Check
SiUS121630EA
200
Service Diagnosis
8.14 Capacitor Voltage Check
Check No.21
Before this check, be sure to check the main circuit for short circuit.
With the circuit breaker still on, measure the voltage according to the drawing of the model in
question. Be careful never to touch any live parts.
To prevent an electrical shock, use a multimeter to check that the voltage between FU2 and
DC– is 50 V or less.
The surface of the test points (DC–) may be covered with the coating. Be sure to make firm
contact between the multimeter probes and the test points.
(R21938)
Multimeter
(DC. voltage range)
FU2
DC–
Coating
PCB
Multimeter probe
(R21939)