background image

2

English

 

• 

Make sure that a separate power supply circuit is provided 

for this unit and that all electrical work is carried out by 

qualified personnel according to local, state, and national 

regulations. An insufficient power supply capacity or 

improper electrical construction may lead to electric shock 

or fire.

•  Make sure that all wiring is secured, that specified wires 

are used, and that no external forces act on the terminal 

connections or wires. Improper connections or installation 

may result in fire.

• 

When wiring, position the wires so that the electrical 

wiring box cover can be securely fastened. Improper 

positioning of the electrical wiring box cover may result in 

electric shock, fire, or the terminals overheating.

• 

Before touching electrical parts, turn off the unit.

• 

The circuit must be protected with safety devices in 

accordance with local and national codes, i.e. a circuit 

breaker.

• 

Securely fasten the outdoor unit terminal cover (panel). If the 

terminal cover/panel is not installed properly, dust or water 

may enter the outdoor unit causing fire or electric shock.

• 

When installing or relocating the system, keep the refrigerant 

circuit free from substances other than the specified 

refrigerant (R410A) such as air. Any presence of air or other 

foreign substance in the refrigerant circuit can cause an 

abnormal pressure rise or rupture, resulting in injury.

• 

Do not change the setting of the protection devices. If the 

pressure switch, thermal switch, or other protection device 

is shorted and operated forcibly, or parts other than those 

specified by Daikin are used, fire or explosion may occur.

CAUTION 

•  Do not touch the switch with wet fingers. Touching a switch 

with wet fingers can cause electric shock.

• 

Do not allow children to play on or around the unit to 

prevent injury.

•  The heat exchanger fins are sharp enough to cut. To avoid 

injury wear gloves or cover the fins while working around 

them.

• 

Do not touch the refrigerant pipes during and immediately 

after operation as the refrigerant pipes may be hot or 

cold, depending on the condition of the refrigerant flowing 

through the refrigerant piping, compressor, and other 

refrigerant cycle parts. Your hands may suffer burns or 

frostbite if you touch the refrigerant pipes. To avoid injury, 

give the pipes time to return to normal temperature or, if 

you must touch them, be sure to wear proper gloves.

• 

Install drain piping to ensure proper drainage. Improper drain 

piping may result in water leakage and property damage.

• 

Insulate piping to prevent condensation.

• 

Be careful when transporting the product.

• 

Do not turn off the power immediately after stopping 

operation. Always wait for at least 5 minutes before turning 

off the power. Otherwise, water leakage may occur.

• 

Do not use a charging cylinder. Using a charging cylinder 

may cause the refrigerant to deteriorate.

• 

Refrigerant R410A in the system must be kept clean, dry, 

and tight. 

 

(a)  Clean and Dry -- Foreign materials (including mineral 

oils such as SUNISO oil or moisture) should be 

prevented from getting into the system.

(b)  Tight -- R410A does not contain any chlorine, does not 

destroy the ozone layer, and does not reduce the earth’s 

protection again harmful ultraviolet radiation. R410A 

can contribute to the greenhouse effect if it is released. 

Therefore take proper measures to check for the tightness 

of the refrigerant piping installation. Read the chapter 

Refrigerant Piping Work

 and follow the procedures.

• 

Since R410A is a blend, the required additional refrigerant 

must be charged in its liquid state. If the refrigerant is 

charged in a state of gas, its composition can change and 

the system will not work properly.

• 

The indoor unit is for R410A. See the catalog for indoor 

models that can be connected. Normal operation is not 

possible when connected to other units.

• 

Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 

lamps (inverter or rapid start types). Install the indoor unit 

far away from fluorescent lamps as much as possible.

• 

Indoor units are for indoor installation only. Outdoor units can be 

installed either outdoors or indoors.

• 

Do not install the air conditioner or heat pump in the 

following locations:

(a)  Where a mineral oil mist or oil spray or vapor is 

produced, for example, in a kitchen. 

 

Plastic parts may deteriorate and fall off or result in 

water leakage.

(b)  Where corrosive gas, such as sulfurous acid gas, is 

produced.  

Corroding copper pipes or soldered parts may result in 

refrigerant leakage.

(c)  Near machinery emitting electromagnetic waves. 

Electromagnetic waves may disturb the operation of 

the control system and cause the unit to malfunction.

(d)  

Where flammable gas may leak, where there is carbon 

fiber, or ignitable dust suspension in the air, or where 

volatile flammables such as thinner or gasoline are handled. 

Operating the unit in such conditions can cause a fire.

• 

Take adequate measures to prevent the outdoor unit 

from being used as a shelter by small animals. Small 

animals making contact with electrical parts can cause 

malfunctions, smoke, or fire. Instruct the user to keep the 

area around the unit clean.

NOTE 

• 

The outdoor unit should be positioned where the unit and power 

supply wires (breaker panel to outdoor unit) are at least 10ft (3m) 

away from any televisions or radios. (The unit may cause interference 

with the picture or sound.) Depending on the radio waves, a distance 

of 10ft (3m) may not be sufficient to eliminate the noise.

• 

Dismantling the unit, treatment of the refrigerant, oil and 

additional parts must be done in accordance with the 

relevant local, state, and national regulations.

• 

Do not use the following tools that are used with 

conventional refrigerants: gauge manifold, charge hose, gas 

leak detector, reverse flow check valve, refrigerant charge 

base, vacuum gauge, or refrigerant recovery equipment.

• 

If the conventional refrigerant and refrigerator oil are 

mixed in R410A, the refrigerant may deteriorate.

• 

This air conditioner or heat pump is an appliance that 

should not be accessible to the general public.

•  As design pressure is 604 psi, the wall thickness of field-

installed pipes should be selected in accordance with the 

relevant local, state, and national regulations.

RN003-U

English

01_EN_3P537039-1.indd   2

9/12/2018   7:37:42 PM

Summary of Contents for 4MXL36TVJU

Page 1: ...nglish Français Español MODELS 5MXS48TVJU 4MXL36TVJU DAIKIN ROOM AIR CONDITIONER INSTALLATION MANUAL R410A Split Series Installation manual Manuel dinstallation Manual de instalación Manuel dinstallation ...

Page 2: ...ssive leak can lead to oxygen depletion especially in basements and an asphyxiation hazard could occur leading to serious injury or death Do not ground units to water pipes gas pipes telephone wires or lightning rods as incomplete grounding can cause a severe shock hazard resulting in severe injury or death Additionally grounding to gas pipes could cause a gas leak and potential explosion causing ...

Page 3: ...m getting into the system b Tight R410A does not contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Piping Work and follow the p...

Page 4: ...ife of the air conditioner 8 Since water will flow from the drain of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed suspended from a ceiling or stacked CAUTION When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor...

Page 5: ...ndoor units 9 13 16 250 from wall Allow space for piping and electrical servicing If there is a danger of the unit falling or overturning fix the unit with foundation bolts or with wire or other means In sites with poor drainage use block bases for the outdoor unit Adjust foot height until the unit is level Otherwise water leakage or pooling of water may occur Also insulate the connection on the ou...

Page 6: ...hange the orientation of the outdoor unit outlet side or use the air direction adjustment grille sold separately More than 3 15 16 100 More than 13 3 4 350 Selecting a Location for Installation of the Indoor Units The maximum allowable length of refrigerant piping and the maximum allowable height difference between the outdoor and indoor units are listed below The shorter the refrigerant piping th...

Page 7: ...ng size is determined by the size of the indoor unit fittings Reducers are used at the outdoor unit to accommodate the correct gas line pipe size 4MXL36 Port B 07 09 12 15 18 D E 07 09 12 15 18 24 A 07 09 12 C 07 09 12 15 18 Use a reducer to connect pipes Use No 2 and 4 reducers Use No 5 and 6 reducers Use No 1 and 3 reducers 5MXS48 07 09 12 15 18 07 09 12 15 18 24 07 09 12 07 09 12 15 18 07 09 12...

Page 8: ... inch 12 7mm Be sure to attach the gasket No 2 φ1 2 φ3 8 No 3 φ5 8 φ1 2 No 4 φ1 2 φ3 8 No 5 φ5 8 φ3 8 No 6 φ5 8 φ3 8 Connection port of outdoor unit No 5 No 6 Flare nut for φ3 8 inch 9 5mm Be sure to attach the gasket When using the reducer packing shown above be careful not to overtighten the nut or the smaller pipe may become damaged Apply about 2 3 to 3 3 the normal torque Apply a coat of refri...

Page 9: ...ends in the hose if it is too long or hangs down 5 Make sure the D drain plugs and the B drain socket of the outdoor unit are securely inserted and there is no leakage Drain plugs D Drain plugs Air outlet side B Drain socket D C Drain socket cap B Drain socket Projection Projection 3 Flaring the pipe end WARNING Do not use mineral oil on flared part Prevent mineral oil from getting into the system...

Page 10: ...15 3 8ft lbf 17 0 21 0N m 7 8 inch 22mm 16 1 4 19 7 8ft lbf 22 0 27 0N m Cautions on pipe handling Protect the open end of the pipe from dust and moisture All pipe bends should be as gentle as possible Use a pipe bender for bending Wall If no flare cap is available cover the flare mouth with tape to keep dirt and water out Be sure to place a cap Rain Selection of copper and heat insulation materials...

Page 11: ...Pa for 1 hour minimum 24 hours recommended If there is a pressure drop check for leaks make repairs and perform the pressure test again 2 Connect the gauge manifold s charging hose to the gas stop valve s service port 3 Fully open the low pressure valve Lo on the gauge manifold and fully close the high pressure valve Hi High pressure valve will require no further operation 4 Evacuate system using ...

Page 12: ...phon pipe inside so the cylinder need not be upside down to fill with liquid Filling other cylinders Turn the cylinder upside down when filling Be sure to use the R410A tools to ensure pressure and to prevent foreign objects entering 7 Charging with refrigerant CAUTION Even though the stop valve is fully closed the refrigerant may slowly leak out do not leave the flare nut removed for a long period ...

Page 13: ...er with at least 1 8 inch 3mm between the contact point gaps When carrying out wiring take care not to pull at the conduit Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire Do not turn on the circuit breaker until all work is completed Method of Mounting Conduit When connecting indoor units for 3 rooms or more open knockout holes without deforming the condu...

Page 14: ...om D terminal blocks are actually integrated Recommend using AWG14 stranded and insulated wire for connections between indoor and outdoor units Local code always supersedes recommendation Shape the wires so that there is no lifting of the shield cover or other structural parts For Room A For Room E For Room C For Room D For Room B For power supply Ground wires Ground wires Use the specified wires a...

Page 15: ...ording to the operation mode of the set indoor unit 2 Priority during powerful operation If the indoor unit which is set for priority room setting is operating at powerful the capabilities of other indoor units will be somewhat reduced Power supply gives priority to the indoor unit which is set for priority room setting 3 Quiet operation priority Setting the indoor unit to quiet operation will mak...

Page 16: ...edure Turn the night quiet mode switch SW6 1 to on COOL HEAT mode lock S15 1 Remove the top plate 10 screws 2 Remove the right side plate 6 screws 3 Remove the front plate 1 screw The front plate is heavy so take care 4 Remove the shield plate 2 screws 5 Use the S15 connector to set the unit to only cool or heat Setting to only heat H short circuit pins 1 and 3 of the connector S15 Setting to only...

Page 17: ...ervice PC board switch cover 1 screw 4 Switch SW5 and SW6 to off 5 Turn the operation mode switch SW2 to COOL 6 Screw the service PC board switch cover back on 1 screw 7 Attach the shield cover 2 screws and the right side plate 6 screws 8 Turn on the power 9 Push the forced operation switch SW1 above the service PC board cover The operation will start Forced cooling operation will stop automatical...

Page 18: ...er to the collective indications label on the reverse side of the right side plate or the service manual If self correction is not possible check the indoor unit wiring and piping in the usual manner Service PC board A 1 2 3 4 5 Wiring error check switch SW3 LED Status 1 2 3 4 5 All Flashing Automatic correction impossible Automatic correction completed Abnormal stop Note 3 Message Flashing One af...

Page 19: ... unit inlet and outlet If the measurements are above the values shown in the table below then they are normal COOL operation HEAT operation Temperature difference between inlet and outlet About 14 F 8 C About 36 F 20 C When running in one room 2 5 After trial operation is complete set the temperature to a normal level 78 F to 82 F 26 C to 28 C in COOL operation 68 F to 75 F 20 C to 24 C in HEAT op...

Page 20: ...Two dimensional bar code is a manufacturing code 3P537039 1 M18B063 1809 HT ...

Reviews: