SiUS121630EA
Troubleshooting for Outdoor Unit
Service Diagnosis
167
7.5
Anti-icing Control for Indoor Unit
Error Code
A5
Outdoor Unit LED
Display
A
j
1
i
2
h
3
i
4
i
5
h
Method of Error
Detection
During cooling operation, indoor unit icing is detected by checking the temperatures sensed by the
indoor heat exchanger thermistor and room temperature thermistor that are located in a shut-down
room.
Error Decision
Conditions
In cooling operation, the both conditions (A) and (B) are met for 5 minutes.
(A) Room temperature – Indoor heat exchanger temperature
≥
10°C (18°F)
(B) Indoor heat exchanger temperature
≤
–1°C (30.2°F)
If the error repeats, the system is shut down.
Reset condition: 3-minute standby is over and the indoor heat exchanger temperature is above
0°C (32°F)
Supposed
Causes
Wrong wiring or piping
Defective electronic expansion valve
Short-circuited air
Defective indoor heat exchanger thermistor
Defective room temperature thermistor