14.1
Data for designing the flue gas pipe
Device
Burner
load in kW
Rated output in kW
Flue gas mass flow in
g/s
Heating oil/EL
Flue gas temperature in °C
Available pum-
ping pressure in
Pa
50/30 °C
80/60 °C
50/30 °C
80/60 °C
A2 F 18H
8.5
8.3
3.90
34
52
100
18.2
17.7
8.36
46
68
200
A2 F 24H
10.9
10.6
5.01
34
52
100
24.7
24.1
11.35
46
70
200
A2 F 32H
12.8
12.5
5.88
34
52
100
32.2
31.4
14.79
46
72
200
Tab. 14-1
Triple values for chimney design (flue gas flow dependent on heat output, see
)
14.2
Emissions measurement
The control measurement can be made by an easily selectable auto-
matic function (see also enclosed "Control system instructions").
1
Press the Exit button for at least 5 secs.
è
The
"
Special Level
"
menu is displayed.
2
Use the rotary button to select the "Emissions measurement"
program.
3
Confirm the selection with a brief push of the rotary button.
è
The following load types are available for selection:
–
Off: The emission measurement is switched off, any heat ge-
nerators switched on by the A2 F control functions continue
to be regulated normally.
–
Base load: The heat generator is switched on and operated
at the minimum output of the heat generator, irrespective of
the set operating mode.
–
Full load: The heat generator is switched on and operated at
the maximum output of the heat generator, irrespective of
the set operating mode.
4
Use the rotary button to select the "Full Load" load type,
but do
not confirm it
.
è
Display: "Full Load"
è
The burner is turned on for 30 min. and is regulated at maxi-
mum load.
5
Use the rotary button to select the "Base Load" load type,
but
do not confirm it
.
è
Display: "Base Load"
è
The modulating oil burner runs at minimum output for
30 mins.
6
Cancellation and jump back by:
–
Pushing the Exit button or rotary switch again
–
Selection of a different menu using the rotary switch and
confirmation.
Special Level
Emissions measurement
Manual Operation
Emissions measurement
Off
Emissions measurement
Base Load
Emissions measurement
Full Load
Emissions measurement
Full Load
T-HS
T-HS
T-HS
T-HS
Bild 14-1