background image

7

n

English

Refrigerant Piping Work

4.

Purging air and checking gas leakage

WARNING

• Do not mix any substance other than the specified refrigerant (R410A) into the refrigeration cycle.
• When refrigerant gas leaks occur, ventilate the room as soon and as much as possible.
• R410A, as well as other refrigerants, should always be recovered and never be released directly into the environment.
• Be sure to check for gas leaks.

• When piping work is completed, it is necessary to purge the air and check for gas leakage.
• Be sure to perform vacuum pumping for all the rooms at the same time.
• Be sure to use the special tools for the R410A (gauge manifold, charge hose, vacuum pump, vacuum pump adapter, etc.).
• Use a hexagonal wrench (4mm) to operate the stop valve rod.
• All refrigerant pipe joints should be tightened with a torque wrench at the specified tightening torque. 

1) Connect the charge hose protrusions (the side for pushing the pin) for low pressure and high pressure on the gauge manifold to 

the gas stop valve service port for rooms 

A and B

.

2) Fully open gauge manifold’s low-pressure valve (Lo) and high-pressure valve (Hi).

3) Apply vacuum pumping for 20 minutes or longer. Check that the compound pressure gauge reads –0.1MPa (–76cmHg).

4) After checking the vacuum, close the low pressure and high pressure valves on the gauge manifold and stop the vacuum 

pump. (Leave as is for 4-5 minutes and make sure the coupling meter needle does not go back. ) If it does go back, this may 
indicate the presence of moisture or leaking from connecting parts.
After inspecting all the connection and loosening then retightening the nuts, repeat steps 2)

 →

 3)

 →

 4).

5) Remove the valve caps on the liquid and gas stop valves at the pipes for rooms A and B.

6) Open the valve rods on the liquid stop valves for rooms A and B by turning them 90° counterclockwise using a hex wrench. 

Close them 5 seconds later and check for gas leaks.
After checking for gas leaks, check the areas around flares on the indoor unit, and the areas around flares and valve rods on 
the outdoor unit by applying soapy water.
Wipe down thoroughly after the check is complete.

7) Remove the charge hose from the gas stop valve service ports at the pipes for rooms A and B and completely open the liquid 

and gas stop valves at the pipes for rooms A and B. 
(Stop the valve rods as far as they go and do not attempt to turn them any further.)

8) Use a torque wrench to tighten the valve caps and service port caps on the liquid and gas stop valves at the pipes for rooms A 

and B to the designated torque.

Room B gas 
stop valve

Room B liquid 
stop valve

Room A gas 
stop valve

Room A liquid 
stop valve

Valve cap

Service port

Compound 
gauge

Gauge manifold

Low-pressure valve

High-pressure valve

Charge hose

Vacuum pump

Vacuum pump adapter

Summary of Contents for 2MXS40H3V1B2

Page 1: ...English T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S rie split R410A Montagehandleiding R410A...

Page 2: ...Certificado C 06 Nota delineato nel A e giudicato positivamente da B secondo il Certificato C 07 A B C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 0...

Page 3: ......

Page 4: ...f the control box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refriger...

Page 5: ...f sulfate gas corrosion may shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot...

Page 6: ...ng base optional parts Clamping material Insulation tube Service lid Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent air from gettin...

Page 7: ...ation bolts Prepare 4 sets of M8 or M10 foundation bolts nuts and washers each which are available on the market It is best to screw in the foundation bolts until their ends are 20mm from the foundati...

Page 8: ...formance Connect so that the piping is as short as possible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor...

Page 9: ...e of the flare Use refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the f...

Page 10: ...pressure valves on the gauge manifold and stop the vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does go back this may indicate the presence of...

Page 11: ...refrigerant may slowly leak out do not leave the flare nut removed for a long period of time Do not overfill with refrigerant This will break the compressor Filling a cylinder with an attached siphon...

Page 12: ...on flared part Prevent mineral oil from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are...

Page 13: ...inuously The units in both rooms will start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the...

Page 14: ...e sure to use the round crimp style terminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the...

Page 15: ...bend the electric box hook 4 Remove the lower electric box cover 5 Cut the jumper J3 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAUTION...

Page 16: ...t the manual included with the indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when th...

Page 17: ......

Page 18: ......

Page 19: ......

Page 20: ...3P401524 1 2015 02 Copyright 2015 Daikin...

Reviews: