background image

English

2

Accessories

Accessories supplied with the outdoor unit:

Precautions for Selecting the Location

1) Choose a place solid enough to bear the weight and vibration of the unit, where the operation noise will not be amplified.
2) Choose a location where the hot air discharged from the unit or the operation noise, will not cause a nuisance to the 

neighbors of the user.

3) Avoid places near a bedroom and the like, so that the operation noise will cause no trouble.
4) There must be sufficient spaces for carrying the unit into and out of the site.
5) There must be sufficient space for air passage and no obstructions around the air inlet and the air outlet.
6) The site must be free from the possibility of flammable gas leakage in a nearby place. 

Locate the unit so that the noise and the discharged hot air will not annoy the neighbors.

7) Install units, power cords and inter-unit wires at least 3m away from television and radio sets.  This is to prevent interfer-

ence to images and sounds.  (Noises may be heard even if they are more than 3m away depending on radio wave con-
ditions.)

8) In coastal areas or other places with salty atmosphere of sulfate gas, corrosion may shorten the life of the air condi-

tioner.

9) Since drain flows out of the outdoor unit, do not place under the unit anything which must be kept away from moisture.

NOTE:

Cannot be installed hanging from ceiling or stacked.

 CAUTION

When operating the air conditioner in a low outdoor ambient temper-
ature, be sure to follow the instructions described below.
• To prevent exposure to wind, install the outdoor unit with its suc-

tion side facing the wall.

• Never install the outdoor unit at a site where the suction side may 

be exposed directly to wind.

• To prevent exposure to wind, it is recommended to install a baffle 

plate on the air discharge side of the outdoor unit.

• In heavy snowfall areas, select an installation site where the snow 

will not affect the unit.

Installation Manual 

There is on the bottom packing case.

1

Refrigerant charge label

There is on the bottom packing case.

1

Drain plug  (heat pump models)

There is on the bottom packing case.

1

Multilingual fluorinated greenhouse gases label 

There is on the bottom packing case.

1

Screw bag (for fixing the wire retainer) 

There is on the bottom packing case.

1

Reducer assembly (only 50 class) 

There is on the bottom packing case.

1

A

B

C

D

E

F

Construct a large canopy.

Construct a pedestal.

Install the unit high enough off the 

ground to prevent burying in snow.

01_EN_3P210724-1F.fm  Page 2  Tuesday, October 30, 2012  10:39 AM

Summary of Contents for 2MXS40G2V1B

Page 1: ...Nederlands Espa ol Italiano Portugues English T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S ri...

Page 2: ...F2V1B 2MXS40G2V1B 2MXS50G2V1B 2MKS40G2V1B 2MKS50G2V1B 2MXS40H2V1B 2MXS50H2V1B 2MKS40H2V1B 2MKS50H2V1B DAIKIN INDUSTRIES LTD Noboru Murata Manager Quality Control Department 1st of Nov 2008 Low Voltage...

Page 3: ...P6 07 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 10D Shinri Sada Manager Quality Control Department 2MXS40H3V1B 2MXS50H3V1B 2AMX40G3V1B 2AMX50G3V1B Machinery 2006 42 EC Electro...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 5: ...rol box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes...

Page 6: ...shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from c...

Page 7: ...ng Level mounting base optional parts Clamping material Insulation tube Service lid Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent...

Page 8: ...market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer packing shown above be careful not to overtighten the nut or the smaller...

Page 9: ...ssible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher than the indoor units If t...

Page 10: ...refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 tu...

Page 11: ...nifold and stop the vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does go back this may indicate the presence of moisture or leaking from conne...

Page 12: ...t do not leave the flare nut removed for a long period of time Do not overfill with refrigerant This will break the compressor Filling a cylinder with an attached siphon Stand the cylinder upright whe...

Page 13: ...l from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Do never...

Page 14: ...start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the operation to stop 3 Use this method...

Page 15: ...erminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the wire and make sure that it does not d...

Page 16: ...t to bend the electric box hook 4 Remove the lower electric box cover 5 Cut the jumper J4 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAU...

Page 17: ...ove the lower electric box cover 5 Cut the jumper J3 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAUTION When removing the upper electric...

Page 18: ...indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operat...

Page 19: ...1210 HT 3P210724 1F M07B062F Two dimensional bar code is a code for manufacturing 00_CV_3P210724 1F fm Page 2 Tuesday October 30 2012 10 36 AM...

Reviews: