background image

5

n

English

Outdoor Unit Installation Guideline

• Where a wall or other obstacle is in the path of outdoor unit’s inlet or outlet airflow, follow the installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 1200mm or less.

Selecting a Location for Installation of 

the Indoor Units

• The maximum allowable length of refrigerant piping, and the maximum allowable height difference between the outdoor and 

indoor units, are listed below.
(The shorter the refrigerant piping, the better the performance. Connect so that the piping is as short as possible. 

Shortest allow-

able length per room is 3m.

Piping to each indoor unit

20m max.

Total length of piping between all units

30m max.

If the outdoor unit is positioned higher than the 
indoor units.

If the outdoor unit is positioned otherwise.
(If lower than one or more indoor units.)

More than 50

More than 100

Side view

Direction 
of air

1200
or less

Wall facing one side

Top view

More than 150

More than 300

More than 50

unit: mm

Walls facing three sides

Top view

More than 50

More than 50

More than 150

More 
than 100

Walls facing two sides

Level  
difference: 
15m max.

Level  
difference: 
7.5m max.

Indoor Unit

Outdoor Unit

Level 
difference: 
7.5m max.

Level  
difference: 
15m max.

Outdoor Unit

Indoor Unit

Summary of Contents for 2MXS40H3V1B2

Page 1: ...English T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A...

Page 2: ...Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 0...

Page 3: ......

Page 4: ...f the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refriger...

Page 5: ...f sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot...

Page 6: ...ng base optional parts Clamping material Insulation tube Service lid Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from gettin...

Page 7: ...ation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundati...

Page 8: ...formance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 9: ...e of the flare Use refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the f...

Page 10: ...pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does go back this may indicate the presence of...

Page 11: ...refrigerant may slowly leak out do not leave the flare nut removed for a long period of time Do not overfill with refrigerant This will break the compressor Filling a cylinder with an attached siphon...

Page 12: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 13: ...inuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 14: ...e sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the...

Page 15: ...bend the electric box hook 4 Remove the lower electric box cover 5 Cut the jumper J3 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAUTION...

Page 16: ...t the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when th...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P401524 1 2015 02 Copyright 2015 Daikin...

Reviews: