Daikin Alterma EBHQ011AA6V3 Operation Manual Download Page 3

 

E(D/B)(H/L)Q011~0W1

 

Unit for air to water heat pump system and options

 

4PW51122-1

 

Operation manual

 

2

 

O

 

PERATING

 

 

 

THE

 

 

 

UNIT

 

I

 

NTRODUCTION

 

The 

 

AD

 

  heat pump system is designed to provide

you a comfortable indoor climate for many years at low energy
consumption.

To  get the most comfort with the lowest energy consumption out of
your system, it is very important to observe the items listed below.

Defining possible schedule timer actions for each day and filling out
the form at the very end of this manual can help you minimize the
energy consumption. Ask your installer for support if required.

 

 

Make sure the 

 

AD

 

 heat pump system works at

the lowest possible hot water temperature required to heat your
house.

To optimize this, make sure the weather dependent set point is
used and configured to match the installation environment.
Refer to 

"Field settings" on page 10

.

 

 

Make sure the equilibrium temperature field setting is configured
correctly.

Refer to 

"Field settings" on page 10

.

This function applies to operation of the backup heater. Setting
the equilibrium temperature correctly will avoid the backup
heater to operate when the heat pump has sufficient capacity to
heat up your house.

 

 

It is advised to install a room thermostat connected to the unit.
This will prevent excessive space heating and will stop the unit
and the circulation pump when the room temperature is above
the thermostat set point.

 

 

Next recommendations only apply to installations with an
optional domestic hot water tank.

 

 

Make sure the domestic hot water is only heated up to the
domestic hot water temperature you require.
Start with a low domestic hot water temperature set point
(e.g. 45°C), and only increase if you feel that the domestic
hot water supply temperature is not sufficient.

 

 

Make sure both the domestic water heating and booster
heating only start 1 to 2 hours before you expect domestic
hot water usage.
In case you only need a lot of domestic hot water in the
evening or in the morning, only allow domestic water heating
during early morning and early evening. Also keep hours with
low electricity cost tariffs in mind.
To  do this, program both the domestic water heating and
booster heating schedule timer. Refer to Programming in
chapter 

"Programming and consulting the schedule timer" on

page 7

.

 

O

 

PERATING

 

 

 

THE

 

 

 

DIGITAL

 

 

 

CONTROLLER

 

Operating the unit comes down to operating the digital controller.

 

Features and functions

 

The digital controller is a state of the art controller that offers full
control over your installation. It can control a cooling/heating and a
heating only installation.

Both installations are available in multiple versions which vary in
capacity, electrical supply and installed equipment (with an optional
domestic hot water tank with a booster heater).

 

Basic controller functions

 

The basic controller functions are:

 

 

Turning the unit ON/OFF.

 

 

Operation mode change-over:
-

space heating (refer to 

page 4

),

-

space cooling (refer to 

page 5

) (*),

-

domestic water heating (refer to 

page 5

) (*).

 

 

Selection of features:
-

quiet mode (refer to 

page 5

),

-

weather dependent control (refer to 

page 6

).

 

 

Temperature set point adjustment (refer to 

page 5

).

The digital controller supports a power cut off of maximum 2 hours.
When autorestart is enabled (see 

"Field settings" on page 10

) this

allows a power supply shut down of 2 hours without user intervention
(e.g. benefit kWh rate power supply).

 

Clock function

 

The clock functions are:

 

 

24 hour real time clock.

 

 

Day of the week indicator.

 

Schedule timer function

 

The schedule timer function allows the user to schedule the
operation of the installation according to a daily or a weekly program.

 

Never let the digital controller get wet. This may cause an
electric shock or fire.

Never press the buttons of the digital controller with a hard,
pointed object. This may damage the digital controller.

Never inspect or service the digital controller yourself, ask
a qualified service person to do this.

 

NOTE

 

 

Descriptions in this manual that apply to a specific
installation or that depend on the installed
equipment, are marked with an asterisk (*).

 

 

Some functions described in this manual may not
be available or should not be available. Ask your
installer or your local dealer for more information
on permission levels.

 

NOTE

 

(*) The functions 'space cooling' and 'domestic water
heating' can only be selected when the corresponding
equipment is installed.

Summary of Contents for Alterma EBHQ011AA6V3

Page 1: ...AA6W1 EDLQ011AA6V3 EDLQ014AA6V3 EDLQ016AA6V3 EDLQ011AA6W1 EDLQ014AA6W1 EDLQ016AA6W1 EBHQ011AA6V3 EBHQ014AA6V3 EBHQ016AA6V3 EBHQ011AA6W1 EBHQ014AA6W1 EBHQ016AA6W1 EBLQ011AA6V3 EBLQ014AA6V3 EBLQ016AA6V3 EBLQ011AA6W1 EBLQ014AA6W1 EBLQ016AA6W1 Unit for air to water heat pump system and options ...

Page 2: ...nits and heating only units The AD outdoor monoblock unit range consists of two main versions a heating cooling EB version and a heating only ED version Both versions are delivered with an integrated backup heater for additional heating capacity during cold outdoor temperatures The backup heater also serves as a backup in case of malfunctioning of the unit and for freeze protection of the outside ...

Page 3: ...th low electricity cost tariffs in mind To do this program both the domestic water heating and booster heating schedule timer Refer to Programming in chapter Programming and consulting the schedule timer on page 7 OPERATING THE DIGITAL CONTROLLER Operating the unit comes down to operating the digital controller Features and functions The digital controller is a state of the art controller that off...

Page 4: ... is required on the installation Consult your dealer 11 SET TEMPERATURE DISPLAY 9 The display shows the current set temperature of the installation 12 SETTING Not used For installation purposes only 13 NOT AVAILABLE n This icon is displayed whenever a non installed option is addressed or a function is not available 14 DEFROST STARTUP MODE ICON d This icon indicates that the defrost startup mode is...

Page 5: ...oller is set in permission level 2 or 3 refer to Field settings on page 10 the quiet mode button will not be operable Setting up the controller After initial installation the user can set the clock and day of the week The controller is equipped with a schedule timer that enables the user to schedule operations Setting the clock and day of the week is required to be able to use the schedule timer S...

Page 6: ... C during commissioning of the installation When set lower than 25 C only the backup heater will operate In order to avoid overheating space heating is not operable when the outdoor ambient temperature rises above a certain temperature as set through field setting 4 02 refer to Field settings on page 10 Temperature range for cooling 5 C to 22 C 3 Switch on the unit by pushing the y button The oper...

Page 7: ...ther dependent or manually set Five actions per weekday can be programmed totalling 35 actions 2 Quiet mode refer to Programming quiet mode booster heating or domestic water heating on page 9 Switch the mode on or off at a scheduled time Five actions can be programmed per mode These actions are repeated daily 3 Booster heating refer to Programming quiet mode booster heating or domestic water heati...

Page 8: ...ot a requirement but will simplify the interpretation of the program later If 2 or more actions are programmed for the same day and at the same time only the action with the highest action number will be executed You can always alter add or remove the programmed actions later When programming heating actions time and set point cooling actions are added automatically at the same time but with the p...

Page 9: ...n to select x to switch cooling or heating and the controller off 9 set the temperature by means of the bi and bj buttons a to select automatic temperature calculation only in heating mode 10 Use the pi and pj buttons to set the correct action time 11 Repeat steps 8 to 10 to program the other actions of the selected day When all actions have been programmed make sure that the display shows the hig...

Page 10: ...ant to consult 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to consult by means of the pi and pj buttons The selected day is blinking 5 Press the button to confirm the selected day The first programmed action of the selected day appears 6 Use the pi and pj buttons to consult the other progr...

Page 11: ...g or heating mode 1 Use the button to select the operation mode cooling or heating you want to delete 2 Press the button The actual mode is blinking 3 Press the button to confirm the selected mode The actual day is blinking 4 Select the day you would like to delete by means of the pi and pj buttons The selected day is blinking 5 Press the and ba button simultaneously for 5 seconds to delete the se...

Page 12: ...der outdoor temperatures i e Lo_A warmer water is required 1 03 Set point at high ambient temperature Hi_Ti the target outgoing water temperature when the outdoor temperature equals or rises above the high ambient temperature Hi_A Note that the Hi_Ti value should be lower than Lo_Ti as for warmer outdoor temperatures i e Hi_A less warm water suffices 2 Disinfection function Applies only to install...

Page 13: ...ture equals or drops below the specified equilibrium temperature When the function is disabled operation of the backup heater is possible at all outdoor temperatures Enabling this function reduces the working time of the backup heater 5 00 Equilibrium temperature status specifies whether the equilibrium temperature function is enabled 1 or disabled 0 5 01 Equilibrium temperature outdoor temperatur...

Page 14: ...tra degrees are specified by the domestic hot water step length field setting Correct setting prevents the booster heater from repeatedly turning on and off i e chattering to maintain the domestic hot water set point temperature Note the booster heater will turn back on when the domestic hot water temperature drops 2 C fixed value below the booster heater OFF temperature 7 00 Domestic hot water st...

Page 15: ... water temperature for cooling operation 9 04 Overshoot setting defines how much the water temperature may rise above the setpoint before the compressor stops This function is only applicable in heating mode A Quiet mode This field setting allows to select the desired quiet mode Two quiet modes are available quiet mode A and quiet mode B In quiet mode A priority is given to the unit operating quie...

Page 16: ...that contact will open and the unit will go in forced off mode 1 When parameter D 01 2 at the moment that the benefit kWh rate signal is sent by the electricity company that contact will close and the unit will go in forced off mode 2 E Unit information readout E 00 Readout of the software version example 23 E 01 Readout of the EEPROM version example 23 E 02 Readout of the unit model identificatio...

Page 17: ...heating off temperature 25 14 25 1 C 03 Booster heater operation 1 0 1 04 Freeze up protection function 0 active Read only 5 Equilibrium temperature and space heating priority temperature 00 Equilibrium temperature status 1 ON 0 1 01 Equilibrium temperature 0 15 35 1 C 02 Space heating priority status 0 OFF 0 1 03 Space heating priority temperatures 0 15 20 1 C 04 Set point correction for domestic...

Page 18: ...off heaters 0 0 1 2 3 01 Unit connection to benefit kWh rate power supply 0 OFF 0 1 2 02 Not applicable Do not change the default value 0 E Unit information readout 00 Software version Read only 01 EEPROM version Read only 02 Unit model identification Read only 03 Liquid refrigerant temperature Read only C 04 Inlet water temperature Read only C First code Second code Setting name Installer setting...

Page 19: ...o late or too early Check if the clock and the day of the week are set correctly correct if necessary DISPOSAL REQUIREMENTS Dismantling of the unit treatment of the refrigerant of oil and of other parts must be done in accordance with relevant local and national legislation Your product is marked with this symbol This means that electrical and electronic products shall not be mixed with unsorted h...

Page 20: ...NOTES NOTES ...

Page 21: ......

Page 22: ...4PW51122 1 Copyright Daikin ...

Reviews: