Application guidelines
Installer reference guide
36
EPGA11~16DAV3(7) + EA23DA6V(7)+9W
Daikin Altherma 3 H F
4P556075-1A – 2021.09
6.3.6 DHW pump for disinfection
Setup
c
a
b
d f
e g
h
i
a
Indoor unit
b
DHW tank
c
DHW pump (field supply)
d
Heater element (field supply)
e
Non‑return valve (field supply)
f
Shower (field supply)
g
Cold water
h
Domestic hot water OUT
i
Recirculation connection
▪
The DHW pump is field-supplied and its installation is the responsibility of the
installer. For the electrical wiring, see
"9.2.5 To connect the domestic hot water
83].
▪
If the applicable legislation requires a higher temperature than the maximum
tank setpoint during disinfection (see [2-03] in the field settings table), you can
connect a DHW pump and heater element as shown above.
▪
If applicable legislation requires disinfection of the water piping until the tapping
point, you can connect a DHW pump and heater element (if needed) as shown
above.
▪
To ensure a complete disinfection, you have to open the tapping point.
WARNING
When opening the tapping point, the water temperature can be up to 55°C.
Configuration
The indoor unit can control DHW pump operation. For more information, see
87].
6.4 Setting up the energy metering
▪
Via the user interface, you can read out the following energy data:
-
Produced heat
-
Consumed energy
▪
You can read out the energy data:
-
For space heating
-
For domestic hot water production
▪
You can read out the energy data:
-
Per month
-
Per year
INFORMATION
The calculated produced heat and consumed energy are an estimation, the accuracy
cannot be guaranteed.