[3] Auto restart

When power returns after a power supply failure, the auto restart
function reapplies the user interface settings at the time of the power
supply failure.

Note that with the function disabled the schedule timer will not be
activated when power returns to the unit after a power supply failure.
Press the 

pr

 button to enable the schedule timer again.

[3-00] Status: defines whether the auto restart function is
turned ON (0) or OFF (1).

[4] Backup heater operation and space heating off temperature

Backup heater operation
The operation of the backup heater can altogether be enabled or
disabled, or it can be disabled depending on operation of the booster
heater.

[4-00] Status: defines whether backup heater operation is
enabled (1) or disabled (0).

[4-01] Priority: defines whether backup heater and booster
heater can operate simultaneously (0), or if the booster
heater operation has priority over the backup heater
operation (1), or if the backup heater operation has priority
over the booster heater operation (2).

Space heating off temperature

[4-02] Space heating off temperature: outdoor temperature
above which space heating is turned off, to avoid
overheating.

[4-03] Booster heater operation: defines whether the optional
booster heater operation is enabled (1) or limited (0).

[4-04] Freeze-up protection function: avoids the freeze-up of
the water piping between home and unit. In case of low
ambient temperatures it will activate the pump and in case of
low water temperatures it will additionally activate the backup
heater.
Default freeze-up protection function takes into account
freezing of water piping which is unsuficiently insulated.
Basically it means that the pump is activated whenever
ambient temperatures become close to freezing,
independantly of the working temperature.

However, if the installer can guarantee that the complete
installation is protected from freezing sufficiently with a
minimum thickness of 13 

mm and x

0,040 W/mK

insulation material, then a lower level of freeze-up
protection, that will reduce the pump running time, can be
set.

If the water system contains glycol, then a lower level of
freeze-up protection, that will reduce the pump running
time, can be set.

For more information contact your local dealer.

[5] 

 

Equilibrium temperature and space heating priority

temperature

Equilibrium temperature  — The 'equilibrium temperature' field
settings apply to operation of the backup heater.
When the equilibrium temperature function is enabled, operation of
the backup heater is restricted to low outdoor temperatures, i.e. when
the outdoor temperature equals or drops below the specified
equilibrium temperature. When the function is disabled, operation of
the backup heater is possible at all outdoor temperatures. Enabling
this function reduces the working time of the backup heater.

[5-00] Equilibrium temperature status: specifies whether the
equilibrium temperature function is enabled 

(1) or

disabled (0).

[5-01] Equilibrium temperature: outdoor temperature below
which operation of the backup heater is allowed.

Space heating priority temperature — Applies only to installations
with a domestic hot water tank. — The 'space heating priority
temperature' field settings apply to operation of the 3-way valve and
the booster heater in the domestic hot water tank.
When the space heating priority function is enabled, it is assured that
the full capacity of the heat pump is used for space heating only
when the outdoor temperature equals or drops below the specified
space heating priority temperature, i.e. low outdoor temperature. In
this case the domestic water will only be heated by the booster
heater.

[5-02] Space heating priority status: specifies whether space
heating priority is enabled (1) or disabled (0).

[5-03] Space heating priority temperature: outdoor
temperature below which the domestic water will be heated
by the booster heater only, i.e. low outdoor temperature.

NOTE

It is therefore recommended to leave the auto restart
function enabled.

NOTE

If the benefit kWh rate power supply is of the type that
power supply is interrupted, then always allow the auto
restart function.

NOTE

Even in case the backup heater operation
status field setting [4-00] is set to disabled (0),
the backup heater can operate during start-up
and defrost operation.

NOTE

When the priority field setting is set to ON (1),
space heating performance of the system
might be decreased at low outdoor
temperatures, since in case of domestic water
heating demand the backup heater will not be
available for space heating (space heating will
still be provided by the heat pump).

When the priority field setting is set to ON (2),
domestic water heating performance of the
system might be decreased at low outdoor
temperatures, since in case of space heating
demand the booster heater will not be
available for domestic water heating. However
domestic water heating by heatpump will still
be available.

When the priority field setting is set to OFF (0),
make sure that electrical power consumption
does not exceed supply limits.

NOTE

If the booster heater operation is limited than the
booster heater operation is only allowed during
the disinfection function 

[2] (refer to 

"[2]

Disinfection function" on page 

11

.) or when

powerful domestic hot water temperature is
initiated.

NOTE

If the booster heater operation is limited ([4-03]=0)
and the ambient outdoor temperature 

T

is lower

than the field setting to which parameter [5-03] is
set, then the domestic water will not be heated.

Summary of Contents for Alterma EBHQ011AA6V3

Page 1: ...AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Unit for air to water heat pump system and options ...

Page 2: ...nits and heating only units The AD outdoor monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside ...

Page 3: ...th low electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that off...

Page 4: ... is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is...

Page 5: ...oller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer S...

Page 6: ... C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The oper...

Page 7: ...ther dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heati...

Page 8: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the p...

Page 9: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Page 10: ...ant to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other progr...

Page 11: ...g or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the se...

Page 12: ...der outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection function Applies only to install...

Page 13: ...ture equals or drops below the specified equilibrium temperature When the function is disabled operation of the backup heater is possible at all outdoor temperatures Enabling this function reduces the working time of the backup heater 5 00 Equilibrium temperature status specifies whether the equilibrium temperature function is enabled 1 or disabled 0 5 01 Equilibrium temperature outdoor temperatur...

Page 14: ...tra degrees are specified by the domestic hot water step length field setting Correct setting prevents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water st...

Page 15: ... water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given to the unit operating quie...

Page 16: ...that contact will open and the unit will go in forced off mode 1 When parameter D 01 2 at the moment that the benefit kWh rate signal is sent by the electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identificatio...

Page 17: ...heating off temperature 25 14 25 1 C 03 Booster heater operation 1 0 1 04 Freeze up protection function 0 active Read only 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 35 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic...

Page 18: ...off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting...

Page 19: ...o late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted h...

Page 20: ...NOTES NOTES ...

Page 21: ......

Page 22: ...4PW51122 1 Copyright Daikin ...

Reviews: