![background image](http://html.mh-extra.com/html/daikin/2mxm68a2v1b/2mxm68a2v1b_installers-reference-manual_501090032.webp)
7
|
Piping installation
Installer reference guide
32
2MXM-A, 3MXM-A, 4MXM-A, 5MXM-A
R32 Split series
4P600463-5E – 2021.12
7 Piping installation
In this chapter
7.1 Preparing refrigerant piping
7.1.1 Refrigerant piping requirements
INFORMATION
Also read the precautions and requirements in the
CAUTION
Piping and joints of a split system shall be made with permanent joints when inside
an occupied space except joints directly connecting the piping to the indoor units.
NOTICE
The piping and other pressure-containing parts shall be suitable for refrigerant. Use
phosphoric acid deoxidised seamless copper for refrigerant.
▪
Foreign materials inside pipes (including oils for fabrication) must be
≤30 mg/10 m.
Refrigerant piping diameter
2MXM68
Liquid piping
2× Ø6.4 mm (1/4")
Gas piping
1× Ø9.5 mm (3/8")
1× Ø12.7 mm (1/2")
3MXM40, 3MXM52, 3MXM68
Liquid piping
3× Ø6.4 mm (1/4")
Gas piping
1× Ø9.5 mm (3/8")
2× Ø12.7 mm (1/2")