Daikin Alterma EBHQ011AA6V3 Operation Manual Download Page 8

Operation manual

7

E(D/B)(H/L)Q011~0W1

Unit for air to water heat pump system and options

4PW51122-1

What can the schedule timer NOT do?

The schedule timer can not change the operation mode from space
cooling to space heating or vice versa.

How to interpret the programmed actions

To be able to understand the behaviour of your installation when the
schedule timer is enabled, it is important to keep in mind that the
"last" programmed command overruled the "preceding" programmed
command and will remain active until the "next" programmed
command occurs.

Example: imagine the actual time is 17:30 and actions are
programmed at 13:00, 16:00 and 19:00. The "last" programmed
command (16:00) overruled the "previous" programmed command
(13:00) and will remain active until the "next" programmed command
(19:00) occurs.

So in order to know the actual setting, one should consult the last
programmed command. It is clear that the "last" programmed
command may date from the day before. Refer to 

"Consulting

programmed actions" on page 9

.

Programming and consulting the schedule timer

Getting started

Programming the schedule timer is flexible (you can add, remove or
alter programmed actions whenever required) and straightforward
(programming steps are limited to a minimum). However, before
programming the schedule timer, remind:

Familiarise yourself with the icons and the buttons. You will need
them when programming. Refer to 

"Name and function of

buttons and icons" on page 3

.

Fill out the form at the very end of this manual. This form can
help you define the required actions for each day. Keep in mind
that:
-

In the space cooling/heating program, 5 actions can be 
programmed per weekday. The same actions are repeated 
on a weekly basis.

-

In the domestic water heating, booster heater and quiet 
mode program, 5 actions can be programmed per mode. The 
same actions are repeated on a daily basis.

Take your time to enter all data accurately.

Try to program the actions in a chronological way: start with
action 1 for the first action and end with the highest number for
the last action. This is not a requirement but will simplify the
interpretation of the program later.

If 2 or more actions are programmed for the same day and at the
same time, only the action with the highest action number will be
executed.

You can always alter, add or remove the programmed actions
later.

When programming heating actions (time and set point), cooling
actions are added automatically at the same time but with the
predefined default cooling set point. Conversely, when
programming cooling actions (time and setpoint), heating
actions are added automatically at the same time but with the
default heating set point.

The set points of these automatically added actions can be
adjusted by programming the corresponding mode. This means
that after programming heating, you should also program the
corresponding cooling set points and vice versa.

NOTE

During schedule timer operation, someone may have
altered the actual settings manually (in other words,
the "last" command was overruled manually). The icon

p

, indicating the schedule timer operation, may still be

displayed, giving the impression that the "last"
command settings are still active. The "next"
programmed command will overrule the altered
settings and return to the original program.

Due to the fact that the schedule timer cannot switch
between operation modes (cooling or heating) and the fact
that each programmed action implies a cooling setpoint
and a heating setpoint, the following situations may occur:

when the schedule timer is active in heating mode,
and the mode is changed manually to cooling (by
means of the 

=

  button), the operation mode will

from then on remain cooling and program actions will
follow the corresponding cooling setpoints. Returning
to heating mode needs to be carried out manually (by
means of the 

=

 button).

when the schedule timer is active in cooling mode,
and the mode is changed manually to heating (by
means of the 

=

  button), the operation mode will

from then on remain heating and program actions will
follow the corresponding heating setpoints. Returning
to cooling mode needs to be carried out manually (by
means of the 

=

 button).

The above proves the importance of programming both
cooling and heating setpoints for each action. If you do not
program these setpoints, the predefined default values will
be used.

Summary of Contents for Alterma EBHQ011AA6V3

Page 1: ...AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Unit for air to water heat pump system and options ...

Page 2: ...nits and heating only units The AD outdoor monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside ...

Page 3: ...th low electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that off...

Page 4: ... is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is...

Page 5: ...oller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer S...

Page 6: ... C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The oper...

Page 7: ...ther dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heati...

Page 8: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the p...

Page 9: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Page 10: ...ant to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other progr...

Page 11: ...g or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the se...

Page 12: ...der outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection function Applies only to install...

Page 13: ...ture equals or drops below the specified equilibrium temperature When the function is disabled operation of the backup heater is possible at all outdoor temperatures Enabling this function reduces the working time of the backup heater 5 00 Equilibrium temperature status specifies whether the equilibrium temperature function is enabled 1 or disabled 0 5 01 Equilibrium temperature outdoor temperatur...

Page 14: ...tra degrees are specified by the domestic hot water step length field setting Correct setting prevents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water st...

Page 15: ... water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given to the unit operating quie...

Page 16: ...that contact will open and the unit will go in forced off mode 1 When parameter D 01 2 at the moment that the benefit kWh rate signal is sent by the electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identificatio...

Page 17: ...heating off temperature 25 14 25 1 C 03 Booster heater operation 1 0 1 04 Freeze up protection function 0 active Read only 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 35 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic...

Page 18: ...off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting...

Page 19: ...o late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted h...

Page 20: ...NOTES NOTES ...

Page 21: ......

Page 22: ...4PW51122 1 Copyright Daikin ...

Reviews: