15 Disposal
NOTICE
Do NOT try to dismantle the system yourself: dismantling of the system, treatment of
the refrigerant, oil and other parts MUST comply with applicable legislation. Units
MUST be treated at a specialised treatment facility for reuse, recycling and recovery.
In this chapter
To recover refrigerant ............................................................................................................................................................ 186
15.1.1
15.1 To recover refrigerant
When disposing of the outdoor unit, you need to recover its refrigerant.
To ensure that no refrigerant remains trapped in the unit:
▪
Make sure the stop valves are open (
a
,
b
).
▪
Make sure the valves (
Y1E
,
Y3E
,
Y2S
,
Y3S
) are open.
▪
Use all 3 service ports (
a
,
b
,
c
) to recover refrigerant.
Components
a
b
c
Y1E
Y3E
Y2S + Y3S
a
Liquid stop valve with service port
b
Gas stop valve with service port
c
Service port 5/16" flare
Y1E
Electronic expansion valve (main)
Y3E
Electronic expansion valve (injection)
Y2S
Solenoid valve (injection bypass)
Y3S
Solenoid valve (hot gas bypass)