background image

9

English

Refrigerant Piping Work

Precautions for Laying Refrigerant Piping 

• Cautions on pipe handling

1) Protect the open end of the pipe against dust and moisture.
2) All pipe bends should be as gentle as possible. Use a pipe bender for 

bending.

• Selection of copper and heat insulation materials

When using commercial copper pipes and fittings, observe the following:
1) Insulation material:  Polyethylene foam 

Heat transfer rate:  0.041 to 0.052W/mK (0.035 to 0.045kcal/mh°C)

Refrigerant gas pipe’s surface temperature reaches 110°C max.
Choose heat insulation materials that will withstand this temperature.

2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-

sions as below.

3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.

• Flaring the pipe end 

1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing down-

ward so that the chips do not enter the pipe.

3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.

WARNING

• Do not use mineral oil on flared part.
• Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
• Never use piping which has been used for previous installations. Only use parts which are delivered with the unit.
• Do never install a drier to this R410A unit in order to guarantee its lifetime.
• The drying material may dissolve and damage the system.
• Incomplete flaring may cause refrigerant gas leakage.

Gas pipe

Liquid pipe

Gas pipe 

insulation

Liquid pipe 

insulation

O.D.9.5mm

O.D.12.7mm

O.D.6.4mm

I.D.12-15mm

I.D.8-10mm

Minimum bend radius

Thickness 

13mm Min

Thickness 

10mm Min

30mm or 

more

40mm or 

more

30mm or 

more

 Thickness 0.8mm (C1220T-O)

Wall

If no flare cap is 
available, cover 
the flare mouth 
with tape to keep 
dirt or water out.

Be sure to 
place a cap.

Rain

Gas pipe

Liquid pipe

Gas pipe 
insulation

Liquid pipe 
insulation

Finishing tape

Drain hose

Inter-unit wires

(Cut exactly at 

right angles.)

 Remove burrs

Set exactly at the position shown below.

A

Flaring

Die

Check

Flare’s inner 
surface must 
be flaw-free.

The pipe end must 
be evenly flared in 
a perfect circle.

Make sure that the 
flare nut is fitted.

A

0-0.5mm

Clutch-type

Flare tool for R410A

1.0-1.5mm

Clutch-type (Rigid-type)

1.5-2.0mm

Wing-nut type (Imperial-type)

Conventional flare tool

01_EN_3P210724-1F.fm  Page 9  Tuesday, October 30, 2012  10:39 AM

Summary of Contents for 2MXS40G2V1B

Page 1: ...Nederlands Espa ol Italiano Portugues English T rk e Installation manual R410A Split series Montaj k lavuzlar R410A Split serisi Installationsanleitung Split Baureihe R410A Manuel d installation S ri...

Page 2: ...F2V1B 2MXS40G2V1B 2MXS50G2V1B 2MKS40G2V1B 2MKS50G2V1B 2MXS40H2V1B 2MXS50H2V1B 2MKS40H2V1B 2MKS50H2V1B DAIKIN INDUSTRIES LTD Noboru Murata Manager Quality Control Department 1st of Nov 2008 Low Voltage...

Page 3: ...P6 07 2012 DEKRA Certification B V NB0344 74736 KRQ EMC97 4957 3SB65451 10D Shinri Sada Manager Quality Control Department 2MXS40H3V1B 2MXS50H3V1B 2AMX40G3V1B 2AMX50G3V1B Machinery 2006 42 EC Electro...

Page 4: ...3SB65451 4 fm Page 2 Thursday October 27 2011 4 49 PM...

Page 5: ...rol box lid may result in electric shocks fire or over heating terminals If refrigerant gas leaks during installation ventilate the area immediately Toxic gas may be produced if the refrigerant comes...

Page 6: ...shorten the life of the air condi tioner 9 Since drain flows out of the outdoor unit do not place under the unit anything which must be kept away from moisture NOTE Cannot be installed hanging from c...

Page 7: ...ng Level mounting base optional parts Clamping material Insulation tube Service lid Tape Also insulate the connection on the outdoor unit Use tape or insulating material on all connections to prevent...

Page 8: ...market It is best to screw in the foundation bolts until their ends are 20mm from the foundation surface When using the reducer packing shown above be careful not to overtighten the nut or the smaller...

Page 9: ...ssible Shortest allow able length per room is 3m Piping to each indoor unit 20m max Total length of piping between all units 30m max If the outdoor unit is positioned higher than the indoor units If t...

Page 10: ...refrigeration oil for R410A Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas leakage Align the centres of both flares and tighten the flare nuts 3 or 4 tu...

Page 11: ...nifold and stop the vacuum pump Leave as is for 4 5 minutes and make sure the coupling meter needle does not go back If it does go back this may indicate the presence of moisture or leaking from conne...

Page 12: ...t do not leave the flare nut removed for a long period of time Do not overfill with refrigerant This will break the compressor Filling a cylinder with an attached siphon Stand the cylinder upright whe...

Page 13: ...l from getting into the system as this would reduce the lifetime of the units Never use piping which has been used for previous installations Only use parts which are delivered with the unit Do never...

Page 14: ...start 2 Forced cooling operation will end after around 15 minutes and the unit will stop automatically Press the start stop button on the indoor unit to force the operation to stop 3 Use this method...

Page 15: ...erminal for connection to the power supply terminal block Place the round crimp style terminals on the wires up to the covered part and secure in place 3 Pull the wire and make sure that it does not d...

Page 16: ...t to bend the electric box hook 4 Remove the lower electric box cover 5 Cut the jumper J4 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAU...

Page 17: ...ove the lower electric box cover 5 Cut the jumper J3 of the PCB inside 6 Go back through step 4 3 2 1 Make sure all components are well secured when doing this CAUTION When removing the upper electric...

Page 18: ...indoor unit Instruct the customer how to operate the unit correctly particularly cleaning of the air filters operation procedures and temperature adjustment Even when the air conditioner is not operat...

Page 19: ...1210 HT 3P210724 1F M07B062F Two dimensional bar code is a code for manufacturing 00_CV_3P210724 1F fm Page 2 Tuesday October 30 2012 10 36 AM...

Reviews: