8
|
Charging refrigerant
Installer reference guide
47
4MWXM-A
R32 Split series
4P678385-1A – 2022.02
3
Open the gas stop valve.
If pump down is needed in case of dismantling or relocating the system, see
8.7 To fix the fluorinated greenhouse gases label
1
Fill in the label as follows:
b
Contains fluorinated greenhouse gases
2
1
1
1
2
2
kg
tCO
2
eq
GWP × kg
1000
=
=
+
kg
=
kg
=
GWP: XXX
RXXX
a
f
c
d
e
a
If a multilingual fluorinated greenhouse gases label is delivered with the unit (see
accessories), peel off the applicable language and stick it on top of
a
.
b
Factory refrigerant charge: see unit name plate
c
Additional refrigerant amount charged
d
Total refrigerant charge
e Quantity of fluorinated greenhouse gases
of the total refrigerant charge
expressed as tonnes CO
2
equivalent.
f
GWP = Global warming potential
NOTICE
Applicable legislation on
fluorinated greenhouse gases
requires that the refrigerant
charge of the unit is indicated both in weight and CO
2
equivalent.
Formula to calculate the quantity in CO
2
equivalent tonnes:
GWP value of the
refrigerant × total refrigerant charge [in kg] / 1000
Use the GWP value mentioned on the refrigerant charge label.
2
Fix the label on the inside of the outdoor unit near the gas and liquid stop
valves.
Summary of Contents for 4MWXM-A
Page 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B ...
Page 32: ...6 Unit installation Installer reference guide 32 4MWXM A R32 Split series 4P678385 1A 2022 02 ...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ...4P678385 1A 2022 02 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...