I
[4-05]
0
9.I
[4-06]
R/W
0: Manual
1: Automatic
2: Auto SH reduced/ DHW ON
3: Auto SH reduced/ DHW OFF
4: Auto SH normal/ DHW OFF
9.I
[4-07]
3
9.I
[4-08]
R/W
0: No
1: Continuous
2: Inputs
3: Current Sensor
9.I
[4-09]
R/W
0: Amp
1: kW
9.I
[4-0A]
R/W (*5,
*6, *7)
R/O (*4)
0: 1 (*4, *7)
1: 1/1+2 (*5, *6)
2: 1/2
3: 1/2 + 1/1+2 in emergency
9.I
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
9.I
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
9.I
[4-0E]
6
9.I
[5-00]
R/W
0: No (*10)
1: Yes (*9)
9.I
[5-01]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-02]
R/W
0: Disabled
1: Enabled
9.I
[5-03]
R/W
-15~35°C, step: 1°C
0°C
9.I
[5-04]
R/W
0~20°C, step: 1°C
10°C
9.I
[5-05]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-06]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-07]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-08]
R/W
0~50 A, step: 1 A
50 A
9.I
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
9.I
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
--
Equilibrium: Deactivate backup heater (or external backup heat
source in case of a bivalent system) above the equilibrium
temperature for space heating?
What is the equilibrium temperature for the building?
Space heating priority.
Space heating priority temperature.
Set point correction for domestic hot water temperature.
--
Which power limitation mode is required on the system?
Which power limitation type is required?
Backup heater configuration
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
Which electric heater has priority?
Below which outdoor temperature is heating allowed?
Operation permission of the booster heater.
Water pipe freeze prevention
--
Emergency
What is the BUH operation mode?
In case a bizone kit is installed, antiblockage of kit pump(s) and kit
mixing valve
(*1) *X*_(*2) *H*_(*3) *B*_(*4) *EKECBUA*3V_
(*5) *EKECBUA*6V_(*6) *EKECBUA*9W_(*7) BUH less_
(*8) 300L tank_(*9) E_(*10) E7
4P681797-1B - 2022.09