background image

3P384095-3A  M14B150A

DAIKIN AIR CONDITIONER

• The precautions described herein are classified as WARNING and CAUTION. They both contain important 

information regarding safety. Be sure to observe all precautions without fail.

• Meaning of WARNING and CAUTION notices

WARNING

• The safety marks shown in this manual have the following meanings:

• After completing installation, conduct a trial operation to check for faults and explain to the customer how to 

operate the air conditioner and take care of it with the aid of the operation manual.

• Ask your dealer or qualified personnel to carry out installation work. 

Do not attempt to install the air conditioner yourself. Improper installation may result in water leakage, electric shocks or fire.

• 

Install the air conditioner in accordance with the instructions in this installation manual. 

Improper installation may result in water leakage, electric shocks or fire.

• 

Be sure to use only the specified accessories and parts for installation work. 

Failure to use the specified parts may result in the unit falling, water leakage, electric shocks or fire.

• 

Electrical work must be performed in accordance with relevant local and national regulations and with the instructions in this installation manual. 

Be sure to use a dedicated power supply circuit only. 

Insufficient power supply and improper workmanship may result in electric shocks or fire.

• Use a cable of suitable length. 

Do not use tapped wires or an extension lead, as this may cause overheating, electric shocks or fire.

• 

When wiring the power supply and connecting the wiring between the indoor and outdoor units, position the wires so that the 

control box lid can be securely fastened. 

Improper positioning of the control box lid may result in electric shocks, fire or over heating terminals.

• Make sure that all wiring is secured, the specified wires are used, and that there is no strain on the terminal 

connections or wires. 

Improper connections or securing of wires may result in abnormal heat build-up or fire.

• 

When installing or relocating the air conditioner, do not let any other substances besides R32, such as air, enter the refrigerant circuit.

 

The presence of air or other foreign matter in the refrigerant circuit causes an abnormal pressure rise, which may result in equipment damage and even injury.

• If refrigerant gas leaks during installation, ventilate the area immediately.

Toxic gas may be produced if the refrigerant comes into contact with fire.

• After completing installation, check for refrigerant gas leakage.

 

Toxic gas may be produced if the refrigerant gas 

leaks into the room and comes into contact with a source of fire, such as a fan heater, stove or cooker.

• Be sure to earth the air conditioner.  

Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. Imperfect earthing may result in electric shocks.

• 

Be sure to install an earth leakage circuit breaker. 

Failure to install an earth leakage circuit breaker may result in electric shocks or fire.

• 

During installation, attach the refrigerant piping securely before operating the compressor. 

If the refrigerant pipes are not attached and the stop valve 

is open when the compressor is operated, air will be sucked in, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

• 

During pump down, stop the compressor before removing the refrigerant piping. 

If the compressor is still operating and the stop valve is open during pump 

down, air will be sucked in when the refrigerant piping is removed, causing abnormal pressure in the refrigeration cycle, which may result in equipment damage and even injury.

Safety Precautions (1)

WARNING

CAUTION

Failure to follow these instructions properly may result in personal injury or loss of life.

Failure to follow these instructions properly may result in property damage or personal injury, which may be serious depending on the circumstances.

Be sure to follow the instructions.

Be sure to establish an earth connection.

Never attempt.

• Install the air conditioner on a foundation strong enough to hold the weight of the unit. 

A foundation of insufficient strength may result in the equipment falling and causing injury.

Read the precautions in this manual 

carefully before operating the unit.

This appliance is filled with R32.

• Do not pierce or burn.

• 

Do not use means to accelerate the defrosting process or to clean, other than those recommended by the manufacturer.

• The appliance must be stored in a room without continuously operating ignition sources (for example: open flames, 

an operating gas appliance or an operating electric heater).

• Be aware that refrigerants may not contain an odour.
• The appliance must be installed, operated and stored in a room with a floor area larger than 4.9m

2

.

• Comply with national gas regulations.

Two-dimensional bar code 
is a manufacturing code.

Accessories

Precautions for Selecting the Location

• Choose a place solid enough to bear the weight and vibration of the unit, where the operating sound will not 

be amplified.

• Choose a location where the hot air discharged from the unit or the operating sound will not cause a 

nuisance to the neighbours of the user.

• 

Avoid places near a bedroom and the like, so that the operating sound will cause no trouble.

• 

There must be sufficient spaces for carrying the unit into and out of the site.

• 

There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.

• 

The site must be free from the possibility of flammable gas leakage in a nearby place.

• 

Install units, power cords and inter-unit wire at least 3m away from television and radio sets.  This is to 

prevent interference to images and sounds.  (Noise may be experienced even if they are more than 3m 

away depending on radio wave conditions.)

• 

In coastal areas or other places with a salty atmosphere or one containing sulphate gas, corrosion may 

shorten the life of the air conditioner.

• 

Since water will flow from the drain of the outdoor unit, do not place under the unit anything which must be 

kept away from moisture.

NOTE

Cannot be installed suspended  from ceiling or stacked.

Construct a large canopy.
Construct a pedestal.

Install the unit high enough 
off the ground to prevent 

burying in snow.

Accessories supplied with the outdoor unit:

When operating the air conditioner in a low outdoor ambient 

temperature, be sure to follow the instructions described below.

 •  To prevent exposure to wind, install the outdoor unit with its 

suction side facing the wall.

 •  Never install the outdoor unit at a site where the suction side may 

be exposed directly to wind.

 •  To prevent exposure to wind, it is recommended to install a baffle 

plate on the air discharge side of the outdoor unit.

 •  In heavy snowfall areas, select an installation site where the snow will not affect the unit.

CAUTION

N004

1

1

Installation manual

A

Refrigerant charge label

C

1

There is on the bottom packing case.

Drain socket 

(Only heat pump models)

B

 This product is not designed for re-packing. In case of re-packing contact to Daikin dealer.

Safety Precautions (2)

CAUTION

• Do not install the air conditioner at any place where there is a danger of flammable gas leakage. 

In the event of a gas leakage, build-up of gas near the air conditioner may cause a fire to break out.

• Tighten the flare nut as specified, such as with a torque wrench. 

If the flare nut is too tight, it may crack after prolonged use, causing refrigerant leakage.

• 

The temperature of refrigerant circuit will be high, please keep the inter-unit wires away from copper pipes that are not thermally insulated.

• While following the instructions in this installation manual, install drain piping to ensure proper drainage and insulate 

the piping to prevent condensation. 

Improper drain piping may result in indoor water leakage and property damage.

• Only qualified personnel can handle, fill, purge and dispose of the refrigerant.

1

1

2

2

+ =

2

=

1

=

• 

Where a wall or other obstacle is in the path of the outdoor unit’s intake or exhaust airflow, follow the installation guidelines below.

•  For any of the below installation patterns, the wall height on the outlet side should be 1200mm or less.

Outdoor Unit Installation Drawings

Installation Guidelines

Precautions on Installation

• 

Check the strength and level of the installation surface so that the unit does not 

cause any operating vibration or noise after installation.

• 

In accordance with the foundation drawing, fix the unit securely by means of the foundation bolts. 

(Prepare 4 sets of M8 or M10 foundation bolts, nuts and washers; all separately available.)

• 

It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface.

20mm

Top view

More than 50

More than 

350

More than 50

More 

than 100

Walls facing two sides

unit: mm

More than 100

More 

than 350

Side view

Wall facing one side

More than 100

More than 350

1200

or less

CAUTION

** Keep the piping length 
  between 1.5m and 30m.

376mm

(Foot bolt-hole centres)

Stop valve cover

Service lid

250mm from w

all

(Foot bolt-hole centres)

(

From unit’s side)

175mm

610mm

Allow space for piping 
and electrical servicing.

Allow 300mm of 

work space below 

the ceiling surface.

Wrap the insulation 

pipe with finishing tape 
from bottom to top.

Refrigerant piping must be 
protected from physical damage.
Install a plastic cover or equivalent.

Partition plate

Where there is a danger of the unit falling, use foot bolts, or wires.

In sites with poor drainage, use 
block bases for the outdoor unit.
Adjust foot height until the unit is 
level.  Otherwise, water leakage or 
pooling of water may occur.

Max. allowable piping height

Max. allowable piping length

30m

20m

Min. allowable piping length

1.5m

Liquid pipe

Gas pipe

O.D. 6.4mm

O.D. 12.7mm O.D. 15.9mm

20g/m

Additional refrigerant 

required for refrigerant pipe 

exceeding 10m in length.

Max. allowable refrigerant 

charge amount

***

**

*

Refrigerant piping must be kept to a minimum.

*

   Be sure to add the proper amount of additional 

refrigerant.

  Failure to do so may result in reduced performance.

**

  The suggested shortest pipe length is 1.5m, in order 

to avoid noise from the outdoor unit and vibration. 
(Mechanical noise and vibration may occur 
depending on how the unit is installed and the 
environment in which it is used.)

***

18 class
24 class
28 class

1.52kg
1.80kg
2.00kg

Unit dimensions 

Height

Width

Depth

695mm
930mm
350mm

Please fill in with indelible ink, 

 

1

  

the factory refrigerant charge of the product, 

 

2

  

the additional refrigerant amount charged in the field and

 

1

  +  

2

  

the total refrigerant charge 

on the refrigerant charge label supplied with the product.
Affix the refrigerant charge label near the manufacturer’s label 
after filling it out.

Refrigerant charge label

1

  factory refrigerant charge of the product: 

see unit name plate 

2

  additional refrigerant amount charged in 

the field 

3

  total refrigerant charge 

4  outdoor unit

5

  refrigerant cylinder and manifold for 

charging

The filled out label must be adhered in the 
proximity of the product charging port.

1

1

2

2

+ =

2

=

1

=

3

4

5

2

1

C

Outdoor Unit Installation (1)

4.

  Refrigerant piping

3.

  Flaring the pipe end

1) Cut the pipe end with a pipe cutter.

2) Remove burrs with the cut surface 

facing downward so that the chips do 

not enter the pipe.

3) Put the flare nut on the pipe.

4) Flare the pipe.

5) Check that the flaring is properly made.

 •  Do not use mineral oil on flared part.

 •  Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.

 • 

Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.

 •  Never install a drier to this R32 unit in order to guarantee its lifetime.

 •  The drying material may dissolve and damage the system.

 •  Incomplete flaring may cause refrigerant gas leakage.

WARNING

Valve cap tightening torque

Gas side

Liquid side

15.9mm

12.7mm

6.4mm

48.1-59.7N • m

(490-610kgf • cm)

21.6-27.4N • m

(220-280kgf • cm)

Flare nut tightening torque

Gas side

Liquid side

12.7mm

6.4mm

49.5-60.3N • m

(505-615kgf • cm)

15.9mm

61.8-75.4N • m

(630-770kgf • cm)

14.2-17.2N • m

(144-175kgf • cm)

 •  Use the flare nut fixed to the main unit. (This is to prevent cracking of the flare nut as a result of 

deterioration over time.)

 • 

To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil for R32.)

 • 

Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage.

 •  Align the centres of both flares and tighten the flare nuts 3 or 4 turns by hand.  Then tighten them fully 

with a spanner and a torque wrench.

 •  Refrigerant oil for R410A can also be used for application to the inner flare.

CAUTION

Do not apply refrigeration oil to the outer surface.

Flare nut

Apply refrigeration oil to the inner surface of the flare.

Do not apply refrigeration oil to the flare nut 
to avoid tightening with excessive torque.

Apply oil

Service port cap tightening torque

10.8-14.7N • m (110-150kgf • cm)

1.

  Installing the outdoor unit

2) If drain work is necessary, follow the procedures below.

2.

  Drain work

1) Use the     drain socket for drainage.

2) When attaching the     drain socket to the bottom frame make sure to first 

connect the drain hose to the drain socket.

3) If the drain port is covered by a mounting base or floor surface, place 

additional foot bases of at least 30mm in height under the outdoor unit’s feet.

4) In cold areas, do not use a drain hose with the outdoor unit.  

(Otherwise, the drain water may freeze, impairing heating performance.)

B

B

1) When installing the outdoor unit, refer to “Precautions for Selecting the Location” and the “Outdoor 

Unit Installation Drawings”.

(Cut exactly at 

right angles.)

 Remove burrs.

Set exactly at the position shown below.

A

Flaring

Die

A

0-0.5mm

Clutch-type

Flare tool for R32 or R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

Check

Flare’s inner 
surface must 

be flaw-free.

The pipe end must 

be evenly flared in 

a perfect circle.

Make sure that the 

flare nut is fitted.

B

Drain-water hole

Bottom frame

Drain socket

Hose (available commercially,

inner dia. 16mm)

Outdoor Unit Installation (2)

*1. Pipe length vs. vacuum pump run time

*2. If the compound pressure gauge pointer swings back, refrigerant may have water content or a loose pipe 

joint may exist.  Check all pipe joints and retighten nuts as needed, then repeat steps 2) through 4).

•  When piping work is completed, it is necessary to evacuate the air with a 

vacuum pump and check for gas leakage.

•  If using additional refrigerant, perform air purging of the refrigerant pipes 

and indoor unit using a vacuum pump, then charge additional refrigerant.

•  Use a hexagonal wrench (4mm) to operate the stop valve rod.
•  All refrigerant pipe joints should be tightened with a torque wrench to the 

specified tightening torque.

5.

  Evacuating the air with a vacuum pump and checking for gas leakage

 •  Do not mix any substance other than the specified refrigerant (R32) into the refrigeration cycle.

 •  If refrigerant gas leaks should occur, ventilate the room as soon and as much as possible.

 • 

R32, as well as other refrigerants, should always be recovered and never be released directly into the 

environment.

 •  Use a vacuum pump for R32 or R410A exclusively. Using the same vacuum pump for different 

refrigerants may damage the vacuum pump or the unit.

 • 

Use tools for R32 or R410A (such as the gauge manifold, charging hose, or vacuum pump 

adapter).

1) Connect projection side of charging hose (which comes from gauge manifold) to gas stop valve’s 

service port.

2) Fully open gauge manifold’s low-pressure valve (Lo) and completely close its high-pressure valve (Hi).  

(High-pressure valve subsequently requires no operation.)

3) Perform vacuum pumping and make sure that the compound pressure gauge reads –0.1MPa 

(–76cmHg).*1

4) Close gauge manifold’s low-pressure valve (Lo) and stop vacuum pump.  

(Keep this state for a few minutes to make sure that the compound pressure gauge pointer does not 

swing back.)*2

5) Remove valve caps from liquid stop valve and gas stop valve.

6) Turn the liquid stop valve’s rod 90° counter-clockwise with a hexagonal wrench to open the valve.

Close it after 5 seconds, and check for gas leakage.

Using soapy water, check for gas leakage from indoor unit’s flare and outdoor unit’s flare and valve rods.

After the check is complete, wipe all soapy water off.

7) Disconnect charging hose from gas stop valve’s service port, then fully open liquid and gas stop valves.

(Do not attempt to turn valve rod beyond its stop.)

8) Tighten valve caps and service port cap for the liquid and gas stop valves with a torque wrench to the 

specified torques.

Pipe length

Up to 15m

More than 15m

Run time

Not less than 10 min.

Not less than 15 min.

WARNING

Gauge 

manifold

Compound 

pressure gauge

Pressure meter

Low-pressure 

valve

High-pressure 

valve

Charging 

hoses

Vacuum pump

Valve 

caps

Service port

Liquid 

stop 

valve

Gas stop 

valve

Outdoor Unit Installation (3)

6.

  Refrigerant piping work

 

6-1  Cautions on pipe handling

   

1)  Protect the open end of the pipe against dust and moisture.

   

2)  All pipe bends should be as gentle as possible. Use a pipe bender 

for bending.

 

6-2 Selection of copper and heat insulation materials

  

When using com

mercial copper pipes and fittings, observe the following:

  

1)  Insulation material:  Polyethylene foam 

   

 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

   

 

Refrigerant gas pipe’s surface temperature reaches 110°C max.

   

 

Choose heat insulation materials that will withstand this temperature.

   

2)  Be sure to insulate both the gas and liquid piping and to provide 

insulation dimensions as below.

   

3)

   Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

Wiring (1)

•   

Do not turn on the circuit breaker until all 

work is completed.

1) 

Dismount the service lid and the partition 

plate. (Refer to 

Fig. 1 in Wiring (2).)

2) 

Strip the insulation from the wire (20mm).

3) 

Connect the inter-unit wire between the 

indoor and outdoor units 

so that the 

terminal numbers match. Tighten the 

terminal screws securely. We recommend a 
flathead screwdriver be used to tighten the 
screws. (Refer to 

Fig. 2 in Wiring (2).)

4)  Pull the wire lightly to make sure that it does not disconnect. Then fix the wire in place with the wire retainer.
5)  After completing the work, reattach the partition plate and the service lid to their original positions. (Refer to 

“How to attach the partition plate.” in Wiring (2).)

 •  Do not use tapped wires, extension cords, or starburst connections, as they may cause overheating, 

electrical shock, or fire.

 •  Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain 

pump, etc., from the terminal block.) Doing so may cause electric shock or fire.

 •  Be sure to install an earth leak detector. (One that can handle higher harmonics.)
   (This unit uses an inverter, which means that an earth leak detector capable of handling harmonics must 

be used in order to prevent any malfunction of the earth leak detector itself.)

 •  Use an all-pole disconnection type circuit breaker with at least 3mm between the contact point gaps.

 •  Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

WARNING

Gas side

Piping size

O.D. 12.7mm

O.D. 15.9mm

O.D. 6.4mm

40mm or more

50mm or more

30mm or more

0.8mm (C1220T-O)

1.0mm (C1220T-O)

0.8mm (C1220T-O)

I.D. 14-16mm

I.D. 16-20mm

I.D. 8-10mm

10mm Min.

Minimum bend radius

Piping thickness

Thermal insulation size Thermal insulation

thickness

Liquid side

Wall

If no flare cap is 

available, cover the 

flare mouth with 

tape to keep dirt or 

water out.

Be sure to 

place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wire

1

2

3

1 2

3

Circuit 

breaker

20A

Earth leakage 

circuit breaker

Earth

Firmly fix the wires with 

the ter

minal screws.

Outdoor unit

Indoor 
unit

Power supply
50Hz 220V-240V 
60Hz 220V-230V 

Firmly fix the wires with 

the ter

minal screws.

L N

Power supply wire
3-core 2.5mm² or more
60245 IEC 57

Inter-unit wire
4-core 1.5mm² or more
60245 IEC 57

Wiring (2)

 •  Precautions to be taken for power supply wiring.

When using stranded wires, make sure to use a 
round crimp-style terminal for connection to the 
power supply terminal block. Place the round 
crimp-style terminals on the wires up to the 
covered part and secure in place.  

 •  Use the following method when installing a round crimp-style terminal. 

•  When connecting the inter-unit wire to the terminal block using a single core wire, be sure to curl 

the end of the lead. Improper work may cause heat and fires.

Wire retainer

CAUTION

Stranded 
wire

Round crimp-style
terminal

Stripping wire at terminal block

Good

Wrong

Good

Wrong

Arrow view 

A

 

Screw
Round crimp-style 

terminal

Flat washer

Screw

Round crimp-style 

terminal

Flat washer

A

Flat washer

Screw

Round crimp-style terminal

Good

Wrong

Strip wire end 
to this point.

Excessive strip length may 
cause electrical shock or leakage.

 How to attach the partition plate.

1) Insert the protrusion of the partition 

plate into the notch in the metal 
sheet.

2) Slide the partition plate so that the tab 

on the metal sheet fits into the slit on 

the partition plate.

3) Secure with 2 screws.

Screws

Service lid

Partition plate

Fig. 1

Screws

Power supply
terminal block

1

2

3

Partition plate

Do not strip the 
cover all the way 
to the part that 
comes in contact 
with the partition 
plate.

Shape wires 
so that the 
service lid 

fits securely.

Fig. 2

Slit

Partition plate

Protrusion

Notch

1)

1)

2)

2)

Tab

Test items

Incomplete cooling/heating function

No refrigerant gas leaks.

Draining line is properly installed.

Indoor and outdoor units are installed properly on solid bases.

Refrigerant gas and liquid pipes and indoor drain hose 

extension are thermally insulated.

Fall, vibration, noise

Water leakage
Water leakage

System is properly earthed.

Electrical leakage

Indoor unit properly receives remote control commands.

No operation

Stop valves are opened.

Incomplete cooling/heating function
Incomplete cooling/heating function

The specified wires are used for inter-unit wiring.

No operation or burn damage

Symptom

Check

Indoor or outdoor unit’s air inlet or air outlet are 

unobstructed.

1.

  Trial operation and testing

•  Trial operation should be carried out in either COOL or HEAT operation. (RKM models are operable in COOL operation only)

 1-1 

Measure the supply voltage and make sure that it is within the specified range.

 1-2 In COOL operation, select the lowest programmable temperature; in HEAT operation, select 

the highest programmable temperature.

1-3 Carry out the trial operation in accordance with the operation manual to ensure that all 

functions and parts, such as louvres movement, are working properly.

•  For protection, the system disables restart operation for 3 minutes after it is turned off.
•  When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on, in some cases no 

air will be output for about 10 minutes in order to protect the air conditioner.

1-4 After trial operation is complete, set the temperature to a normal level (26°C to 28°C in COOL 

operation, 20°C to 24°C in HEAT operation).

•  When operating the air conditioner in COOL operation in winter, or HEAT operation in summer, set it to the trial operation 

mode (See the installation manual for the indoor unit).

•  The air conditioner draws a small amount of power in its standby mode.  If the system is not to be used for some time after 

installation, shut off the circuit breaker to eliminate unnecessary power consumption.

•  If the circuit breaker trips to shut off the power to the air conditioner, the system will restore the original operation mode when 

the circuit breaker is opened again.

2.

  Test items

Trial Operation and Testing

Valve cap

Hexagonal 

wrench

Close

Liquid stop valve

Gas stop valve

Service port

CAUTION

When pressing the switch, do not touch the terminal block. It has a high voltage, and touching it could cause electric shock.

Pump Down Operation

In order to protect the environment, be sure to pump down when relocating or disposing of the unit.

1)  Remove the valve caps from the liquid stop valve and gas stop valve.

2)  Carry out forced cooling operation.

3)  After 3 to 4 minutes, close the liquid stop valve with a hexagonal wrench.

4)  5 to 6 minutes after closing the liquid stop valve, close the gas stop valve and stop forced 

cooling operation.

Forced cooling operation

 

  Using the indoor unit ON/OFF switch

Press the indoor unit ON/OFF switch for at least 5 seconds. (The operation will start.)

•  Forced cooling operation will stop automatically after about 15 minutes. 

To stop the operation, press the indoor unit ON/OFF switch.

 

  Using the indoor unit’s remote controller

1)  Press         and select the COOL operation.

2)  Press         to turn on the system.

3)  Press both of      and         at the same time. 

4)  Press      , select “     ”, and press         for confirmation.

•  Forced cooling operation will stop automatically after about 30 minutes. To stop the operation, press        .

01_EN_3P384095-3A.indd   1

2019/07/23   8:52:40

Summary of Contents for 3P384095-1A

Page 1: ...tions or wires Improper connections or securing of wires may result in abnormal heat build up or fire Install the air conditioner on a foundation strong enough to hold the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury When installing or relocating the air conditioner do not let any other substances besides R32 such as air enter the re...

Page 2: ... be positioned in a place where 1 the restrictions on the installation requirements specified in the indoor unit installation drawings are met 2 both the air inlet and air outlet are unobstructed 3 the unit is not exposed to direct sunlight 4 the unit is away from sources of heat or steam 5 there is no source of machine oil vapour this may shorten the indoor unit service life 6 cool warm air is cir...

Page 3: ...sure that no gap is left in the insulation pipe s cut line Caulk pipe hole gap with putty Wireless remote controller D E Remote controller holder Fixing screws for remote controller holder M3 20L 2 pcs F How to attach the indoor unit Hook the tabs of the bottom frame to the mounting plate If the tabs are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area...

Page 4: ...it as a guide 4 Open the front panel then open the service lid Refer to Installation Tips 5 Pass the inter unit wire from the outdoor unit through the feed through wall hole and then through the back of the indoor unit Pull them through the front side Bend the ends of cable tie wires upward for easier work in advance If the inter unit wire ends are to be stripped first bundle the wire lead ends wit...

Page 5: ...se tapped wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire WARNING How to set the...

Page 6: ... pipe 4 Flare the pipe 5 Check that the flaring is properly made Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a drier to this R32 unit in order to guarantee it s lifetime The drying mate...

Page 7: ...flare nut fixed to the main unit This is to prevent cracking of the flare nut as a result of deterioration over time To prevent gas leakage apply refrigeration oil only to the inner surface of the flare Use refrigeration oil for R32 Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage CAUTION Wall If no flare cap is available cover the flare mouth with tap...

Page 8: ...peration manual to ensure that all functions and parts such as louvres movement are working properly For protection the system disables restart operation for 3 minutes after it is turned off When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on in some cases no air will be output for about 10 minutes in order to protect the air conditioner 1 4 Afte...

Page 9: ...ﻏﻴﺮ ﺗﺰاﻳﺪ ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ اﻷﺳﻼك ﺗﺜﺒﻴﺖ أو اﳋﺎﻃﺌﺔ اﻟﺘﻮﺻﻴﻼت اﻟﻮﺣﺪة وزن ﻞ ﹼ ﻟﺘﺤﻤ ﻛﺎﻓﻲ ﺑﺸﻜﻞ ﻗﻮﻳﺔ ﻗﺎﻋﺪة ﻋﻠﻰ اﻟﻬﻮاء ﻣﻜﻴﻒ ﺑﺘﺮﻛﻴﺐ ﻗﻢ إﺻﺎﺑﺔ ﺑﺤﺪوث واﻟﺘﺴﺒﺐ اﳌﻌﺪات ﺳﻘﻮط ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ ﹴ ﻛﺎف ﹴ ﻞ ﺑﺸﻜ ﻗﻮﻳﺔ ﻏﻴﺮ ﻗﺎﻋﺪة ﺑﺘﺮﻛﻴﺐ اﻟﻘﻴﺎم ﻋﻨﺪ اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ داﺋﺮة إﻟﻰ ﺑﺎﻟﺪﺧﻮل اﻟﻬﻮاء ﻣﺜﻞ R32 ﻏﺎز ﺟﺎﻧﺐ إﻟﻰ أﺧﺮى ﻣﻮاد أﻳﺔ ﺗﺪع ﻻ اﻟﺘﺮﻛﻴﺐ ﻣﻮﻗﻊ ﺗﻐﻴﻴﺮ إﻋﺎدة أو اﻟﻬﻮاء ﻣﻜﻴﻒ ﺗﺮﻛﻴﺐ ﻋﻨﺪ ﺑﺠﺮوح اﻹﺻﺎﺑﺔ إﻟﻰ وﺣﺘﻰ اﳌﻌﺪات ﺗﻠﻒ إﻟﻰ ﺑﺪوره ﻳﺆدي ﻗﺪ واﻟﺬي ﻃ...

Page 10: ...ﻛﻴﺐ ﻣﺘﻄﻠﺒﺎت ﻋﻠﻰ اﳌﻔﺮوﺿﺔ اﻟﻘﻴﻮد ﻳﺴﺘﻮﻓﻲ 1 اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﺗﺮﻛﻴﺐ ﻣﺨﻄﻄﺎت اﻟﻬﻮاء وﻣﺨﺮج اﻟﻬﻮاء ﻣﺪﺧﻞ ﻣﻦ ﹴ ﻞ ﻛ ﻓﻲ ﻋﻮاﺋﻖ ﺗﻮﺟﺪ ﻻ 2 اﳌﺒﺎﺷﺮة اﻟﺸﻤﺲ ﻷﺷﻌﺔ ﻣﻌﺮﺿﺔ اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن ﻻ 3 اﻟﺒﺨﺎر أو اﳊﺮارة ﻣﺼﺎدر ﻋﻦ ﺑﻌﻴﺪة اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن 4 اﻟﻌﻤﺮ ﺗﻘﻠﻴﻞ إﻟﻰ ﻫﺬا ﻳﺆدي أن ﳝﻜﻦ اﻵﻟﺔ زﻳﺖ ﺑﺨﺎر ﻓﻴﻪ ﻳﻮﺟﺪ ﻻ 5 اﻟﺪاﺧﻠﻴﺔ ﻟﻠﻮﺣﺪة اﻟﺘﺸﻐﻴﻠﻲ اﻟﻐﺮﻓﺔ ﻋﺒﺮ اﻟﺪاﻓﺊ اﻟﺒﺎرد اﻟﻬﻮاء ﺗﺪوﻳﺮ ﻓﻴﻪ ﻳﺘﻢ 6 اﳌﺼﺎﺑﻴﺢ أﻧﻮاع ﻣﻦ ﻧﻮع أي ﻋﻦ ﺑﻌﻴﺪة اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن ﻣﻜﺎ...

Page 11: ... ﺗﺜﺒﻴﺖ ﺑﺮاﻏﻲ ﻣﻘﺎس ﺑﻌﺪ ﻋﻦ اﻟﺘﺤﻜﻢ ﻗﻄﻌﺔ 2 20L M3 F اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﺗﺜﺒﻴﺖ ﻛﻴﻔﻴﺔ اﻟﺴﻔﻠﻲ ﺑﺎﻹﻃﺎر اﳋﺎﺻﺔ اﻷﻟﺴﻨﺔ ﺑﺮﺑﻂ ﻗﻢ اﻟﺘﻌﻠﻴﻖ ﻟﻮﺣﺔ إﻟﻰ ﺗﺼﻞ أن إﻟﻰ اﻧﺰع اﻷﻟﺴﻨﺔ رﺑﻂ اﻟﺼﻌﺐ ﻣﻦ ﻛﺎن إذا اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﻧﺰع ﻛﻴﻔﻴﺔ ﻟﻸﻋﻠﻰ ﻋﻼﻣﺔ ﲢﻤﻞ اﻟﺘﻲ اﳌﻨﻄﻘﺔ ادﻓﻊ اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ ﻣﻦ اﻟﺴﻔﻠﻲ اﳉﺰء ﻋﻨﺪ اﻟﻘﻴﺎم اﻟﺼﻌﺐ ﻣﻦ ﻛﺎن إذا اﻷﻟﺴﻨﺔ ﻟﺘﺤﺮﻳﺮ اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ اﻧﺰع ﺑﺘﺤﺮﻳﺮه اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ A اﻟﺘﻌﻠﻴﻖ ﻟﻮﺣﺔ اﻟﻠﺴﺎن اﻟﺴﻔﻠﻲ اﻹﻃﺎر اﳋﻠﻔﻲ...

Page 12: ...ي اﳉﺰء ﻋﻠﻰ اﳌﻮﺟﻮدة اﻟﺼﻴﺎﻧﺔ ﻏﻄﺎء اﻓﺘﺢ ﺛﻢ وﻣﻦ اﻷﻣﺎﻣﻴﺔ اﻟﻠﻮﺣﺔ اﻓﺘﺢ 4 اﻟﺘﺮﻛﻴﺐ ﺣﻮل ﺗﻮﺟﻴﻬﺎت راﺟﻊ ﺧﻼﻟﻪ ﻣﻦ ﻳﺘﻢ ﺛﻘﺐ ﻋﺒﺮ اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة ﻣﻦ ﻟﻠﻮﺣﺪة اﻟﺪاﺧﻠﻲ اﻟﺴﻠﻚ ﺑﺘﻤﺮﻳﺮ ﻗﻢ 5 اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﻣﻦ اﳋﻠﻔﻴﺔ اﳉﻬﺔ ﺧﻼل ﻣﻦ ﺛﻢ وﻣﻦ اﻟﺘﻠﻘﻴﻢ اﻷﻣﺎﻣﻲ اﳉﺎﻧﺐ ﺧﻼل ﻣﻦ اﺳﺤﺒﻬﺎ ﹴ ﻞ ﺑﺸﻜ ﺑﺎﻟﻌﻤﻞ اﻟﻘﻴﺎم ﻟﺘﺴﻬﻴﻞ اﻷﻋﻠﻰ ﻧﺤﻮ اﻟﻜﺒﻞ ﺳﻠﻚ ﻋﺮوة أﻃﺮاف ﺑﺜﻨﻲ ﻗﻢ ﻣﺴﺒﻖ ﺑﺸﺮﻳﻂ اﻟﺴﻠﻚ أﻃﺮاف ﺑﺮﺑﻂ ﻗﻢ ﹰ ﻻ أو ﻟﻠﻮﺣﺪة اﻟﺪاﺧﻠﻲ اﻟﺴﻠﻚ أﻃﺮاف ﺗﻌﺮﻳﺔ ﺣﺎل ﻓﻲ ﻻﺻﻖ ﺧﻄﺎﻓﺎت ﻋ...

Page 13: ...ﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﺣﺮﻳﻖ ﻧﺸﻮب أو ﻛﻬﺮﺑﺎﺋﻴﺔ اﻟﻜﺘﻠﺔ ﻣﻦ إﻟﺦ اﻟﺘﺼﺮﻳﻒ ﲟﻀﺨﺔ اﳋﺎص اﻟﺘﻴﺎر ﺳﻠﻚ ﺗﻘﺴﻴﻢ إﻟﻰ ﺗﻌﻤﺪ ﻻ اﳌﻨﺘﺞ داﺧﻞ ﹰ ﺎ ﻣﺤﻠﻴ ﺷﺮاؤﻫﺎ ﰎ ﻛﻬﺮﺑﺎﺋﻴﺔ ﻗﻄﻊ اﺳﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﺣﺮﻳﻖ ﻧﺸﻮب أو ﻛﻬﺮﺑﺎﺋﻴﺔ ﺻﺪﻣﺔ ﺣﺪوث إﻟﻰ ﺑﺬﻟﻚ اﻟﻘﻴﺎم ﻳﺆدي ﻗﺪ اﻟﻄﺮﻓﻴﺔ ﺣﺮﻳﻖ ﻧﺸﻮب أو ﻛﻬﺮﺑﺎﺋﻴﺔ ﺻﺪﻣﺔ ﺣﺪوث إﻟﻰ ﺑﺬﻟﻚ اﻟﻘﻴﺎم ﻳﺆدي ﻗﺪ اﻟﺪاﺧﻠﻴﺔ ﺑﺎﻟﻮﺣﺪة اﻟﺘﻴﺎر ﺳﻠﻚ ﺗﻮﺻﻴﻞ إﻟﻰ ﺗﻌﻤﺪ ﻻ ﲢﺬﻳﺮ اﻟﺘﺼﺮﻳﻒ ﺧﺮﻃﻮم وﺿﻊ ﻛﻴﻔﻴﺔ اﻟﺘﺜﺒﻴﺖ ﺑﺮﻏﻲ ﺑﺸﺪ وﻗﻢ اﻟﺘﺼﺮﻳﻒ ﺧﺮﻃﻮم أدﺧﻞ ﻟﻠﻤﻴﺎه...

Page 14: ...ﺪ أﻧﻪ ﻣﻦ ﲢﻘﻖ 5 اﻟﺘﻮﺳﻌﺔ ﺟﺰء ﻋﻠﻰ ﻣﻌﺪﻧﻲ زﻳﺖ اﺳﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﻟﻠﻮﺣﺪات اﻟﺘﺸﻐﻴﻠﻲ اﻟﻌﻤﺮ ﺗﻘﻠﻴﻞ ﻓﻲ ذﻟﻚ ﻳﺘﺴﺒﺐ ﻓﻘﺪ اﻟﻨﻈﺎم إﻟﻰ اﳌﻌﺪﻧﻲ اﻟﺰﻳﺖ دﺧﻮل ﺗﻔﺎدى ﻓﻘﻂ اﻟﻮﺣﺪة ﻣﻊ اﳌﺮﻓﻘﺔ اﻟﻘﻄﻊ ﺑﺎﺳﺘﻌﻤﺎل ﻗﻢ ﺳﺎﺑﻘﺔ ﺗﺮﻛﻴﺐ ﻋﻤﻠﻴﺎت ﻓﻲ اﺳﺘﻌﻤﺎﻟﻬﺎ ﰎ أﻧﺎﺑﻴﺐ اﺳﺘﻌﻤﺎل إﻟﻰ ا ﹰ أﺑﺪ ﺗﻌﻤﺪ ﻻ ﻟﻠﻮﺣﺪة اﻟﺘﺸﻐﻴﻠﻲ اﻟﻌﻤﺮ ﻟﻀﻤﺎن وذﻟﻚ R32 ﺑﻐﺎز ﺗﻌﺒﺄ اﻟﺘﻲ اﻟﻮﺣﺪة ﻫﺬه ﻋﻠﻰ ﻣﺠﻔﻒ ﺗﺮﻛﻴﺐ إﻟﻰ ا ﹰ إﺑﺪ ﺗﻌﻤﺪ ﻻ وﺗﻠﻔﻪ اﻟﻨﻈﺎم ﺗﻔﻜﻴﻚ ﻋﻠﻰ اﻟﺘﺠﻔﻴﻒ ﻣﻮاد ﺗﻌﻤﻞ ﻗﺪ اﻟﺘﺒﺮﻳﺪ ﻏﺎز...

Page 15: ...ﺮور ﻣﻊ اﻷداء ﻟﺘﺪﻫﻮر ﻛﻨﺘﻴﺠﺔ اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ ﻓﻲ ﺗﺸﻘﻖ ﺣﺪوث ﻟﺘﻔﺎدي ﺎ ﹰ ﻣﻬﻤ ﻫﺬا ﻌﺪ ﹸ ﻳ اﻟﺘﻮﺳﻌﺔ ﺟﺰء ﻣﻦ ﻓﻘﻂ اﻟﺪاﺧﻠﻲ اﻟﺴﻄﺢ ﻋﻠﻰ اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ زﻳﺖ ﺑﻮﺿﻊ ﻗﻢ اﻟﻐﺎز ﺗﺴﺮﻳﺐ ﻟﺘﻔﺎدي R32 اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ زﻳﺖ اﺳﺘﻌﻤﻞ اﻟﻐﺎز ﺗﺴﺮب وﺗﻔﺎدي اﻟﺘﻮﺳﻌﺔ ﺻﻮاﻣﻴﻞ ﻓﻲ ﺗﻠﻒ ﺣﺪوث ﻟﺘﻔﺎدي اﻟﺘﻮﺳﻌﺔ ﺻﻮاﻣﻴﻞ ﺷﺪ ﻋﻨﺪ اﻟﻌﺰم ﻣﻔﺘﺎح اﺳﺘﻌﻤﻞ ﺗﻨﺒﻴﻪ اﳉﺪار ﻏﻄﺎء ﺗﻮﻓﺮ ﻋﺪم ﺣﺎل ﻓﻲ ﺑﺘﻐﻄﻴﺔ ﻗﻢ اﻟﺘﻮﺳﻌﺔ ﺑﺸﺮﻳﻂ اﻟﺘﻮﺳﻌﺔ ﻓﺘﺤﺔ أو اﻷوﺳﺎخ ﻣﻦ ﳊﻔﻈﻬﺎ اﳌﻴﺎه ﻋﻠﻰ اﺣﺮص ﻏﻄﺎء وﺿﻊ اﳌﻄﺮ...

Page 16: ...ﻳﺔ ﻓﺘﺤﺎت ﺣﺮﻛﺔ اﻟﺘﺸﻐﻴﻞ إﻳﻘﺎف ﺑﻌﺪ دﻗﺎﺋﻖ 3 ﳌﺪة اﻟﺘﺸﻐﻴﻞ إﻋﺎدة ﻋﻤﻠﻴﺔ ﺗﻌﻄﻴﻞ ﻋﻠﻰ اﻟﻨﻈﺎم ﻳﻌﻤﻞ وﻗﺎﺋﻲ ﻛﺈﺟﺮاء ﻳﺘﻢ ﻟﻦ اﳊﺎﻻت ﺑﻌﺾ ﻓﻲ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ اﻟﺪاﺋﺮة ﻗﺎﻃﻊ ﺗﺸﻐﻴﻞ ﺑﻌﺪ ﻣﺒﺎﺷﺮة اﻟﺘﺪﻓﺌﺔ اﻟﻮﺿﻊ ﻓﻲ اﻟﺘﺠﺮﻳﺒﻲ ﺑﺎﻟﺘﺸﻐﻴﻞ اﻟﻘﻴﺎم ﻋﻨﺪ اﻟﻬﻮاء ﻣﻜﻴﻒ ﳊﻤﺎﻳﺔ وذﻟﻚ ﺎ ﹰ ﺗﻘﺮﻳﺒ دﻗﺎﺋﻖ 10 ﳌﺪة اﻟﻬﻮاء ﺧﺮوج ﻓﻲ اﻟﺘﺸﻐﻴﻞ ﻋﻨﺪ م 28 إﻟﻰ م 26 ﻋﺎدي ﻣﺴﺘﻮى ﻋﻨﺪ اﳊﺮارة درﺟﺔ ﺑﻀﺒﻂ ﻗﻢ اﻟﺘﺠﺮﻳﺒﻲ اﻟﺘﺸﻐﻴﻞ إﲤﺎم ﺑﻌﺪ 4 1 اﻟﺘﺪﻓﺌﺔ اﻟﻮﺿﻊ ﻓﻲ اﻟﺘﺸﻐﻴﻞ ﻋﻨﺪ م 24 إﻟﻰ م 20...

Page 17: ...tions or wires Improper connections or securing of wires may result in abnormal heat build up or fire Install the air conditioner on a foundation strong enough to hold the weight of the unit A foundation of insufficient strength may result in the equipment falling and causing injury When installing or relocating the air conditioner do not let any other substances besides R32 such as air enter the re...

Page 18: ... be positioned in a place where 1 the restrictions on the installation requirements specified in the indoor unit installation drawings are met 2 both the air inlet and air outlet are unobstructed 3 the unit is not exposed to direct sunlight 4 the unit is away from sources of heat or steam 5 there is no source of machine oil vapour this may shorten the indoor unit service life 6 cool warm air is cir...

Page 19: ...wall make sure that control signals are properly received by indoor unit How to attach the indoor unit Hook the tabs of the bottom frame to the mounting plate If the tabs are difficult to hook remove the front grille How to remove the indoor unit Push up the marked area at the lower part of the front grille to release the tabs If it is difficult to release remove the front grille Front grille A Moun...

Page 20: ...the indoor unit as a guide 4 Open the front panel then open the service lid Refer to Installation Tips 5 Pass the inter unit wire from the outdoor unit through the feed through wall hole and then through the back of the indoor unit Pull them through the front side Bend the ends of cable tie wires upward for easier work in advance If the inter unit wire ends are to be stripped first bundle the wire ...

Page 21: ...t use tapped wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Do not connect the power wire to the indoor unit Doing so may cause electric shock or fire WARNING How to set ...

Page 22: ... nut on the pipe 4 Flare the pipe 5 Check that the flaring is properly made Do not use mineral oil on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a drier to this R32 unit in order to guarantee it s lifetime The ...

Page 23: ...t fixed to the main unit This is to prevent cracking of the flare nut as a result of deterioration over time To prevent gas leakage apply refrigeration oil only to the inner surface of the flare Use refrigeration oil for R32 Use a torque wrench when tightening the flare nuts to prevent damage to the flare nuts and gas leakage CAUTION Wall If no flare cap is available cover the flare mouth with tape to ke...

Page 24: ...ation in accordance with the operation manual to ensure that all functions and parts such as louvres movement are working properly For protection the system disables restart operation for 3 minutes after it is turned off When trial operation is conducted in the HEAT operation directly after the circuit breaker is turned on in some cases no air will be output for about 10 minutes in order to protec...

Page 25: ...ﻏﻴﺮ ﺗﺰاﻳﺪ ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ اﻷﺳﻼك ﺗﺜﺒﻴﺖ أو اﳋﺎﻃﺌﺔ اﻟﺘﻮﺻﻴﻼت اﻟﻮﺣﺪة وزن ﻞ ﹼ ﻟﺘﺤﻤ ﻛﺎﻓﻲ ﺑﺸﻜﻞ ﻗﻮﻳﺔ ﻗﺎﻋﺪة ﻋﻠﻰ اﻟﻬﻮاء ﻣﻜﻴﻒ ﺑﺘﺮﻛﻴﺐ ﻗﻢ إﺻﺎﺑﺔ ﺑﺤﺪوث واﻟﺘﺴﺒﺐ اﳌﻌﺪات ﺳﻘﻮط ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ ﹴ ﻛﺎف ﹴ ﻞ ﺑﺸﻜ ﻗﻮﻳﺔ ﻏﻴﺮ ﻗﺎﻋﺪة ﺑﺘﺮﻛﻴﺐ اﻟﻘﻴﺎم ﻋﻨﺪ اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ داﺋﺮة إﻟﻰ ﺑﺎﻟﺪﺧﻮل اﻟﻬﻮاء ﻣﺜﻞ R32 ﻏﺎز ﺟﺎﻧﺐ إﻟﻰ أﺧﺮى ﻣﻮاد أﻳﺔ ﺗﺪع ﻻ اﻟﺘﺮﻛﻴﺐ ﻣﻮﻗﻊ ﺗﻐﻴﻴﺮ إﻋﺎدة أو اﻟﻬﻮاء ﻣﻜﻴﻒ ﺗﺮﻛﻴﺐ ﻋﻨﺪ ﺑﺠﺮوح اﻹﺻﺎﺑﺔ إﻟﻰ وﺣﺘﻰ اﳌﻌﺪات ﺗﻠﻒ إﻟﻰ ﺑﺪوره ﻳﺆدي ﻗﺪ واﻟﺬي ﻃ...

Page 26: ...ﻛﻴﺐ ﻣﺘﻄﻠﺒﺎت ﻋﻠﻰ اﳌﻔﺮوﺿﺔ اﻟﻘﻴﻮد ﻳﺴﺘﻮﻓﻲ 1 اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﺗﺮﻛﻴﺐ ﻣﺨﻄﻄﺎت اﻟﻬﻮاء وﻣﺨﺮج اﻟﻬﻮاء ﻣﺪﺧﻞ ﻣﻦ ﹴ ﻞ ﻛ ﻓﻲ ﻋﻮاﺋﻖ ﺗﻮﺟﺪ ﻻ 2 اﳌﺒﺎﺷﺮة اﻟﺸﻤﺲ ﻷﺷﻌﺔ ﻣﻌﺮﺿﺔ اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن ﻻ 3 اﻟﺒﺨﺎر أو اﳊﺮارة ﻣﺼﺎدر ﻋﻦ ﺑﻌﻴﺪة اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن 4 اﻟﻌﻤﺮ ﺗﻘﻠﻴﻞ إﻟﻰ ﻫﺬا ﻳﺆدي أن ﳝﻜﻦ اﻵﻟﺔ زﻳﺖ ﺑﺨﺎر ﻓﻴﻪ ﻳﻮﺟﺪ ﻻ 5 اﻟﺪاﺧﻠﻴﺔ ﻟﻠﻮﺣﺪة اﻟﺘﺸﻐﻴﻠﻲ اﻟﻐﺮﻓﺔ ﻋﺒﺮ اﻟﺪاﻓﺊ اﻟﺒﺎرد اﻟﻬﻮاء ﺗﺪوﻳﺮ ﻓﻴﻪ ﻳﺘﻢ 6 اﳌﺼﺎﺑﻴﺢ أﻧﻮاع ﻣﻦ ﻧﻮع أي ﻋﻦ ﺑﻌﻴﺪة اﻟﻮﺣﺪة ﻓﻴﻪ ﺗﻜﻮن ﻣﻜﺎ...

Page 27: ... وﺣﺪة ﺣﺎﻣﻞ ﺗﺜﺒﻴﺖ ﺑﺮاﻏﻲ ﻣﻘﺎس ﺑﻌﺪ ﻋﻦ اﻟﺘﺤﻜﻢ ﻗﻄﻌﺔ 2 20L M3 F ﻋﻦ اﻟﺘﺤﻜﻢ وﺣﺪة اﻟﻼﺳﻠﻜﻴﺔ ﺑﻌﺪ D اﻟﺘﺤﻜﻢ وﺣﺪة ﺣﺎﻣﻞ ﺑﻌﺪ ﻋﻦ E اﻟﻬﻮاء ﻣﺮﺷﺤﺎت اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ ﻣﺜﺒﺖ ﲡﻮﻳﻒ داﺧﻞ اﻷداة ﺑﺈدﺧﺎل ﻗﻢ 1 اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ ﻣﺜﺒﺖ ﻧﺰع ﻛﻴﻔﻴﺔ اﻟﺴﻬﻢ ﺑﺎﲡﺎه 90 اﻷداة ﺑﺘﺪوﻳﺮ ﻗﻢ 2 اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ ﻣﺜﺒﺖ اﻧﺰع 3 اﻟﺪاﺧﻠﻴﺔ ﻟﻠﻮﺣﺪة اﻟﺴﻔﻠﻲ اﳉﺰء اﻷﻣﺎﻣﻴﺔ اﻟﺸﺒﻜﺔ ﻣﺜﺒﺖ اﻟﺘﻴﺘﺎﻧﻴﻮم أﺑﺎﺗﻴﺖ ﻣﺎدة ﻣﻦ اﳌﺼﻨﻮع اﻟﻬﻮاء ﺗﻨﻘﻴﺔ ﻣﺮﺷﺢ ﻗﻄﻊ 3 اﻟﻀﻮﺋﻲ ﺑﺎﻟﺘﺤﻔﻴﺰ ﻳﻌﻤﻞ واﻟﺬي C ...

