7
|
Piping installation
Installer reference guide
38
4MWXM-A
R32 Split series
4P678385-1A – 2022.02
a
b
a
Cut exactly at right angles.
b
Remove burrs.
3
Remove the flare nut from the stop valve and put the flare nut on the pipe.
4
Flare the pipe. Set exactly at the position as shown in the following figure.
A
Flare tool for R32
(clutch type)
Conventional flare tool
Clutch type
(Ridgid-type)
Wing nut type
(Imperial-type)
A
0~0.5 mm
1.0~1.5 mm
1.5~2.0 mm
5
Check that the flaring is properly made.
a
b
c
a
Flare’s inner surface MUST be flawless.
b
The pipe end MUST be evenly flared in a perfect circle.
c
Make sure the flare nut is fitted.
7.2.6 Connections between outdoor and indoor unit using reducers
Total indoor air conditioning units capacity class that can be connected to this
outdoor unit
≤9.0 kW
Port
Dimensions
Class
Reducer
A
Liquid Ø6.4 mm
Gas Ø9.5 mm
15, 20, 25, 35, (42)
(a)
—
B+C
Liquid Ø6.4 mm
Gas Ø12.7 mm
15, 20, 25, 35, (42)
(a)
1+2 (accessory)
42, 50, 60
—
71
(b)
ASYCPIR
To tank
Liquid Ø6.4 mm
Gas Ø9.5 mm
90, 120
—
(a)
Only in case of connection with FTXM42R.
(b)
Only for connection with FBA71A9. Use option ASYCPIR for liquid (Ø9.5 mm→Ø6.4 mm)
and gas (Ø15.9 mm→Ø12.7 mm) piping.
1
2
Ø12.7 mm → Ø9.5 mm
Summary of Contents for 4MWXM-A
Page 1: ...Installer reference guide R32 Split series 4MWXM52A2V1B ...
Page 32: ...6 Unit installation Installer reference guide 32 4MWXM A R32 Split series 4P678385 1A 2022 02 ...
Page 77: ......
Page 78: ......
Page 79: ......
Page 80: ...4P678385 1A 2022 02 Copyright 2021 Daikin Verantwortung für Energie und Umwelt ...