Specifications

Electrical rating:

  •  24 VAC (18-30 VAC) 

 

•  1 amp maximum per terminal 

 

•  3 amp maximum total load

Temperature control range: 

55°F to 90°F (13°C to 32°C)   

Accuracy:

 ± 1°F (± 0.5°C)

System configurations:

 2-stage heat, 2-stage cool

Timing:

  Anti-short Cycle: 4 minutes (bypass anti-short cycle delay by returning to OFF mode for 5 seconds)

 

Backlight Operation: 10 seconds

Terminations:

 A, L, S1, S2, R, C, W1, Y1, W2, Y2, G, O 

Package Contents/Tools Required

Package includes:

 

910121746

 thermostat on base, thermostat cover, wiring labels, screws and wall anchors, 

Installation, Operation and Application Guide

Tools required for installation:

 Drill with 3/16” bit, hammer, screwdriver

Important Safety Information

WARNING!

Always turn off power at the main power supply before installing, cleaning, or removing 
thermostat.

•  This thermostat is for 24 VAC applications only; do not use on voltages over 30 VAC
•  All wiring must conform to local and national electrical and building codes
•  Do not use air conditioning when the outdoor temperature is below 50 degrees; this can damage your A/C system 

and cause personal injuries

•  Use this thermostat only as described in this manual

Icon Descriptions

Cooling operation icon

Fan operation icon

Heating operation icon

Room temperature 
offset activated

Parts Diagram

Configuration 

switch

Reset switch

Right (fan) button

Down button

Up button

S1 S2 R

C

G

Y1 W2 Y2

RESET

CONFIG

To Remove Existing Thermostat

ELECTRICAL SHOCK HAZARD

 – Turn off power at the main service panel by removing the fuse 

or switching the appropriate circuit breaker to the OFF position before removing the existing 
thermostat.

1.  Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit 

breaker off.

2.  Remove cover of old thermostat. This should expose the wires.
3.  Label the existing wires with the enclosed wire labels before removing wires.
4.  After labeling wires, remove wires from wire terminals.
5.  Remove existing thermostat base from wall.
6.  Refer to the following section for instructions on how to install this thermostat.

To Install Thermostat

ELECTRICAL SHOCK HAZARD

 – Turn off power at the main service panel by removing the fuse 

or switching the appropriate circuit breaker to the OFF position before removing the existing 
thermostat.
IMPORTANT:

 

Thermostat installation must conform to local and national building and electrical codes and 
ordinances.

 

 

Note:

 

Mount the thermostat about five feet above the floor. Do not mount the thermostat on an outside wall, in 
direct sunlight, behind a door, or in an area affected by a vent or duct.

1. Turn off power to the heating and cooling system by removing the fuse or switching the appropriate circuit breaker 

off.

2. To remove cover, pull gently at the seam at the top.
3. Put thermostat base against the wall where you plan to mount it (Be sure wires will feed through the wire opening 

in the base of the thermostat).

4. Mark the placement of the mounting holes.
5. Set thermostat base and cover away from working area.
6. Using a 3/16” drill bit, drill holes in the places you have marked for mounting.
7. Use a hammer to tap supplied anchors in mounting holes.

Terminals S1 and S2 can be used for an indoor remote sensor. 
The indoor remote sensor is used to read the indoor temperature 
in a different location. This is beneficial when the thermostat is not 
mounted in the ideal location. The remote sensor P/N is 910116773.
1.  Remove cover from remote sensor housing.
2.  Select an appropriate location for mounting the remote sensor.
3.  Mount remote sensor unit using hardware provided.
4.  Install two strand shielded wire between remote sensor and 

thermostat. Shielded wire is recommended.  

Do not

 run remote sensor wire in conduit with other wires.

  • 

Wire 1

 should run between the S1 terminal on the thermostat 

and the S1 terminal on the remote sensor

  • 

Wire 2

 should run between the S2 terminal on the thermostat 

and the S2 terminal on the remote sensor

  •  Connect the shielding of the wire to the S2 terminal on the thermostat
5.  Configure the thermostat to operate with the remote indoor sensor (see Configuration Mode setting 9).

Remote Sensor Installation (Optional)

 

Note:

  Remote or outdoor sensor reading can be 

displayed by simultaneously pressing the 

Down

 and 

SYS

 buttons.

Remote Sensor:

 

(Contact Daikin for optional remote sensor.)

8. Align thermostat base with mounting holes and feed the control wires through slit in thermal intrusion barrier and 

into wire opening.

9. Use supplied screws to mount thermostat base to wall.
10. Insert stripped, labeled wires in matching wire terminals. 

 

CAUTION!

Be sure exposed portion of wires does not touch other wires.

11.  Gently tug wire to be sure of proper connection. Double check that each wire is connected to the proper 

terminal. 

12. Turn on power to the system at the main service panel.
13. Configure thermostat to match the type of system you have.
14. Replace cover on thermostat by snapping it in place.
15. Test thermostat operation as described in “Testing the Thermostat”.

1

ST

 Cool

2

ND

 Cool

1

ST

 Heat

2

ND

 Heat

Heat/Cool

Y1

YI, Y2

W1

W1, W2

The 

910121746

 thermostat is configurable for all systems. The configuration directly affects the outputs.

Use the output chart to correctly configure and wire the thermostat to your system.

910121746 Output Chart

Configuration Mode

OFF

1.  Verify the 

910121746

 is in the 

OFF

 mode.

 

Press the 

SYS

 (left) button until off mode displays.

2.  Remove the cover of the thermostat by gently pulling near one of the corners at 

the top of the thermostat.

To exit configuration mode, press the 

CONFIG

 switch for 1 second.

Press the 

up

 or 

down

 button to change settings within each screen.

Down button

Up button

Press the 

right

 button to advance to the next screen.

 

Note:

 

Pressing the 

left

 button will return you to the previous screen.

Left 

button

Right 

button

The configuration mode is used to set the 

910121746

 to match your heating/cooling system. To configure the 

910121746

, perform the following steps:

3.  Press the 

CONFIG

 button for 1 second while the 

910121746

 is in 

OFF 

mode.

CONFIG

S1 S2 R

C

W

O/B

G

Y1 W2

W3

Y2

RESET

CONFIG

FP

Wiring Diagrams

L

S1

S2

R

C

W1

Y1

W2

Y2

G

A

O

O

G

Y1

Y2

W1

W2

A

R

C

4

3

2

1

5

O

G

Y1

Y2

W1

W2

A

R

C

ICM 

Thermostat 

Terminal

TB2

TB1

ICM 

Thermostat 

Terminal

WSHP Main Control Board 

Terminals TB1 and TB2

Terminal Designator Descriptions

 R –  24 VAC hot
 C –  24 VAC common

 W1 –  1st stage heat
 Y1 –  1st stage cool

 W2 –  2nd stage heat
 Y2 –  2nd stage cool 

  G  –  Fan
  A  –  Alarm input

  L  –  Status input
  O  –  Override/reset

Daikin P/N (910121746)

• Configurable
• 2-Stage Heat/2-Stage Cool Systems
• Large Display With Backlight
• Selectable Fahrenheit or Celsius
• Status Indicator Light
• Relay Outputs  

(minimum voltage drop in thermostat)

• Remote Sensor Compatible

Installation, Operation & Application Guide

Version B: 10-15-13

2 Heat/2 Cool, Auto Changeover, Hardwired

Non-Programmable Electronic Thermostat