9/10
Breadcrumb Field code
Setting name
Range, step
Default value
Date
Value
Installer setting at variance with
default value
Field settings table
9.I
[9-05]
R/W
15~37°C, step: 1°C
25°C
9.I
[9-06]
R/W
[2-0D]=2:
37~60, step: 1°C
55°C
[2-0D]
≠
2:
37~55, step: 1°C
55°C
9.I
[9-07]
R/W
5~18°C, step: 1°C
8°C (*3)
9.I
[9-08]
R/W
18~22°C, step: 1°C
22°C (*3)
9.I
[9-0C]
R/W
1~6°C, step: 0,5°C
1 °C
9.I
[9-0D]
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
9.I
[9-0E]
R/W
0~8, step:1
0: No limitation
1~4: 90~60% pump speed
5~8: 90~60% pump speed during
sampling
6
9.I
[C-00]
R/O
1: Heat pump priority
9.I
[C-01]
0
9.I
[C-02]
R/W
0: No
1: Bivalent
9.I
[C-03]
R/W
-25~25°C, step: 1°C
0°C
9.I
[C-04]
R/W
2~10°C, step 1°C
3°C
9.I
[C-05]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-06]
R/W
0: -
1: 1 contact
2: 2 contacts
9.I
[C-07]
R/W
0: LWT control
1: Ext RT control
2: RT control
9.I
[C-08]
R/W
0: No
1: Outdoor sensor
2: Room sensor
9.I
[C-09]
R/W
0: Normally open
1: Normally closed
9.I
[C-0A]
0
9.I
[D-00]
R/W
0: None
1: BSH only
2: BUH only
3: All heaters
9.I
[D-01]
R/W
0: No
1: Active open
2: Active closed
3: Safety thermostat
9.I
[D-02]
R/W
0: No
1: Secondary rtrn
2: Disinf. Shunt
9.I
[D-03]
R/W
0: No
1: increase 2°C, span 4°C
2: increase 4°C, span 4°C
3: increase 2°C, span 8°C
4: increase 4°C, span 8°C
9.I
[D-04]
R/W
0: No
1: Pwr consmp ctrl
9.I
[D-05]
R/W
0: Forced off
1: As normal
9.I
[D-07]
R/O
0: No
9.I
[D-08]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-09]
R/W
0: No
1: 0,1 pulse/kWh
2: 1 pulse/kWh
3: 10 pulse/kWh
4: 100 pulse/kWh
5: 1000 pulse/kWh
9.I
[D-0A]
0
9.I
[D-0B]
2
9.I
[E-00]
R/O
0~5
0: LT split
9.I
[E-01]
R/O
1
9.I
[E-02]
R/W (*3)
R/O
0: Reversible (*3)
1: Heating only
9.I
[E-03]
R/O
3: 6V (*1)
4: 9W (*2)
9.I
[E-04]
R/O
0: No
1: Yes
9.I
[E-05]
R/O
0: No
1: Yes
9.I
[E-06]
R/O
0: No
1: Yes
9.I
[E-07]
R/O
1: Integrated
9.I
[E-08]
R/O
0: disabled
1: Enabled
9.I
[E-09]
1
9.I
[E-0A]
0
Room temperature hysteresis.
Pump speed limitation add zone
Pump speed limitation main zone
Domestic heating water priority.
What is the mimimum desired LWT for add. zone in heating?
--
Is an external backup heat source connected?
Bivalent activation temperature.
Bivalent hysteresis temperature.
What is the thermo request contact type for the main zone?
Which heaters are permitted if prefer. kWh rate PS is cut?
What is the maximum desired LWT for add. zone in heating?
What is the maximum desired LWT for add. zone in cooling?
Contact type of preferential kWh rate PS installation?
What is the thermo request contact type for the add. zone?
What is the unit control method in space operation?
Which type of external sensor is installed?
What is the required alarm output contact type?
--
Leaving water temperature compensation around 0°C.
--
Which type of DHW pump is installed?
What is the mimimum desired LWT for add. zone in cooling?
Which type of compressor is installed?
Is a demand PCB connected?
Is the pump allowed to run if prefer. kWh rate PS is cut?
Is a solar kit connected?
Is an external kWh meter used for power measurement?
Is an external kWh meter used for power measurement?
What is the indoor unit software type?
What is the number of backup heater steps?
Is the power saving function available on the outdoor unit?
--
Which type of unit is installed?
Can the system prepare domestic hot water?
Is a DHW tank installed in the system?
What kind of DHW tank is installed?
Power saving function for outdoor unit.
--
--
(*1) *6V_(*2) *9W_
(*3) + EKHVCONV2_
(*4) EAVZ16S18*_(*5) EAVZ16S23*
(#) Setting is not applicable for this unit.