12

Wiring

WARNING

• Do not use tapped wires, stranded wires, extension cords, or starburst connections, as they may cause overheating, electrical 

shock, or fire.

• Do not use locally purchased electrical parts inside the product. (Do not branch the power for the drain pump, etc., from the ter-

minal block.) Doing so may cause electric shock or fire.

• Be sure to install an earth leakage breaker. (One that can handle higher harmonics.)

(This unit uses an inverter, which means that an earth leakage breaker capable of handling harmonics must be used, in order 
to prevent malfunctioning of the earth leakage breaker itself.)

• Use an all-pole disconnection type breaker with at least 3 mm between the contact point gaps.
• Do not connect the power wire to the indoor unit. Doing so may cause electric shock or fire.

Equipment complying with EN/IEC 61000-3-12

(1)

 

according to the following table:

• Do not turn on the safety breaker until all work is 

completed.

1) Strip the insulation from the wire (20mm).
2) Connect the inter-unit wires between the indoor 

and outdoor units 

so that the terminal numbers 

match

. Tighten the terminal screws securely. 

We recommend a flathead screwdriver be used 
to tighten the screws. The screws are packed 
with the terminal board.

3) Pull the wire and make sure that it does not disconnect. Then fix the wire in place with a wire stop.

n

Earth

This air conditioner must be earthed.
For earthing, follow the applicable local standard for electrical installations.

(1) European/International Technical Standard setting the limits for harmonic currents produced by equipment connected to 

public low-voltage systems with input current >16 A and 

75 A per phase.

Model

Compliance with EN/IEC 61000-3-12

3MXS40K3V1B2

NO

3MXS52E4V1B2

YES

3AMX52E4V1B2

YES

Safety breaker

Earth leakage
circuit breaker

Outdoor unit

50Hz 
220-240V

Be sure to use the dedicated circuits.

To room B

To room C

To room D

Inter-unit wire
4-core 1.5mm² or more
H05RN

Room

A

Room A

Room

C

Room

D

Room

B

Indoor unit

Power supply wire
3-core 2.5mm² or more
H05RN

L

N

Shape the wires so that 
there is no lifting of the 
service hatch or other 
structural parts.

Secure the branch wiring firmly using 

the 4 

included screws

, as shown in the figure.

Secure firmly, making sure no outside pressure is 
exerted on the terminals.

Use the specified wires and 
connect them securely.

CAUTION

When connecting the connection wires to the 
terminal board using a single core wire, be sure 
to perform curling.
Problems with the work may cause heat and fires.

Good

Wrong

Good

Wrong

• Ground terminal installation

Use the following method when installing the round 
crimp-style terminal.

Round crimp-
style terminal

Flat washer

Screw

Flat washer

Round crimp-
style terminal

Screw

Summary of Contents for 3MXS40K3V1B2

Page 1: ...INSTALLATION MANUAL R410A Split Series Models 3MXS40K3V1B2 3MXS52E4V1B2 3AMX52E4V1B2...

Page 2: ...Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 0...

Page 3: ......

Page 4: ...ng terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes into contact with fire After completing installation check f...

Page 5: ...ty atmosphere of sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moistu...

Page 6: ...ne Wrap the insulation pipe with the finishing tape from bottom to top Caulk pipe hole gap with putty Foot bolt hole centres 580 Foot bolt hole centres 330 250mm from wall Allow space for piping and e...

Page 7: ...52 Up to 9 0kW Precautions on Installation Check the strength and level of the installation ground so that the unit will not cause any operating vibration or noise after installed In accordance with t...

Page 8: ...the piping is as short as possible Shortest allow able length per room is 3m Outdoor unit capacity class 3MXS40 3MXS52 3AMX52 Piping to each indoor unit 25m max Total length of piping between all unit...

Page 9: ...ce of the flare Use refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the...

Page 10: ...etely close its high pressure valve Hi High pressure valve subsequently requires no operation 3 Apply vacuum pumping Check that the compound pressure gauge reads 0 1MPa 76cmHg Evacuation for at least...

Page 11: ...k out do not leave the flare nut removed for a long period of time Outdoor capacity class 3MXS40 3MXS52 3AMX52 Total length of piping for all rooms 30m Filling a cylinder with an attached siphon Stand...

Page 12: ...ould reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Never install a dryer to this R410A unit in order...

Page 13: ...readed connection port of the outdoor unit where the flare nut comes in Use an appropriate wrench to avoid damaging the connection thread by overtightening the flare nut Flare nut tightening torque Fl...

Page 14: ...the liquid stop valve with a hexagonal wrench 4 After two to three minutes close the gas stop valve and stop forced cooling operation 1 Forced operation 1 Turn the Operation Mode switch SW2 to COOL 2...

Page 15: ...make sure that it does not disconnect Then fix the wire in place with a wire stop n Earth This air conditioner must be earthed For earthing follow the applicable local standard for electrical installa...

Page 16: ...perating all other indoor units do not operate and enter standby mode according to the operation mode of the set indoor unit 1 2 Priority during high power operation If the indoor unit which is set fo...

Page 17: ...ed Setting procedure Remove the SW5 jumper switch Once the settings are complete reset the power NOTE Install the removed jumper switch as described below This switch will be needed to later disable t...

Page 18: ...OTE 1 For two rooms LED 3 and 4 are not displayed and for three rooms LED 4 is not displayed 2 If the outside air temperature is 5 C or less the wiring error check function will not operate 3 After wi...

Page 19: ...ers operation procedures and temperature adjustment Even when the air conditioner is not operating it consumes some electric power If the customer is not going to use the unit soon after it is install...

Page 20: ...3P401524 2 2015 02 Copyright 2015 Daikin...

Reviews: