3
|
Specific installer safety instructions
Installer reference guide
19
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1C – 2020.08
WARNING
▪
Do NOT use locally purchased electrical parts inside the product.
▪
Do NOT branch the power supply for the drain pump, etc. from the terminal
block. This could result in electrical shock or fire.
WARNING
Keep the interconnection wiring away from copper pipes without thermal insulation
as such pipes will be very hot.
DANGER: RISK OF ELECTROCUTION
All electrical parts (including thermistors) are powered by the power supply. Do not
touch them with bare hands.
DANGER: RISK OF ELECTROCUTION
Disconnect the power supply for more than 10 minutes, and measure the voltage at
the terminals of main circuit capacitors or electrical components before servicing.
The voltage MUST be less than 50 V DC before you can touch electrical components.
For the location of the terminals, see the wiring diagram.
Finishing the outdoor unit installation (see
"10 Finishing the outdoor unit
)
DANGER: RISK OF ELECTROCUTION
▪
Make sure that the system is earthed properly.
▪
Turn off the power supply before servicing.
▪
Install the switch box cover before turning on the power supply.
Maintenance and service (see
DANGER: RISK OF ELECTROCUTION
DANGER: RISK OF BURNING/SCALDING
WARNING
▪
Before carrying out any maintenance or repair activity, ALWAYS switch off the
circuit breaker on the supply panel, remove the fuses or open the protection
devices of the unit.
▪
Do NOT touch live parts for 10 minutes after the power supply is turned off
because of high voltage risk.
▪
Please note that some sections of the electric component box are hot.
▪
Make sure you do NOT touch a conductive section.
▪
Do NOT rinse the unit. This may cause electric shocks or fire.