Page 28: ...ﺪة ﻣﻦ اﻟﻌﻠﻮي اﳉﺰء ﻋﻠﻰ اﳌﻮﺟﻮدة اﻟﺼﻴﺎﻧﺔ ﻏﻄﺎء اﻓﺘﺢ ﺛﻢ وﻣﻦ اﻷﻣﺎﻣﻴﺔ اﻟﻠﻮﺣﺔ اﻓﺘﺢ 4 اﻟﺘﺮﻛﻴﺐ ﺣﻮل ﺗﻮﺟﻴﻬﺎت راﺟﻊ ﺧﻼﻟﻪ ﻣﻦ ﻳﺘﻢ ﺛﻘﺐ ﻋﺒﺮ اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة ﻣﻦ ﻟﻠﻮﺣﺪة اﻟﺪاﺧﻠﻲ اﻟﺴﻠﻚ ﺑﺘﻤﺮﻳﺮ ﻗﻢ 5 اﻟﺪاﺧﻠﻴﺔ اﻟﻮﺣﺪة ﻣﻦ اﳋﻠﻔﻴﺔ اﳉﻬﺔ ﺧﻼل ﻣﻦ ﺛﻢ وﻣﻦ اﻟﺘﻠﻘﻴﻢ اﻷﻣﺎﻣﻲ اﳉﺎﻧﺐ ﺧﻼل ﻣﻦ اﺳﺤﺒﻬﺎ ﹴ ﻞ ﺑﺸﻜ ﺑﺎﻟﻌﻤﻞ اﻟﻘﻴﺎم ﻟﺘﺴﻬﻴﻞ اﻷﻋﻠﻰ ﻧﺤﻮ اﻟﻜﺒﻞ ﺳﻠﻚ ﻋﺮوة أﻃﺮاف ﺑﺜﻨﻲ ﻗﻢ ﻣﺴﺒﻖ ﺑﺸﺮﻳﻂ اﻟﺴﻠﻚ أﻃﺮاف ﺑﺮﺑﻂ ﻗﻢ ﹰ ﻻ أو ﻟﻠﻮﺣﺪة اﻟﺪاﺧﻠﻲ اﻟﺴﻠﻚ أﻃﺮاف ﺗﻌﺮﻳﺔ ﺣﺎل ﻓﻲ ﻻ...

Page 29: ...ﺑﺘﻌﺮﻳﺔ ﻗﻢ 1 اﻟﻜﺘﻞ ﻋﻠﻰ اﳌﻮﺟﻮدة اﻟﺘﻮﺻﻴﻞ أﻃﺮاف أرﻗﺎم ﻣﻊ اﻟﺴﻠﻚ أﻟﻮان ﲟﻄﺎﺑﻘﺔ ﻗﻢ 2 أﻃﺮاف ﻓﻲ اﻷﺳﻼك ﺗﺜﺒﻴﺖ وإﺣﻜﺎم واﳋﺎرﺟﻴﺔ اﻟﺪاﺧﻠﻴﺔ ﻟﻠﻮﺣﺪات اﻟﻄﺮﻓﻴﺔ ﻟﻠﺒﺮاﻏﻲ اﳌﻄﺎﺑﻘﺔ اﻟﺘﻮﺻﻴﻞ ﻟﻬﺎ اﳌﻄﺎﺑﻘﺔ اﻟﺘﻮﺻﻴﻞ ﺑﺄﻃﺮاف ﺗﺄرﻳﺾ أﺳﻼك ﺑﺘﻮﺻﻴﻞ ﻗﻢ 3 ﻓﻲ ﺑﺘﺜﺒﻴﺘﻬﺎ ﻗﻢ ﺛﻢ وﻣﻦ ﺑﺈﺣﻜﺎم ﺗﻮﺻﻴﻠﻬﺎ ﻣﻦ ﻟﻠﺘﺄﻛﺪ ﺑﺨﻔﺔ اﻷﺳﻼك اﺳﺤﺐ 4 اﻷﺳﻼك ﺣﺎﻓﻈﺔ وﺗﺜﺒﻴﺖ ﺑﻌﺪ ﻋﻦ اﻟﺘﺤﻜﻢ وﺣﺪة ﻛﺒﻞ ﺑﻮﺿﻊ ﻗﻢ ﻣﺤﻮل ﺑﻨﻈﺎم ﺗﻮﺻﻴﻠﻪ ﰎ ﺣﺎل ﻓﻲ 5 S21 اﳌﻮﺻﻞ HA ﺑﻨﻈﺎم ﺗﻮﺻﻴﻠﻪ ﻋﻨﺪ 5 راﺟﻊ ﻗﻢ ﺛﻢ ...

Page 30: ...اﻟﺘﻮﺳﻌﺔ ﲤﺖ ﻗﺪ أﻧﻪ ﻣﻦ ﲢﻘﻖ 5 اﻟﺘﻮﺳﻌﺔ ﺟﺰء ﻋﻠﻰ ﻣﻌﺪﻧﻲ زﻳﺖ اﺳﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﻟﻠﻮﺣﺪات اﻟﺘﺸﻐﻴﻠﻲ اﻟﻌﻤﺮ ﺗﻘﻠﻴﻞ ﻓﻲ ذﻟﻚ ﻳﺘﺴﺒﺐ ﻓﻘﺪ اﻟﻨﻈﺎم إﻟﻰ اﳌﻌﺪﻧﻲ اﻟﺰﻳﺖ دﺧﻮل ﺗﻔﺎدى ﻓﻘﻂ اﻟﻮﺣﺪة ﻣﻊ اﳌﺮﻓﻘﺔ اﻟﻘﻄﻊ ﺑﺎﺳﺘﻌﻤﺎل ﻗﻢ ﺳﺎﺑﻘﺔ ﺗﺮﻛﻴﺐ ﻋﻤﻠﻴﺎت ﻓﻲ اﺳﺘﻌﻤﺎﻟﻬﺎ ﰎ أﻧﺎﺑﻴﺐ اﺳﺘﻌﻤﺎل إﻟﻰ ا ﹰ أﺑﺪ ﺗﻌﻤﺪ ﻻ ﻟﻠﻮﺣﺪة اﻟﺘﺸﻐﻴﻠﻲ اﻟﻌﻤﺮ ﻟﻀﻤﺎن وذﻟﻚ R32 ﺑﻐﺎز ﺗﻌﺒﺄ اﻟﺘﻲ اﻟﻮﺣﺪة ﻫﺬه ﻋﻠﻰ ﻣﺠﻔﻒ ﺗﺮﻛﻴﺐ إﻟﻰ ا ﹰ إﺑﺪ ﺗﻌﻤﺪ ﻻ وﺗﻠﻔﻪ اﻟﻨﻈﺎم ﺗﻔﻜﻴﻚ ﻋﻠﻰ اﻟﺘﺠﻔﻴﻒ ﻣﻮاد ﺗﻌﻤﻞ ﻗﺪ...

Page 31: ... إﻟﻰ 0 035 ﻣﻦ أﻗﺼﻰ ﻛﺤﺪ م 110 إﻟﻰ اﻟﺘﺒﺮﻳﺪ ﻏﺎز أﻧﺒﻮب ﺳﻄﺢ ﺣﺮارة درﺟﺔ ﺗﺼﻞ ﻫﺬه اﳊﺮارة درﺟﺔ ﺗﺘﺤﻤﻞ ﺣﺮارﻳﺔ ﻋﺰل ﻣﻮاد ﺑﺎﺧﺘﻴﺎر ﻗﻢ اﻟﻌﺰل أﺑﻌﺎد ﺗﻨﻔﻴﺬ ﻓﻲ ﺑﺎﻟﺘﻘﻴﺪ وﻗﻢ واﻟﺴﺎﺋﻞ اﻟﻐﺎز أﻧﺎﺑﻴﺐ ﻣﻦ ﹴ ﻞ ﻛ ﻋﺰل ﻋﻠﻰ اﺣﺮص 2 أدﻧﺎه ﻣﻮﺿﺢ ﻫﻮ ﻛﻤﺎ اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ ﻟﺸﺪ اﻟﻌﺰم ﻣﻔﺘﺎح اﻟﺴﺎﺋﻞ ﺟﺎﻧﺐ اﻟﻐﺎز ﺟﺎﻧﺐ م ن 17 2 14 2 ﺳﻢ ق ﻛﺠﻢ 175 144 م ن 75 4 61 8 ﺳﻢ ق ﻛﺠﻢ 770 630 ﱈ 6 4 ﱈ 15 9 اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ اﻟﻌﺰم ﻣﻔﺘﺎح اﻷﻧﺎﺑﻴﺐ ﲤﺪﻳﺪ وﺣﺪة رﺑﻂ ﻣﻔﺘﺎح ﺑ...

Page 32: ...ﺘﺸﻐﻴﻞ ﺳﻴﺘﻮﻗﻒ اﺿﻐﻂ اﻟﺘﺸﻐﻴﻞ ﻹﻳﻘﺎف اﻟﺘﺠﺮﻳﺒﻲ اﻟﺘﺸﻐﻴﻞ وﺿﻊ ﻓﻲ اﻟﻮﻇﺎﺋﻒ ﺑﻌﺾ اﺳﺘﻌﻤﺎل ﻳﺘﻌﺬر اﻟﺘﺮﻛﻴﺐ ﺑﻌﺪ اﻟﻮﻗﺖ ﻣﻦ ﻟﻔﺘﺮة اﻟﻨﻈﺎم اﺳﺘﻌﻤﺎل ﻋﺪم ﺣﺎل ﻓﻲ اﻻﺳﺘﻌﺪاد وﺿﻊ ﻓﻲ ﺣﺘﻰ اﻟﻜﻬﺮﺑﺎء ﻣﻦ ﹰ ﻼ ﺿﺌﻴ ا ﹰ ﻣﻘﺪار ﺎ ﹰ داﺋﻤ اﻟﻬﻮاء ﻣﻜﻴﻒ ﻳﺴﺘﻬﻠﻚ اﻟﻀﺮوري ﻏﻴﺮ اﻟﺘﻴﺎر اﺳﺘﻬﻼك ﻣﻦ ﻟﻠﺤﺪ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ اﻟﺪاﺋﺮة ﻗﺎﻃﻊ ﺑﺈﻳﻘﺎف ﻗﻢ ﻗﺎﻃﻊ ﺗﺸﻐﻴﻞ ﻋﻨﺪ اﻷﺻﻠﻲ اﻟﺘﺸﻐﻴﻞ وﺿﻊ اﺳﺘﻌﺎدة ﻋﻠﻰ اﻟﻨﻈﺎم ﺳﻴﻌﻤﻞ اﻟﻬﻮاء ﻣﻜﻴﻒ ﻋﻦ اﻟﺘﻴﺎر إﻳﻘﺎف ﻋﻦ اﻟﻜﻬﺮﺑﺎﺋﻴﺔ اﻟﺪاﺋﺮة ﻗﺎﻃﻊ اﻣﺘﻨﻊ ...

Page 33: ...s during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check for refrigerant gas leakage Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker Be sure to earth the air conditioner Do not earth the unit t...

Page 34: ...oor unit When operating the air conditioner in a low outdoor ambient temperature be sure to follow the instructions described below To prevent exposure to wind install the outdoor unit with its suction side facing the wall Never install the outdoor unit at a site where the suction side may be exposed directly to wind To prevent exposure to wind it is recommended to install a baffle plate on the air...

Page 35: ...danger of the unit falling use foot bolts or wires In sites with poor drainage use block bases for the outdoor unit Adjust foot height until the unit is level Otherwise water leakage or pooling of water may occur Max allowable piping height Max allowable piping length 30m 20m Min allowable piping length 1 5m Liquid pipe Gas pipe O D 6 4mm O D 12 7mm O D 15 9mm 20g m Additional refrigerant required...

Page 36: ...the flare nuts 3 or 4 turns by hand Then tighten them fully with a spanner and a torque wrench Refrigerant oil for R410A can also be used for application to the inner flare CAUTION Do not apply refrigeration oil to the outer surface Flare nut Apply refrigeration oil to the inner surface of the flare Do not apply refrigeration oil to the flare nut to avoid tightening with excessive torque Apply oil Ser...

Page 37: ...uum pump adapter 1 Connect projection side of charging hose which comes from gauge manifold to gas stop valve s service port 2 Fully open gauge manifold s low pressure valve Lo and completely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Perform vacuum pumping and make sure that the compound pressure gauge reads 0 1MPa 76cmHg 1 4 Close gauge manifold s l...

Page 38: ...the partition plate in Wiring 2 Do not use tapped wires extension cords or starburst connections as they may cause overheating electrical shock or fire Do not use locally purchased electrical parts inside the product Do not branch the power for the drain pump etc from the terminal block Doing so may cause electric shock or fire Be sure to install an earth leak detector One that can handle higher har...

Page 39: ...ong Good Wrong Arrow view A Screw Round crimp style terminal Flat washer Screw Round crimp style terminal Flat washer A Flat washer Screw Round crimp style terminal Good Wrong Strip wire end to this point Excessive strip length may cause electrical shock or leakage How to attach the partition plate 1 Insert the protrusion of the partition plate into the notch in the metal sheet 2 Slide the partiti...

Page 40: ...o 24 C in HEAT operation When operating the air conditioner in COOL operation in winter or HEAT operation in summer set it to the trial operation mode See the installation manual for the indoor unit The air conditioner draws a small amount of power in its standby mode If the system is not to be used for some time after installation shut off the circuit breaker to eliminate unnecessary power consum...

Page 41: ...ﻏﻴﺮ ﺗﺰاﻳﺪ ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ اﻷﺳﻼك ﺗﺜﺒﻴﺖ أو اﳋﺎﻃﺌﺔ اﻟﺘﻮﺻﻴﻼت اﻟﻮﺣﺪة وزن ﻞ ﹼ ﻟﺘﺤﻤ ﻛﺎﻓﻲ ﺑﺸﻜﻞ ﻗﻮﻳﺔ ﻗﺎﻋﺪة ﻋﻠﻰ اﻟﻬﻮاء ﻣﻜﻴﻒ ﺑﺘﺮﻛﻴﺐ ﻗﻢ إﺻﺎﺑﺔ ﺑﺤﺪوث واﻟﺘﺴﺒﺐ اﳌﻌﺪات ﺳﻘﻮط ﻋﻨﻬﺎ ﻳﻨﺘﺞ ﻗﺪ ﹴ ﻛﺎف ﹴ ﻞ ﺑﺸﻜ ﻗﻮﻳﺔ ﻏﻴﺮ ﻗﺎﻋﺪة ﺑﺘﺮﻛﻴﺐ اﻟﻘﻴﺎم ﻋﻨﺪ اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ داﺋﺮة إﻟﻰ ﺑﺎﻟﺪﺧﻮل اﻟﻬﻮاء ﻣﺜﻞ R32 ﻏﺎز ﺟﺎﻧﺐ إﻟﻰ أﺧﺮى ﻣﻮاد أﻳﺔ ﺗﺪع ﻻ اﻟﺘﺮﻛﻴﺐ ﻣﻮﻗﻊ ﺗﻐﻴﻴﺮ إﻋﺎدة أو اﻟﻬﻮاء ﻣﻜﻴﻒ ﺗﺮﻛﻴﺐ ﻋﻨﺪ ﺑﺠﺮوح اﻹﺻﺎﺑﺔ إﻟﻰ وﺣﺘﻰ اﳌﻌﺪات ﺗﻠﻒ إﻟﻰ ﺑﺪوره ﻳﺆدي ﻗﺪ واﻟﺬي ﻃ...

Page 42: ...ﺸﻐﻴﻞ ﻋﻨﺪ أدﻧﺎه اﳌﺬﻛﻮرة اﻟﺘﻌﻠﻴﻤﺎت ﺟﺎﻧﺐ ﻳﻜﻮن ﺑﺤﻴﺚ اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة ﺑﺘﺮﻛﻴﺐ ﻗﻢ ﻟﻠﺮﻳﺎح اﻟﺘﻌﺮض ﻣﻦ ﳊﻤﺎﻳﺘﻪ اﳉﺪار ﻧﺤﻮ ﺎ ﹰ ﻣﺘﺠﻬ اﻟﺸﻔﻂ ﺟﺎﻧﺐ ﻓﻴﻪ ﻳﺘﻌﺮض ﻗﺪ ﻣﺎ ﻣﻮﻗﻊ ﻓﻲ اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة ﺗﺮﻛﻴﺐ إﻟﻰ ا ﹰ أﺑﺪ ﺗﻌﻤﺪ ﻻ ﻣﺒﺎﺷﺮ ﹴ ﻞ ﺑﺸﻜ اﻟﺮﻳﺎح ﺗﺄﺛﻴﺮ إﻟﻰ اﻟﺸﻔﻂ اﳋﺎص اﳉﺎﻧﺐ ﻋﻠﻰ اﻋﺘﺮاﺿﻴﺔ ﻟﻮﺣﺔ ﺑﺘﺮﻛﻴﺐ ﻳﻮﺻﻰ ﻟﻠﺮﻳﺎح اﻟﺘﻌﺮض ﻣﻦ ﳊﻤﺎﻳﺘﻪ اﳋﺎرﺟﻴﺔ ﻟﻠﻮﺣﺪة اﻟﻬﻮاﺋﻲ ﺑﺎﻟﺘﻔﺮﻳﻎ ﻣﻮﻗﻊ ﺑﺎﺧﺘﻴﺎر ﻗﻢ ﻟﻠﺜﻠﻮج ﻛﺜﻴﻒ ﺗﺴﺎﻗﻂ ﻓﻴﻬﺎ ﻳﻮﺟﺪ اﻟﺘﻲ اﳌﻨﺎﻃﻖ ﻓﻲ اﻟﻮﺣﺪة ﻋﻠﻰ اﻟﺜﻠﺞ...

Page 43: ...ﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ ﺗﻌﺒﺌﺔ إﺟﻤﺎﻟﻲ 3 اﳋﺎرﺟﻴﺔ اﻟﻮﺣﺪة 4 اﳋﺎص واﳌﺸﻌﺐ اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ اﺳﻄﻮاﻧﺔ 5 ﺑﺎﻟﺘﻌﺒﺌﺔ ﱈ 376 ﻲ ﻏ ﺮ ﺑ ﺐ ﻘ ﺛ ﺰ ﻛ ا ﺮ ﻣ ة ﺪ ﻋ ﺎ ﻘ ﻟ ا ﺪة ﺎﻋ ﻟﻘ ا ﻏﻲ ﺑﺮ ﺐ ﺛﻘ ﻛﺰ ﻣﺮا ﺪة ﻮﺣ اﻟ ﺐ ﺟﺎﻧ ﻣﻦ ﱈ 175 ﱈ 610 ﻛﺘﻞ ﻗﻮاﻋﺪ ﺑﺎﺳﺘﻌﻤﺎل ﻗﻢ ﻟﻠﺘﺼﺮﻳﻒ ﺗﻔﺘﻘﺮ ﻣﻮاﻗﻊ ﻓﻲ اﳋﺎرﺟﻴﺔ ﻟﻠﻮﺣﺪة ﻣﺴﺘﻮﻳﺔ اﻟﻮﺣﺪة ﺗﺼﺒﺢ ﺣﺘﻰ اﻟﻘﺎﻋﺪة ارﺗﻔﺎع اﺿﺒﻂ اﳌﺎء ﻳﻨﺴﻜﺐ أو اﳌﺎء ﻳﺘﺴﺮب ﻓﻘﺪ وإﻻ اﻟﻮﺣﺪة ﻟﺴﻘﻮط ﻧﺘﻴﺠﺔ ﻣﺤﺘﻤﻞ ﺧﻄﺮ وﺟﻮد ﺣﺎل ﻓﻲ أﺳﻼك أو اﻟﻘﺎﻋﺪة ﺑﺮاﻏﻲ ﺑﺎﺳﺘﻌﻤﺎل ﻗﻢ...

