9
|
Electrical installation
Installer reference guide
55
3(A)MXM+3(A)MXF+4MXM+5MXM
R32 Split series
4P600463-1C – 2020.08
Model
A
B
4MXM80
3- core cable 4.0 mm
2
H07RN-F (60245 IEC 66)
25 A
5MXM90
32 A
Electrical equipment must comply with EN/IEC 61000-3-12, the European/
International Technical Standard setting the limits for harmonic currents produced
by equipment connected to public low-voltage systems with input current >16 A
and ≤75 A per phase.
9.2 To connect the electrical wiring to the outdoor unit
1
Remove the switch box cover (1 screw).
1
2
1×
2
Strip insulation (20 mm) from the wires.
a
b
a
Strip wire end to this point
b
An excessive strip length may cause electrical shock or leakage
3
Connect the wires between the indoor and outdoor units so that the terminal
numbers match. Make sure to match the symbols for piping and wiring.
4
Make sure to connect correct wiring to correct room.
e
-B
e
-E
e
-C
e
-D
a
-A
e
-A
a
-C
a
-D
a
-E
a
-B
b
c
d
a
Terminal for room (A, B, C, D, E)*
b
Circuit breaker
c
Earth leakage circuit breaker
d
Power supply wire
e
Interconnection wire for room (A, B, C, D, E)*
*May differ depending on the model.
5
Tighten the terminal screws securely using a Philips screwdriver.
6
Check that the wires do not disconnect by pulling them lightly.
7
Firmly secure the wire retainer to avoid external stress on wire terminations.
8
Pass the wiring through the cutout on the bottom of the protection plate.