Page 44: ...ﻢ ق ﻛﺠﻢ 610 490 م ن 27 4 21 6 ﺳﻢ ق ﻛﺠﻢ 280 220 اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ ﻟﺸﺪ اﻟﻌﺰم ﻣﻔﺘﺎح اﻟﻐﺎز ﺟﺎﻧﺐ اﻟﺴﺎﺋﻞ ﺟﺎﻧﺐ ﱈ 12 7 ﱈ 6 4 م ن 60 3 49 5 ﺳﻢ ق ﻛﺠﻢ 615 505 ﱈ 15 9 م ن 75 4 61 8 ﺳﻢ ق ﻛﺠﻢ 770 630 م ن 17 2 14 2 ﺳﻢ ق ﻛﺠﻢ 175 144 اﻟﻮﻗﺖ ﻣﺮور ﻣﻊ اﻷداء ﻟﺘﺪﻫﻮر ﻧﺘﻴﺠﺔ وذﻟﻚ اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ ﻓﻲ ﺗﺸﻘﻖ ﺣﺪوث ﻟﺘﻔﺎدي ﻫﺬا ﻳﺘﻢ اﻟﺮﺋﻴﺴﻴﺔ ﺑﺎﻟﻮﺣﺪة اﳌﺜﺒﺘﺔ اﻟﺘﻮﺳﻌﺔ ﺻﺎﻣﻮﻟﺔ اﺳﺘﻌﻤﻞ R32 اﻟﺘﺒﺮﻳﺪ ﺳﺎﺋﻞ زﻳﺖ اﺳﺘﻌﻤﻞ اﻟﺘﻮﺳﻌﺔ ﺟﺰء ﻣﻦ ﻓﻘﻂ اﻟﺪاﺧﻠﻲ اﻟﺴﻄ...

Page 45: ...ﻨﻔﺬ اﳌﺘﺸﻌﺐ اﳌﻘﻴﺎس ﻣﻦ ﻳﺄﺗﻲ واﻟﺬي اﻟﺘﻌﺒﺌﺔ ﺧﺮﻃﻮم ﻣﻦ اﻟﺒﺎرز اﳉﺎﻧﺐ ﺑﺘﻮﺻﻴﻞ ﻗﻢ 1 ﻛﺎﻣﻞ ﹴ ﻞ ﺑﺸﻜ ﺑﻪ اﳋﺎص Hi اﳌﺮﺗﻔﻊ اﻟﻀﻐﻂ ﺻﻤﺎم ﺑﺈﻏﻼق وﻗﻢ Lo اﳌﺘﺸﻌﺐ ﺑﺎﳌﻘﻴﺎس اﳋﺎص اﳌﻨﺨﻔﺾ اﻟﻀﻐﻂ ﺻﻤﺎم اﻓﺘﺢ 2 ﻟﺬﻟﻚ ﺎ ﹰ ﺗﺒﻌ ﻋﻤﻠﻴﺔ ﺑـﺄﻳﺔ اﻟﻘﻴﺎم اﳌﺮﺗﻔﻊ اﻟﻀﻐﻂ ﺻﻤﺎم ﻳﺘﻄﻠﺐ ﻻ 1 زﺋﺒﻖ ﺳﻢ 76 ﺑﺎﺳﻜﺎل ﻣﻴﻐﺎ 0 1 إﻟﻰ ﺗﺸﻴﺮ اﳌﺮﻛﺐ اﻟﻀﻐﻂ ﻣﻘﻴﺎس ﻗﺮاءات أن ﻣﻦ وﺗﺄﻛﺪ اﻟﺘﻔﺮﻳﻎ ﻣﻀﺨﺔ ﺗﺸﻐﻴﻞ ﺑﺈﺟﺮاء ﻗﻢ 3 اﻟﺘﻔﺮﻳﻎ ﻣﻀﺨﺔ ﺑﺈﻳﻘﺎف وﻗﻢ Lo اﳌﺘﺸﻌﺐ ﺑﺎﳌﻘﻴﺎس اﳋﺎص اﳌﻨﺨﻔﺾ اﻟﻀﻐﻂ ﺻﻤ...

Page 46: ...و ﻣﺘﻔﺮﻋﺔ أﺳﻼك اﺳﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﺣﺮﻳﻖ ﻧﺸﻮب أو ﻛﻬﺮﺑﺎﺋﻴﺔ ﺻﺪﻣﺔ إﻟﺦ اﻟﺘﺼﺮﻳﻒ ﲟﻀﺨﺔ اﳋﺎص اﻟﺘﻴﺎر ﺳﻠﻚ ﺗﻘﺴﻴﻢ إﻟﻰ ﺗﻌﻤﺪ ﻻ اﳌﻨﺘﺞ داﺧﻞ ﹰ ﺎ ﻣﺤﻠﻴ ﺷﺮاؤﻫﺎ ﰎ ﻛﻬﺮﺑﺎﺋﻴﺔ ﻗﻄﻊ اﺳﺘﻌﻤﺎل إﻟﻰ ﺗﻌﻤﺪ ﻻ ﺣﺮﻳﻖ ﻧﺸﻮب أو ﻛﻬﺮﺑﺎﺋﻴﺔ ﺻﺪﻣﺔ ﺣﺪوث إﻟﻰ ﺑﺬﻟﻚ اﻟﻘﻴﺎم ﻳﺆدي ﻗﺪ اﻟﻄﺮﻓﻴﺔ اﻟﻜﺘﻠﺔ ﻣﻦ اﻟﻌﺎﻟﻴﺔ اﻟﺬﺑﺬﺑﺎت ﲢﻤﻞ ﻟﻪ ﳝﻜﻦ اﻷرﺿﻲ اﻟﺘﺴﺮب ﻛﺎﺷﻒ ﺗﺮﻛﻴﺐ ﻋﻠﻰ اﺣﺮص ﺣﺪوث ﻟﺘﻔﺎدي وذﻟﻚ اﻟﺬﺑﺬﺑﺎت ﻣﻊ اﻟﺘﻌﺎﻣﻞ ﻋﻠﻰ ﻗﺎدر أرﺿﻲ ﺗﺴﺮب ﻛﺎﺷﻒ اﺳﺘﻌﻤﺎل وﺟﻮب ﻳﻌﻨﻲ وﻫﺬا ﻋﺎﻛﺲ اﻟﻮﺣﺪ...

Page 47: ...اﻷﻋﻠﻰ ﺑﺎﲡﺎه اﻷﺳﻼك ﻋﻠﻰ اﳌﺴﺘﺪﻳﺮ اﻟﻨﻮع اﳌﻜﺎن ﻓﻲ ﺗﺜﺒﻴﺘﻪ ﺑﺈﺣﻜﺎم وﻗﻢ ﺗﻨﺒﻴﻪ داﺋﺮي ﺑﺸﻜﻞ ﻣﺜﻨﻲ ﺗﻮﺻﻴﻞ ﻃﺮف ﺗﺮﻛﻴﺐ ﻋﻨﺪ اﻟﺘﺎﻟﻴﺔ اﻟﻄﺮﻳﻘﺔ اﺳﺘﻌﻤﻞ اﻟﻘﻴﺎم اﻟﺴﻠﻚ ﻃﺮف ﺑﻠﻒ اﻟﻘﻴﺎم ﻣﻦ ﺗﺄﻛﺪ ﻣﻔﺮد ﻟﺐ ذو ﺳﻠﻚ ﺑﺎﺳﺘﻌﻤﺎل اﻟﻄﺮﻓﻴﺔ ﺑﺎﻟﻜﺘﻠﺔ ﻟﻠﻮﺣﺪة اﻟﺪاﺧﻠﻲ اﻟﺴﻠﻚ ﺗﻮﺻﻴﻞ ﻋﻨﺪ ﺣﺮﻳﻖ وﻧﺸﻮب ﺗﺴﺨﲔ ﺣﺪوث إﻟﻰ ﻳﺆدي ﻗﺪ ﺻﺤﻴﺢ ﻏﻴﺮ ﺑﺸﻜﻞ ﺑﺎﻟﻌﻤﻞ 1 اﻟﺸﻜﻞ 1 2 3 2 اﻟﺸﻜﻞ اﻟﺘﻘﺴﻴﻢ ﻟﻮﺣﺔ اﻟﺒﺮاﻏﻲ اﻟﺼﻴﺎﻧﺔ ﻏﻄﺎء اﻟﺒﺮاﻏﻲ اﻷﺳﻼك ﺣﺎﻓﻈﺔ ﺗﻌﺮﻳﺔ إﻟﻰ ﺗﻌﻤﺪ ﻻ إﻟﻰ ﺑﺎﻟﻜﺎﻣﻞ اﻟﻐﻄﺎء...

Page 48: ...ﻗﻢ 1 1 اﻟﺘﺪﻓﺌﺔ اﻟﻮﺿﻊ ﻓﻲ اﻟﺘﺸﻐﻴﻞ وﻋﻨﺪ ﻟﻠﺒﺮﻣﺠﺔ ﻗﺎﺑﻠﺔ ﺣﺮارة درﺟﺔ أﻗﻞ ﺑﺎﺧﺘﻴﺎر ﻗﻢ اﻟﺘﺒﺮﻳﺪ اﻟﻮﺿﻊ ﻓﻲ اﻟﺘﺸﻐﻴﻞ ﻋﻨﺪ 2 1 ﻟﻠﺒﺮﻣﺠﺔ ﻗﺎﺑﻠﺔ ﺣﺮارة درﺟﺔ أﻋﻠﻰ ﺑﺎﺧﺘﻴﺎر ﻗﻢ ﺣﺮﻛﺔ ﻣﺜﻞ ﺻﺤﻴﺢ ﹴ ﻮ ﻧﺤ ﻋﻠﻰ واﻟﻘﻄﻊ اﻟﻮﻇﺎﺋﻒ ﺟﻤﻴﻊ ﻋﻤﻞ ﻟﻀﻤﺎن اﻟﺘﺸﻐﻴﻞ ﻟﺪﻟﻴﻞ ﺎ ﹰ ﻘ وﻓ اﻟﺘﺠﺮﻳﺒﻲ ﺑﺎﻟﺘﺸﻐﻴﻞ ﻗﻢ 3 1 اﻟﺘﻬﻮﻳﺔ ﻓﺘﺤﺎت اﻟﺘﺸﻐﻴﻞ إﻳﻘﺎف ﺑﻌﺪ دﻗﺎﺋﻖ 3 ﳌﺪة اﻟﺘﺸﻐﻴﻞ إﻋﺎدة ﻋﻤﻠﻴﺔ ﺗﻌﻄﻴﻞ ﻋﻠﻰ اﻟﻨﻈﺎم ﻳﻌﻤﻞ وﻗﺎﺋﻲ ﻛﺈﺟﺮاء دﻗﺎﺋﻖ 10 ﳌﺪة اﻟﻬﻮاء ﺧﺮوج ﻳﺘﻢ ﻟﻦ اﳊﺎﻻت ﺑﻌﺾ ﻓﻲ اﻟ...

Reviews: